11  Messages
Event no. Display message and cause
7508
< Fan fault >
< Clean fan >
One of the external fans is blocked.
7701 ...
< Self diagnosis > or
7703
< Interference device >
8001
< Derating occurred >
The power supplied by the inverter has
been reduced to below the nominal power
for more than 10 minutes due to excessive
temperature.
8201,
< Interference device >
8203
< Do not pull ESS >
8202
< Connect ESS, do not open cover >
Device disturbance or reverse current in
the PV array.
Wait until dark before disconnecting the
PV array from the inverter in order to
prevent the risk of an electric arc occurring
when the DC connectors are pulled out.
8301,
< Lightn.prot.inactive >
8302
< Chk lightn.prot.A/PE >
< Chk lightn.prot.B/PE >
At least one surge arrester is defective.
8401
< Overheating >
< Disconn. device from generator and grid >
Device disturbance due to overheating in
the inverter. The inverter disconnects on
the AC and DC sides.
9002
< Inst. code invalid >
The SMA Grid Guard code entered
(personal installer password) is not valid.
82
STP8-17TL-IA-en-31
SMA Solar Technology AG
Corrective measures
• Check heat dissipation
(see Section 10.2 "Checking Heat
Dissipation", page 67).
• Contact the SMA Service Line (see
Section 16 "Contact", page 126)
If this event occurs frequently:
• Ensure sufficient ventilation.
• Check heat dissipation
(see Section 10.2 "Checking Heat
Dissipation", page 67).
• Disconnect the inverter after dark
(see Section 9 "Disconnecting the
Inverter from Voltage Sources",
page 63).
• Contact the SMA Service Line
(see Section 16 "Contact",
page 126)
• Plug the Electronic Solar Switch on
right up to the stop.
• Disconnect the inverter after dark
(see Section 9 "Disconnecting the
Inverter from Voltage Sources",
page 63).
• Replace surge arrester
(see Section 12.4 "Replacing Surge
Arresters Type II", page 90).
• Contact the SMA Service Line
(see Section 16 "Contact",
page 126)
• Enter a valid SMA Grid Guard
code.