The device may be operated only in properly installed condition. Improper use Any other use is considered improper. Especially to note: akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
To avoid damage to the device, keep the device in the warm environment for at least 1 hour before powering on. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
To configure the module over Ethernet: 1. Connect the Ethernet connector of the device to PC over the Ethernet connection cable (not included). akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
3. Set the parameter Apply new time = 0 and hold the value for at least 1 second. The time value cannot be changed more than once per second. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
5. If you want to check the new parameters or continue configuring the device, you must add it again to the project with the new network parameters. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Range Default value Access Update period Status update time interval 1…60 s Status 32-bit status code 0…4294967295 − akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Maximum sampling rate adjusted to the minimum possible for the On / Off selected input signal (Sect. 4.8.1) akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Lower measuring limit to 00.00, and in the Upper measuring limit to 25.00. Then, the pro- cessing and display of readings will be carried out in atmospheres. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Measurement results of the input signals are presented in two formats (Tab. 4.6): AIn REAL – 4-byte floating point value AIn INT – 2-byte integer value where akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
The input circuit provides an optional correction of the measured values for thermocouples using the refer- ence (cold) junction temperature compensation (CJC). The cold junction temperature is measured by three akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
When using the MQTT protocol, it is recommended to set the parameter "Safe state timeout" (“Modbus Slave” group) to 0, since writing is usually event-driven and not cyclic in this case. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Page 20
Obtained value: measured values of all analog inputs. The topic is equivalent to the group of topics: MX210/Device/GET/AI1/VALUE MX210/Device/GET/AI2/VALUE MX210/Device/GET/…/VALUE MX210/Device/GET/AI8/VALUE akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
There is no password by default. If you forgot the password, restore the factory settings (Sect. 6). akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Signal cables should be routed separately or screened from the supply cables. Shielded cable should be used for the signal lines. − akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Three-wire cable, wires of equal length and cross-section Thermocouple (compensating) cable Current signal Two-wire cable Voltage signal Two-wire cable Resistance signal Two-wire cable akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Page 24
Turn the DIP switch in “0” position when using a non-current sensor. Otherwise the measured values will be calculated incorrectly. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Page 25
The status of the input connected with two switch contacts is represented as an integer in the range 0…3 (Tab. 5.3). Table 5.3 Digital input status Status open open open closed closed open closed closed akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
If the module fails (device error or power supply loss), the data is transferred directly from connector − 1 to connector 2 (auto-bypass). Fig. 5.12 Chain topology akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Using a thin tool, press and hold the service button (Fig. 2.2. Pos. 7) for at least 12 seconds Close the cover − The device will operate with the default parameters. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
The device should be cleaned with a damp cloth only. No abrasives or solvent-containing cleaners may be used. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akYtec GmbH. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
The test voltages shown in Fig. B.1 correspond to the tests carried out under normal operating conditions with 1 minute exposure time. akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
The replacement should not take longer than one minute. Otherwise, the real-time clock has to be adjust- ed anew. Fig. С.1 Battery replacement akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Page 37
5120 UINT16 Read community 0x1771 6001 String32 Write community 0x1781 6017 String32 Trap IP address 0x1401 5121 UINT32 akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Page 38
Size of the requested data is less than the size of the first or last parameter in the request Parameter value is beyond the valid limits akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
Page 39
Failed to open the file for writing Nonexistent file requested Read-only file requested Failed to write the required number of bytes akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...