See Installation instructions for more safety precautions.
•
Refer to the appropriate Parts Catalog for part number information.
•
Models listed on page 3.
AE/AH 18,000
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does
not assume any responsibility for property damage or personal injury due to improper service
procedures or services performed by an unqualified person.
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.
Page 1
TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU AL TECHNICAL MANU TECHNICAL MANU AE/AH R410A Window Air Conditioners & Heat Pumps • All safety information must be followed. See Installation instructions for more safety precautions. • Refer to the appropriate Parts Catalog for part number information. •...
PRODUCT IDENTIFICATION The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. 09 3 E 35 A X MAJOR/MINOR DESIGN REV. BASIC MODEL TYPE AE = Electric Heat TTW AH = Heat Pump TTW COOLING CAPACITY 09 = 9000 BTUH...
Page 3
PRODUCT IDENTIFICATION The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. AE093E35AX AH093E35AX AE123E35AX AH123E35AX AE183E35AX AH183E35AX AE093G35AX AH183G35AX AE183G35AX AH093G35AX AE123G35AX AH123G35AX HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
1-877-376-0214 (U.S. and Canada only). If your problem cannot be resolved by Location and Clearances phone, contact an authorized Amana brand servicer. ® Be sure electrical service is adequate for chosen model of Contact and service will be at your expense.
WIRING DIAGRAMS AE[093-123][E/G]35AX HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 16
WIRING DIAGRAMS AE183[E/G]35AX HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 17
WIRING DIAGRAMS AH[093-123][E/G]35AX HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 18
WIRING DIAGRAMS AH183[E/G]35AX HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
TROUBLESHOOTING CODE STATUS CORRECTIVE ACTION Outdoor ambient thermostat Replace or re-connect the thermostat not registering on the board. Outdoor ambient thermostat Replace or re-connect the thermostat not registering on the board. Outdoor coil thermostat Replace or re-connect the thermostat not registering on the board Indoor discharge thermostat Replace or re-connect the thermostat not registering on the board...