When used with a DS9431 , power is
connected to the option bus power terminals
(RA or RB = +, BA or BB = -). Connection to
other (24V) sources will damage the DS7432.
To control panel 12VDC power terminals:
DS7400, terminals 7 and 8, Fig. 4
DS9400, terminals RA and BA, Fig. 5
To DS7430, DS7436 or DS9431 MUX
BUS Terminals (see Figure 4 or 5)
For UL Listed fire installations, Normally
Open (N/O) contacts must be used.
Initiating circuits are Class B
Smoke
Power -
PO2 If Programmed
or
Any LP+ Terminal
Auxiliary
Auxiliary
Power -
Power +
Smoke Power -
Figure 4: 4-Wire Smoke Detector Wiring for the DS7432 and DS7400Xi Control/Communicator.
DS7432 Installation manual
All manuals and user guides at all-guides.com
POWER
+ – + – 1
+
-
+
-
Figure 3: Wiring the DS7432 with Separate Powered Detectors
DS7400Xi Control/Communicator PCB
DS7430 MUX
Expansion Module
Power
Bus
Bus +
DS7432 8-Input Remote Module
+ –
+ –
1
POWER
BUS
EOL
Resistor
P/N: 28010
© Bosch Security Systems B.V., 2020
BUS
2 3
NO
NO
NC
NC
NC
47KΩ 47KΩ
47KΩ 47KΩ
Burg. EOL resistor: DS P/N: 26069 (included)
Fire EOL resistor: DS P/N: 28010 (sold separately)
To separate powered detectors (other than smoke detectors)
Either Bus A or Bus B, or both, may be used
for MUX connections when using the
DS7436 MUX Expansion Module. See the
panel's reference guide for information.
NFPA 72 does not allow redundant/duplicate
applications. Only the BUS (+) needs to be
2 3
4 5
6 7
8
Smoke Power +
Smoke Power -
Example: DS250 in an
Smoke
MB4W base.
Detector
Smoke
Detector
EOL
Example: EOL200
Relay
Input Loops
4 5
6 7
NO
NO
NO
NO
NC
NC
NC
47KΩ 47KΩ
ground paths, do not connect wiring to the
BUS (-) terminal on this module for fire
connected.
8
NO
NO
NC
NC
47KΩ 47KΩ
Page 3