  • Page 1 Clarion Series (CFX-) Oil Mist Collectors Owner’s Manual Installation, Operation & Maintenance Revised 11-25-20...
  • Page 3 Owner’s Manual Installation, Operation & Maintenance Clarion Models: CFX-3000 CFX-1000 CFX-2000 CFX-3000 CFX-6000 CFX-9000 CFX-2000 CFX-1000 Manufactured by: RoboVent 37900 Mound Road Sterling Heights, MI 48310 USA (888) 762-6836 www.robovent.com ©2016 RoboVent All rights reserved.
  • Page 4 When your RoboVent Clarion Series unit needs scheduled maintenance, keep in mind that RoboVent has specially trained staff in servicing our mist and particle collectors. We would be pleased to set up a preventative maintenance program or answer your questions and concerns.
  • Page 5: Table Of Contents

    Appendix C:........Parts List ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 6: Important Safety Instructions

    (or any item you are in contact with, such as a screwdriver or test instrument) can accidentally touch the blower wheel. 6. Disconnect power before working on the motor or blower wheel. The motor or blower wheel should be disassembled only by a factory authorized technician. ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 7: Features Of The Clarion Series Collectors

    (CFM) delivered by the motor power requirements. (see Figure 3. Control Panel The built-in Control Panel of the RoboVent Clarion Series contains all the electrical control devices, including the motor starter with FIGURE 2 thermal overload relay, on/off selector switch and service discon- nect switch.
  • Page 8 Filter replacement is made easy and requires less time and effort than traditional loading systems. 8. Integral Mounting Rails Mounting rails on base for machine top mounting or suspending from building structure. ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 9: Receiving & Inspection

    Receiving & Inspection Receiving RoboVent Equipment is typically shipped on skids or in crates. The number of skids/crates will vary, depending on the type, size and accessories ordered. These skids/crates are too heavy to lift by hand, and will need to be unloaded by an industrial fork-truck or similar equipment.
  • Page 10: Installation

    SECTION 400 Installation The Clarion Oil Mist Series The RoboVent Clarion Oil Mist Series Collectors are universally designed to cover a large spectrum of oil and coolant mist applications. The application will determine the type of mounting system needed. The most common is the machine mounted Collector.
  • Page 11 Electrical connections should only be done by a licensed electrician and accordance with NEC and all applicable local codes. (See Appendix for electrical schematic.) The exact electrical connection will be determined by what model unit is ordered. ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 12: Operation

    If static pressure increases rapidly there may be an issue with the application which may require a different filter combination. In this case call RoboVent Technical Support at 1-(888)-762-6836, or email: customer.service@robovent.com...
  • Page 13: Motor Greasing Guide

    SECTION 600 Motor Greasing Guide ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 14 These motors are created with anti-friction, grease-lubricated bearings. Grease is essential to your motor bearings because it creates an oil film that counteracts the abrasive metal-to- metal contact that can occur between rotating elements. Follow RoboVent’s Motor Greasing Guidelines to properly lubricate your electric motor.
  • Page 15 3000 hours 1000 hours DE & NDE: 6317, DE: 6313C3 & NDE: 6213C3 120 grams 2000 hours 1000 hours DE & NDE: 6317 & DE & NDE: 6313C3 120 grams 2000 hours 1000 hours ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 16 Severe Service: Greater than 16 hours of operation per day. Continuous operation under • high ambient temp (100 to 150° F), dirty moist locations, high vibration, heavy shock loading or where shaft extension end is hot. ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 17 7.5 HP 8 grams 10 HP 12 grams 20 HP 16 grams 30 HP 19.5 grams 40 HP-50 HP 23.5 grams 60 HP-75 HP 27.5 grams 100 HP 34 grams 125 HP 42.5 grams ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 18 On applications with high or low temperatures, speed variation etc., the type of grease and relubrication intervals is given on an additional nameplate attached to the motor. ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 19 20000 hours 364 / 5T 60 HP 27 grams 4800 hours 9700 hours 404 / 5T 100 HP 34 grams 3000 hours 6000 hours 444 / 5T 125 HP 45 grams 2300 hours 4700 hours ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 20 Approved Grease • Shell Dolium R (factory installed) • Chevron SRI (standard service conditions) • Darmex 707 (high temp conditions) • Arrowshell 7 (low temp conditions) ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 21 254 to 286 (160 - 180) 25 HP-30 HP 6311 9 grams 324 to 365 (200 - 225) 40 HP 6313 12 grams 404 to 5000 (280 - 315) 100 HP-125 HP NU322 31.5 grams ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 22 ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 23: Maintenance

    4. Open large filter access door. This gives you access to the Packbed filter. 5. Remove the Packbed Filter from the Collector using RoboVent's SnapLock filter load system. Simply release the SnapLock mechanism by pulling the handles forward from the locked position, lowering the Filter Packbed, and slide the filter out.
  • Page 25 APPENDIX A General Wiring Diagrams...
  • Page 26 APPENDIX A General Wiring Diagram ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 27 APPENDIX B HEPA Filters Installation & Maintenance...
  • Page 28 Magna Series efficiency ranges include: 1000 Series - 99.97% and 1100 Series - 99.99%, all based on a .30 micron particle. RoboVent Magna filters are produced in a wide range of sizes, frame types and header combinations and are ideal for converting or upgrading existing systems. As an option, RoboVent High-Capacity Magna filter models are also available for higher velocity applications and incorporate more media area for lower resistance.
  • Page 29 Applications: The RoboVent Magna Series is designed for use where a high degree of cleanliness is required and contaminants must be removed to protect health, products or building interiors. The filters are ideal in a variety of applications including hospitals, manufacturing plants, microelectronics component assembly, negative-air machines, biological hoods and food processing.
  • Page 30 23-3/8 x 23-3/8 x 11-1/2 1.0" 1.45" 2424B5 24 x 24 x 12 24 x 24 x 11-1/2 1.0" 1.45" 2430B5 24 x 30 x 12 24 x 30 x 11-1/2 1.0" 1.45" ROBOVENT • FUSION 3 SERIES OWNER’S MANUAL...
  • Page 31 188.22 223.31 594 x 594 x 292 5032.5 9150 248.8 360.6 196.88 236.25 610 x 610 x 292 5032.5 9150 248.8 360.6 252.66 298.59 610 x 762 x 292 5032.5 9150 248.8 360.6 ROBOVENT • FUSION 3 SERIES OWNER’S MANUAL...
  • Page 33 APPENDIX C Parts List...
  • Page 34 CFX-1000-011 Expanded Metal Covers M1338 Blower Wheel 13" @ 38% MHG-2 Minihelic Filter Gauge MTR-1 1/2HP Motor, 1.5HP; 3600 RPM MV13 Venturi, 13" TH-SL Tee Handle Door Latch Parts & Service 1 (888) 762-6836 ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 35 OilMist Complete Cabinet CFX-2000-005 Motor Mount Plate CFX-2000-010 Expanded Metal Covers M1530 Blower Wheel 15" @ 30% MHG-2 Minihelic Filter Gauge MTR-2HP Motor, 2HP; 3600 RPM MV15 Venturi, 15" TH-SL Tee Handle Door Latch ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 36 Minihelic Filter Gauge MTR-5HP Motor, 5HP; 3600 RPM VV18 Venturi, 18" TH-SL Tee Handle Door Latch CFX-6000 & CFX-9000 Contact the RoboVent Factory at (888) 762-6836 for Parts List information on the CFX-6000 & CFX-9000. ROBOVENT • CLARION SERIES OWNER’S MANUAL...
  • Page 38 Manufactured by: RoboVent 37900 Mound Road Sterling Heights, MI 48310 USA (888) ROBOVENT (762-6836) ©2014 RoboVent All rights reserved.