8.3. Control of input/output signals from communication

The input terminals, output terminals, analog input and output signals of the inverters can be con-
trolled by communications.
Terminal Output Data (FA50)
The
output
Before controlling them, select Function Number 38 to 41 in Output Terminal Function Selection
(  -  ,  ,  ). Set data (0 or 1) can be output to the output terminals by
setting data of Bit 0 and Bit 1 of terminal output data (FA50) by communications.
Data construction of Terminal Output Data (FA50)
Bit
0
1
2 to 15
Example : Controlling only Terminal OUT1 by communication
Analog Output Data (FA51)
The analog terminals on the inverters, such as Terminal FM can be controlled directly by communi-
cations.
Select "18" (communication analog output) in Analog Terminal Connection Selection Parameters
(example: FM terminal connection meter selection [  ]) before controlling them.
Data set in Analog Output Data (FA51) can be output from the selected analog terminal. The data
adjustment range is 0 to 1023 (10bit resolution) . Refer to "Meter Setting and adjustment" in the in-
struction manual for inverters for the complete information.
terminals on the inverters can be controlled directly by communications.
Output Terminal Function
Specified data output 1
(Output terminal selection Number : 38, 39)
Specified data output 2
(Output Terminal Selection Number : 40, 41)
Set "38" (specified data output 1 [positive logic]) in Output Terminal Selection 1 (  ) in
advance and set "0001H" in FA50 to turn Terminal OUT1 on.
BIT15
FA50:
0
0
0
0
0
0
OFF
OFF
0
0
0
0
0
0
0
0
0
53
E6581222
1
ON
ON
BIT0
0
0
0
0
1
1