End of life disposition Ensure that IER electric steam humidifier is empty from water, if not proceed same way as for a standard drain for service. Disconnect IER electric steam humidifier from power supply, electrical control signal, water main supply, Steam line, and drain.
You can also visit our Youtube® channel: youtube/steamovap and watch our 2 minutes IER service/cleaning video. Figure 1, IER one module Informa on contained in this manual is subject to change without no ce. To obtain the latest technical informa on visit our website at steamOvap.com...
Others Risk of flooding. In order to avoid any risk of flooding steamOvap recommends a Hi limit humidity switch installed in the air duct downstream of the steam distribu on ramp.
2. Verify that model of the humidifier matches the purchase order and that all accessories are included. 3. Any missing item should be reported as soon as possible to steamOvap or its representa ve and within 5 business days a er receipt.
Nb of Phase Op ons MB Moun ng Bracket FS Floor Stand Type & Model B BACnet RS485 IER 12 - 208 / 3 - MB RT Roof top enclosure IER electrical rating Power (kW) / Current (A) Steam Model...
Page 8
O V E R V I E W IER Dimensions & weight Figure 3, IER Dimensions, single module Steam outlets Condensate return Drain outlets Water inlet Figure 4, IER Dimensions, two modules, model IER24, 34, 44 & 62...
Page 9
O V E R V I E W Steam Nb Cyl Nb Steam Dimensions Model Outlet + Ø Capacity + size weight 20in 23in 13in 45lb 6.3lb/h 1x 1-1/2in IER02 [2.8kg/h] small [DN40] [510mm] [585mm] [330mm] [21kg] 20in 23in 13in 45lb 10lb/h 1x 1-1/2in...
I N S T A L L A T I O N Installation overview General 1. Installa on of this humidifier should be carried out by trained and qualified personnel. 2. Any work related to installa on of this humidifier must comply with local code and regula on regarding safety and preven on of accidents.
Page 11
I N S T A L L A T I O N Installation steps : 1. Posi oning & moun ng of IER electric steam humidifier 2. Water supply installa on 3. Drain installa on 4. Steam line installa on for duct humidifica on or Direct humidifica on in room...
If local is subject to below freezing point temperature, ac va on of ant freezing func on of the IER steam humidifier is required. For outdoor installa on please contact your steamOvap representa ve to order and install special RT outdoor enclosure for IER.
Page 13
Clearance guidelines There is no minimum clearance on both side of the IER humidifier, however it is a good prac ce to allow a clearance of 4 to 8 in [100 to 200mm] for ease of installa on and service Allow a minimum clearance of 24in [610mm] with floor to allow for proper drain slope and drain...
Page 14
Moun ng holes pa ern Figure 10, moun ng holes double module Figure 9, moun ng holes single module (IER24, 34, 44 & 62) (IER 04 to 31) Moun ng holes posi ons (in) [mm] Model IER02 to 09 ½...
Page 15
Tighten the 3 screws. Re verify the level in the 2 direc on X and Z axis. 5. Re-install the front cover to the humidifier. 6. Op onal Moun ng bracket (op on MB) is available to your steamOvap representa ve in order to ease up wall moun ng process.
Page 16
1. Ensure that the floor structure and strength is appropriate to support the opera ng weight of the IER electric steam humidifier. 2. A ach the floor stand to the floor or structure to avoid any movement of the IER electric steam humidifier.
Water supply pressure: 15 to 80PSI [1 to 5bar] Water supply temperature: 37 to 105°F [3 to 40°C] IER electric steam humidifier can accept a wide range of water quality. Untreated water will lead to scale deposits that will need to be regularly removed from steam chamber.
Page 18
Water supply connection: 1. Install a manual shut off valve (supplied by others) on the water main line. 2. If IER humidifier is supplied with tap water it is recommended to install a 10µ sediment filter (supplied by others) on the line.
Page 20
24in [60cm] must be provided between IER’s module drain outlet and building’s open drain inlet. ✔ Do not reduce diameter of the drain line. Drain line between IER’s module drain outlet and building’s open drain inlet must be 1-1/4in [DN32] diameter minimum ✔...
I N S T A L L A T I O N Installation – step 4 Steam distribution installation SR models for horizontal in duct humidification SRS(X)(E) - steam ramp with slope Main feature: Easiest to install. Not recommended when large quan ty of 5°...
I N S T A L L A T I O N SRS or SRC SRSX or SRCX One row of nozzle Two rows of nozzles 60° Figure 20, SRS or SRC Figure 21, SRSX or SRCX SR models for Vertical duct - Option -V 90°...
Page 23
I N S T A L L A T I O N Minimum distances for SRS & SRSX Horizontal duct Aligned Staggered Figure 26, minimum distance SR in horizontal duct Here are some guidelines to avoid condensing on the duct surface or on SR steam ramps ...
I N S T A L L A T I O N SOS or SOE – steamOsorb, multi-ramp steam grid Top bracket SOS-R vertical steam ramps Condensate return Bottom bracket SOS-H header Figure 28, steamOsorb (SOS or SOE) mul ramp installa on Main features: Made to measure to fit inside ven la on duct;...
8in [200mm] minimum Electric Steam Humidifier Figure 33, Typical SRC, SRCX or SO installa on – with condensate return line to IER Long steam line installation Make sure to install condensate trap(s) at each of the steam line low point(s)
Page 26
[0.06] [0.06] [0.075] steamOvap recommends the use of rigid pipe (stainless steel or copper) for steam line longer than 10 [3m]. When using flexible steam hose, ensure that the hose is maintained and a ached in order to avoid any kink or sagging.
Page 27
Figure 36, steamOsorb mul ramp install lower than IER When SR steam ramp or SO steamOsorb mul ramp is installed lower than the IER humidifier steam outlet, a tee with condensate port must be installed at the lowest point of the steam line.
I N S T A L L A T I O N Installation – step 5 Power supply installation Electrical Warning Risk of electric shock. Disconnect power supply before installa on or service. Power supply connec on must be done by a trained and qualified electrician. ...
Page 29
(supplied by others) is installed on the power supply line. 4. This disconnec ng device should be installed in proximity of the IER steam humidifier (within 3 feet [1 m]) and must be easily accessible.
For system that needs very accurate RH% control a RH% sensor can replace or supplement the On/Off Hi Limit humidistat in this case the IER humidifier will not only modulate the steam produc on based on the control; signal demand but also on this propor onal Hi- Limit signal.
Page 31
1. Ensure that the safety contact for Air proving switch and Hi limit humidistat are connected to the terminals 4 and 5. 2. Connect the applicable controls according to the above wiring diagram 3. Selec on of control signal is done through set-up screens once the IER will be powered.
Risk of flooding. In order to avoid any risk of flooding steamOvap recommends a Hi limit humidity switch installa on in the air duct downstream of the steam distribu on ramp.
C O N F I G U R A T I O N & O P E R A T I O N Configuration & Operation Dashboard screen Dashboard screen is also the main/home screen Demand & output in lb/h or % Edit button allows to configurate Activity log Output in power (Watt)
Page 34
C O N F I G U R A T I O N & O P E R A T I O N Overview screen Overview screen gives all informa on on internal sensors and control se ngs and allow ordering a drain for service Drain for service is initiated when start button is pushed...
Page 35
IER, if latched will need manual reset by service technician, otherwise it will auto reset when abnormal condi on is over. Alarm level 2, non-cri cal alarm will not stop opera on of IER, auto reset as soon as default is over.
Page 36
Control Setting screen Control se ng screen allows user typically a control engineer to set signal and parameters to control the IER humidifier. Access to this screen can be restricted with pass-code. In this case password is 3549 Pop up to enter password...
Page 37
C O N F I G U R A T I O N & O P E R A T I O N Control se ng / control config Control Se ng menu is subdivided in 4 screens: Control Config •...
Page 38
C O N F I G U R A T I O N & O P E R A T I O N Control se ng / setpoint & output config Select the setpoint source from : Internal External Remote If internal, set the Setpoint with cursor Or, if external, set the...
Page 39
C O N F I G U R A T I O N & O P E R A T I O N Control se ng / Hi Limit config Select RH% Hi Limit source from : On/Off demand External analog demand Both If internal, set the Setpoint with cursor...
Page 40
C O N F I G U R A T I O N & O P E R A T I O N Control se ng / Scheduler Information on current Date & time of the internal clock Scheduler can program events based on date and time Event types are : On or Off...
Page 41
C O N F I G U R A T I O N & O P E R A T I O N Humidifier setting screen Humidifier se ng screen allows user (mechanical contractor) to set humidifier parameters. Access to this screen can be restricted with passcode. In this case passcode is 7030 Humidifier Se ng menu is subdivided in 5 screens: Humidifier se ng 1 •...
Page 42
C O N F I G U R A T I O N & O P E R A T I O N Humidifier se ng / se ng 2 Activate Anti-freeze protection in case humidifier is installed in location with risk of Antifreeze function will keep water inside freezing.
Page 43
C O N F I G U R A T I O N & O P E R A T I O N Humidifier se ng / BMS se ng When BMS Override is ON, full control of the humidifier is remote through Modbus or BACnet connection Edit button allows to set the BMS protocol &...
Page 44
C O N F I G U R A T I O N & O P E R A T I O N Humidifier se ng / BMS se ng Activate passcode protection for Control setting menu Activate passcode protection for Humidifier setting menu Edit and set the internal clock date &...
Page 45
Allows for events and data trending exportation Allows to reset all settings to default (factory values) Caution : Do not use this function without technical support from steamOvap support team or representative Figure 54, Humidifier se ng/System informa on...
Page 46
Alarm level 1, cri cal alarm will stop opera on of IER, if latched will need manual reset by service technician. Alarm level 2, non-cri cal alarm will not stop opera on of IER, auto reset as soon as default is over.
90 days, whichever is longer. No liability whatsoever shall be a ached to steamOvap un l said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in wri ng, signed by an officer of steamOvap.
Page 48
2021 steamOvap technologies inc. 1490 Mazure e Montreal, Qc, H4N 1H2 Canada Tel.: +1-844-357-4477 info@steamOvap.com www.steamOvap.com Informa on contained in this manual is subject to change without no ce. To obtain the latest technical informa on visit our website at www.steamOvap.com...