TIMER SETTINGS
The timer function of the series LCT216 takes a signal input to start a timing sequence. The
sequence can be paused using the GATE input or reset using RST1 input. Use the below
parameters and timing functions to configure the timer.
Parameter Configuration
PV
SV
FUnC
timE
t mode
UP
down
t otmd
t Unit
Display
Units
S 001
sec.
S 01
sec.
S 1
sec.
mS 001
min., sec.
mS 01
min., sec.
m 01
Min.
M 1
Min.
HmS
Hr., min., sec.
Hm 1
Hr., min.
H 1
Hr.
T oUt 1
rtSr
inPtLC
Sets the controller to function as a timer.
Sets the display to count up or down.
Sets the output timing functions. See the timing functions
section or page 9 for detail description of each timing
function.
Sets the display units of measure. See below table for a
list of the available units.
Range
Resolution
0.01 to 9,999.99
10 msec.
0.1 to 99,999.9
0.1 sec.
1 to 999,999
1 sec.
0.01 to 9,959.99
10 msec.
0.1 to 99,959.99
0.1 sec.
0.1 to 99,999.9
0.1 min.
1 to 999,999
1 min.
1 to 995,959
1 sec.
1 to 999,959
1 min.
1 to 999,999
1 hr.
Table A: List of Timing Units
Sets the pulse width (t) for output 1. The default output timeis
0.02 seconds. If you wish the system to keep the operation of
the output, please set the output time to 0.00 seconds.
Sets the minimum pulse width at either 1 msec or 20 msec.
Sets the transistor input type to NPN or PNP. For contact input,
the selection can be either PNP or NPN, but the selection will
determine whether the connection is to terminal 11 or terminal 6.
See the input connection diagrams on page 5.
Page 8
Maximum Time
9,999.99 sec.
99,999.9 sec
999,999 sec.
5,999.99 sec.
59,999.9 sec.
99,999.9 min.
999,999 min
359,999 sec. (100 hr.)
599,999 min. (10,000 hr.)
699,999 hr.