Panasonic WH-SDF09C3E5 Service Manual page 128

Air-to-water heatpump
Hide thumbs Also See for WH-SDF09C3E5:
Table of Contents

Advertisement

17.5.33 Outdoor Current Transformer Open Circuit (F46)
Malfunction Decision Conditions:
A current transformer (CT) open circuit is detected by checking the compressor running frequency (≥ rated
frequency) and CT detected input current (< 0.65A) for continuously 20 seconds.
Malfunction Caused:
1
CT defective.
2
Faulty outdoor unit PCB.
3
Compressor defective (low compression).
Abnormality Judgment:
Continue 3 times in 20 seconds.
128

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents