Hitachi Relion 670 Series Product Manual page 126

Line differential protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Line differential protection RED670
Version 2.2
Control
Table 91. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Phase shift, j
- j
line
bus
Voltage high limit for synchronizing and synchrocheck
Reset ratio, synchrocheck
Frequency difference limit between bus and line for synchrocheck
Phase angle difference limit between bus and line for synchrocheck
Voltage difference limit between bus and line for synchronizing and
synchrocheck
Time delay output for synchrocheck when angle difference between bus
and line jumps from "PhaseDiff" + 2 degrees to "PhaseDiff" - 2 degrees
Frequency difference minimum limit for synchronizing
Frequency difference maximum limit for synchronizing
Maximum closing angle between bus and line for synchronizing
Breaker closing pulse duration
tMaxSynch, which resets synchronizing function if no close has been
made before set time
Minimum time to accept synchronizing conditions
Voltage high limit for energizing check
Reset ratio, voltage high limit
Voltage low limit for energizing check
Reset ratio, voltage low limit
Maximum voltage for energizing
Time delay for energizing check when voltage jumps from 0 to 90% of
Urated
Operate time for synchrocheck function when angle difference between
bus and line jumps from "PhaseDiff" + 2 degrees to "PhaseDiff" - 2
degrees
Operate time for energizing function when voltage jumps from 0 to 90%
of Urated
126
M12359-1 v16
Range or value
(-180 to 180) degrees
(50.0-120.0)% of UBase
> 95%
(0.003-1.000) Hz
(5.0-90.0) degrees
(0.02-0.5) p.u
(0.000-60.000) s
(0.003-0.250) Hz
(0.050-1.000) Hz
(15-30) degrees
(0.050-1.000) s
(0.000-6000.00) s
(0.000-60.000) s
(50.0-120.0)% of UBase
> 95%
(10.0-80.0)% of UBase
< 105%
(50.0-180.0)% of UBase
(0.000-60.000) s
Min. = 15 ms
Max. = 30 ms
Min. = 70 ms
Max. = 90 ms
© 2017 - 2022 Hitachi Energy. All rights reserved
1MRK 505 379-BEN R
Accuracy
-
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
-
±2.5 mHz
±2.0 degrees
±0.5% of U
r
±0.2% or ±35 ms whichever is
greater
±2.5 mHz
±2.5 mHz
±2.0 degrees
±0.2% or ±15 ms whichever is
greater
±0.2% or ±35 ms whichever is
greater
±0.2% or ±35 ms whichever is
greater
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
-
±0.5% of U
r
-
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
±0.2% or ±100 ms whichever is
greater
Hitachi Energy

Advertisement

Table of Contents
loading

This manual is also suitable for: