GE ASH220NCDWA Service Manual page 35

Ductless multi-split heat pump
Hide thumbs Also See for ASH220NCDWA:
Table of Contents

Advertisement

SW6 DIP Switch Settings
Outdoor central control address settings
Outdoor Central
SW6-1
Control Address
0
OFF
1
OFF
2
OFF
3
OFF
4
OFF
5
OFF
6
OFF
7
OFF
8
ON
9
ON
10
ON
11
ON
12
ON
13
ON
14
ON
15
ON
SW7 DIP Switch Settings
Description
USA energy efficiency test mode for High Wall unit
USA energy efficiency test mode for Duct unit
WJ26X25054 - Service Monitor Board DIP Switch Settings
SW1 DIP Switch Settings
DIP Switch Settings
Topic Title
SW6-2
SW6-3
SW6-4
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
SW7-1 SW7-2 SW7-3 SW7-4 SW7-5 SW7-6 SW7-7 SW7-8
Reserved
Reserved
Reserved
Reserved
North American region
Non-North American region
Quiet operation valid
Definition
Time defrost valid: Defrost initiates if
needed when the compressor has been on
for 10 minutes continuously and 50 minutes
cumulative. Termination conditions are the
*See page B-18 for Wiring Error Check.
OUTDOOR TECHNICAL OVERVIEW
OFF*
OFF*
----
ON
OFF
----
----
OFF*
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
*Factory Default Setting
SW1-1
Factory default
Forced heating
Forced cooling
Rated operation
same as demand defrost.
Wiring check active*
----
----
----
----
----
----
----
----
----
OFF*
----
----
----
OFF*
----
----
----
OFF*
----
----
----
----
----
----
----
----
----
SW1-2
SW1-3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
----
----
----
----
----
----
----
----
----
----
----
----
ON*
----
OFF
----
----
OFF*
SW1-4
OFF
OFF
OFF
OFF
ON
ON
B-23