THE C650 SERIES An uninterruptible power supply (UPS) incorporating online double conversion technology, which eliminates all mains power disturbances and IOT software C650/C650R USER MANUAL www.certaups.com For assistance, please contact your local A COMPLETE INSTALLATION CertaUPS partner. AND USER GUIDE...
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit). C650 & C650R User Manual Page 6...
Battery Module provided with the UPS to maintain an identical level of performance and safety. This is a category C3 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures. C650 & C650R User Manual Page 7...
Electrical and Electronic Equipment (WEEE). Battery This product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed to comply with regulations and given correct disposal. C650 & C650R User Manual Page 8...
WLAN module WLAN module (C-WIFI) Wireless connection for IoT COMM Cable RS232 CABLE For RS232 communication Parallel Kit For parallel system installing See in chapter 4.0 Battery cable Battery cable (16 batt.) 1.8m length, C650 & C650R User Manual Page 9...
2.2 PRESENTATION 2.2.1 C650 Tower Model: UPS Module Front view ventilation area LCD module, including 2(1) button 2(2) LCD screen 2(3) LED indicator Tower UPS Tower UPS 6-10kVA C model 6-10kVA B model C650 & C650R User Manual Page 10...
Page 9
C650-100-C EBM (EXTERNAL BATTERY MODULE) FRONT VIEW Ventilation area 1. EBM port 1 EBM label 2. EBM port 2 3. Fuse board cover (replace EBM fuse) iii. 4. EBM detection Box (RJ45 port) C650 & C650R User Manual Page 11...
If you discover damage after acceptance, file a claim for concealed damage. Tower 6/10 kVA C model Tower 6/10kVA B model Tower EBM Rack UPS Rack EBM C650 & C650R User Manual Page 13...
Identify the final position and keep ‘2U’ space for this installation. 1.Install the rail kit (if configured). This rail kit is '2U & with screw holes (M5)', the depth of the rail kit is: 443-773 mm. C650 & C650R User Manual Page 15...
Page 14
Fasten the rail kit to the cabinet with 8pcs M5 screws + washers (as below): 2.Install ‘Rack ear’ to the unit by the M4 screws (flat head) 3.Slide the unit into ‘rail kit’ and ensure ‘rack mounting screw’ is tight. C650 & C650R User Manual Page 16...
Page 15
1. Set up the ‘Extension plate’ as below and install it to ‘Tower foot’ from UPS. 2. Place the UPS & EBM into ‘Tower foot’ individually: Place the EBM module to UPS’s right side and align with the front panel. C650 & C650R User Manual Page 17...
This type of connection must be carried out by a qualified electrical person. Before carrying out any connection, check that the upstream protection devices (Normal AC source and Bypass AC source) are open "O" (Off). Always connect the ground wire first. C650 & C650R User Manual Page 18...
To ensure the cables are well fixed, it is recommended to tie these cables to the convex of the rear panel. 3.4.3 Wiring with external battery module (C650 / C650R EBM) (DC source to UPS) 1. Make sure the UPS is completely off before connecting or disconnecting the EBM.
3.4.4 Wiring with Rackmounted bypass Rackmount bypass is an optional extra, to implement the maintenance bypass switching function to ensure that the output of the system is not affected during the UPS maintenance. C650 & C650R User Manual Page 20...
In parallel, the mechanical installation for each module is the same as the single system. For more details, please refer to Chapter 3.3. Parallel system AC cable diagram: 4.1 WIRING FOR AC CABLE Tower model parallel system Rack model parallel system C650 & C650R User Manual Page 21...
Turn on the input breakers for the parallel UPS. Pressing the button continuously for one UPS of the system, then the system will start to turn on and enter line mode and the system will work normally in parallel. C650 & C650R User Manual Page 22...
Press to exit present menu to Main menu or the higher- menu level menu without changing a setting Press the button to mute the buzzer temporarily, once Mute buzzer new warning or fault is active, buzzer will work again C650 & C650R User Manual Page 23...
Overload or fault has occurred, or a command has been received, and the UPS is Bypass mode in Bypass mode. Battery test UPS is executing a battery test Battery fail The UPS detects bad battery or battery disconnected C650 & C650R User Manual Page 24...
Date and time 00:00 hh:mm LCD contrast [0-100%] Modbus TCP [Enabled], [Disabled] Disabled IoT Enable [Yes], [No] Note: if the utility power is an IT earthing system, the site wiring fault function should be disabled. C650 & C650R User Manual Page 26...
Before using this feature, the UPS must have been powered by utility power with output enabled at least once. Battery start can be disabled. See the ‘Cold start’ setting in ‘start/restart’. 5.7 UPS SHUTDOWN C650 & C650R User Manual Page 27...
60 V DC/30 V AC 20 mA max Dry Out Dry out is the relay out, dry out function can be configured (see Settings > Dry out). Dry out Comments Connector type 1.3mm Maximum wires Inner Relay specification 24Vdc/1A C650 & C650R User Manual Page 28...
2. Enable the IoT function in LCD (see Settings -> IoT) 3. Search for the CertaUPS App from Google Play Store or Apple APP store, download and install. 4. Open the app, register an account, log in, follow the instructions of the app.
6.6 SOFTWARE 6.6.1 Winpower The C650 series is compatible with WinPower which is an open source, online UPS monitoring and management software tool. Key features: • Power flow display for monitoring UPS status • Scheduled system shutdown / restart •...
WinPower View is a mobile app that allows you to centralise monitored UPS by connecting them to the cloud. Please download it from the Google Play Store or Apple APP store. Please refer to chapter 6.3 for IoT connection C650 & C650R User Manual Page 31...
Store the equipment in a cool, dry, clean environment Ensure the batteries are recharged every six months for a minimum of 48 hours Ensure EBMs are recharged every six months for a minimum of 3 hours C650 & C650R User Manual Page 32...
THE EBM IS HEAVY AND REQUIRES A MINIMUM OF 2 PEOPLE TO LIFT INTO RACKING. For the C650 tower module: Turn the MBS to bypass and switch off the input and then replace the EBM(s). For the C650R rotation module: If a PDU is connected to the UPS, turn the MBS to bypass and switch off the input, it is then safe to replace the EBM(s).
For more information contact your local recycling centre. DO NOT discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal contact your local recycling centre. C650 & C650R User Manual Page 34...
TROUBLESHOOTING The C650 series is designed for durable, automatic operation. It also provides alerts whenever potential operating problems occur. ALARMS SHOWN ON THE CONTROL PANEL DO NOT MEAN THAT THE OUTPUT POWER IS AFFECTED. INSTEAD THEY ARE PREVENTIVE ALARMS INTENDED TO ALERT THE USER •...
Page 34
Check if the input breaker is closed. though system is connected to mains power supply Green LED is not on Inverter not switched on Press On-Switch to turn on UPS. even though the power supply is available C650 & C650R User Manual Page 36...
45Hz-55Hz (50Hz system), 54Hz-66Hz (60Hz system) @ load>60% Power Factor Rated current (20pcs battery) OUTPUT Voltage Regulation (AC Mode) 220/230/240V AC Rated Frequency 50 Hz / 60 Hz Power Factor Voltage accuracy ±1% C650 & C650R User Manual Page 37...
Page 36
Winpower, CertaUPS App PHYSICAL Dimension (WxDxH) mm 225 x 416 x 589 225 x 416 x 354 225 x 416 x 589 225 x 416 x 354 Net weight (Kg) IP Protection Level IP20 ENVIRONMENT C650 & C650R User Manual Page 38...
Page 37
113A for 200ms max 105%-125% Load, 10 minutes transfer to Bypass; Overload Capacity 125%-150% Load, 30 seconds transfer to Bypass; >150% Load, 0.5 seconds transfer to Bypass BATTERY Voltage 192 / 240V DC selectable C650 & C650R User Manual Page 39...
Page 38
CE, IEC/EN 62040, UKCA (1) In CVCF mode, UPS needs to be de-rated to 60% capacity (rated output power and maximum charging current). (2) @ 220VAC input phase voltage, rated output power and maximum charging. C650 & C650R User Manual Page 40...
Page 39
A FULL GLOSSARY OF TERMS CAN BE FOUND AT: WWW.CERTAUPS.COM/SUPPORT/UPS-GLOSSARY/ FOR FURTHER INFORMATION OR ASSISTANCE, PLEASE CONTACT YOUR CertaUPS REPRESENTATIVE OR VISIT: WWW.CERTAUPS.COM C650 & C650R User Manual Page 41...