The Minimal Distance From Flammable Materials - Radijator UNI 25 Instruction Manual

Table of Contents

Advertisement

1.1. The minimal distance from flammable materials

 Ensure the appropriate distance from flammable materials, if necessary provide
protection for them.
 The minimal distance from flammable materials is regulated by law – please seek
information from the professionals whose profession is heating and chimneys.
 The minimal distance between the boiler and flue gas discharge pipes from the
materials of low and average flammability should be at least 100mm.
 The minimal distance from the easily flammable materials is 200mm and the same
applies to the materials of an unknown flammability rate.
Fire hazard!
 Storing flammable materials and liquids close to the boiler is forbidden.
 It is mandatory to inform users of
the necessary minimal distance
between flammable materials and
the boiler.
Radijator Inženjering d.o.o, 36000 Kraljevo, Živojina Lazića - Solunca br.6, Srbija
tel. +381 36 399 140, fax. +381 36 399 150, http://www.radijator.rs
Combustibility of Construction materials
A ...
inflammable
B ...
Not easily flammable
C1 ...
Slow burn rate
C2 ...
Avarage burn rate
C3 ...
Easily flammable
e-mail: radijator@radijator.rs
asbestos, stone, building stone,
ceramic wall tiles, terracotta, stucco,
glazed concrete (without organic
additives)
drywall, glass fibers, and isolation
panels (AKUMIN, IZOMIN,
RAJOLIT, LIGNOS, VELOKS,
HERAKLIT)
beech and oak wood, composite
wood, felt, and isolation panels
(HOBREKS,VERZALIT,
UMAKARTA)
pine wood, larch wood, and fir
wood, composite materials
asphalt, cardboard, cellulose
materials, particleboard, cork,
polyurethane, polystyrene,
polypropylene, polyethylene, floor
fibers