Setting The Unit; Launching Test Mode; Manually Acknowledge A System Message - Rittal SK 3178800 Assembly And Operating Instructions Manual

Enclosure cooling unit
Table of Contents

Advertisement

7 Operation
EN
Display
Parameter
Internal
"Int"
temperature
External
"Est"
sensor
Outlet
"Out"
temperature
Tab. 5: Temperature setting range
Keep the Home key pressed down for around 3 sec-
onds to switch to the next menu up.
If you have changed the set temperature, the message
"ACC" will appear in the display for approximately
1 second. After that, the next menu up ("SP") will ap-
pear.
7.4.3

Setting the unit

All temperature values for the unit may be displayed ei-
ther in degrees Celsius "°C" or degrees Fahrenheit "°F".
When changing the unit, all temperature settings are
converted automatically.
Briefly press the Home key in the "tSE" menu.
The sub-menu "Con" (control mode) will appear for
you to select the control mode.
Use the arrow keys to select the "CF" (Celsius/Fahren-
heit) menu and briefly press the Home key again.
The currently set unit will be displayed.
Use the arrow keys to switch between the two setting
options until your preferred unit is displayed.
Keep the Home key pressed down for around 3 sec-
onds to switch to the next menu up.
If you have changed the set unit, the message "ACC"
will appear in the display for approximately 1 second.
After that, the next menu up ("CF") will appear.
7.4.4

Launching test mode

The control system features a test function, during which
the cooling unit commences cooling operation inde-
pendently of the set temperature or door function of the
door operated switch.
Use the arrow keys to select the "tSt" menu from the
"tSE" menu, then briefly press the Home key again.
The current setting "Off" will be displayed.
Use the arrow keys to select the "On" setting and keep
the Home key pressed down for approximately 3 sec-
onds.
The cooling unit begins operation. The progress of the
test is shown in the display as a percentage. Every
second, the percentage symbol is refreshed.
28
Setpoint
Factory
setting
20 °C (68 °F)
...
35 °C (95 °F)
50 °C (122 °F)
18 °C (64 °F)
...
24 °C (75 °F)
28 °C (82 °F)
Fig. 53:
Percentage symbol being refreshed
The entire test takes around 7 minutes. When the test is
complete, in the event of an error "Err" will appear in the
display; otherwise it will show "OK".
Briefly press the Home key to switch back to the start
screen.
7.4.5

Manually acknowledge a system message

For system messages requiring a manual reset, the
message "rSt" will appear in the display alternating with
the system code(s) and the temperature display.
First, rectify the cause of the system message.
Then, to acknowledge the system message, press
then Home key followed by the two arrow keys simul-
taneously for three seconds.
"ACC" appears in the display to confirm acknowledge-
ment.
1 s
Rittal enclosure cooling unit

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SK 3178800 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Sk 3178801Sk 3179800Sk 3179801Sk 3184800Sk 3184840

Table of Contents

Save PDF