(Iii) G.703 Reception Failure Detected In Gif200; (Iv) G.703 Transmission Failure Detected In Mux - Toshiba GR 200 Series Instruction Manual

Interface unit
Hide thumbs Also See for GR 200 Series:
Table of Contents

Advertisement

IEEE C37.94 I/F
(2)
Data with "Yellow
alarm bit"
(1)
Erroneous data
GRL200
IED
G.703 reception failure detected in GIF200
(iii)
If the GIF200 does not receive any data from the MUX, the GIF200 unit sends TX data
consisting of all '1' bits for the GRL200 IED. As a result, the IED gets to detect the error
status of the MUX.
IEEE C37.94 I/F
(2)
Data consisting of all
'1' bits
Data based on
C39.74
GRL200
IED
G.703 transmission failure detected in MUX
(iv)
If the MUX cannot receive data from the GIF200, the MUX issues the AIS by setting '1' to all
bits in the frames, the AIS information is transferred to the remote MUX.
GIF200 unit
Figure 2.7-2 O/E failure in GIF200
GIF200 unit
Figure 2.7-3 G.703 RX failure in GIF200
- 6 -
ITU-T G.703 I/F
Data based on
G.703
Data based on
MUX
G.703
(3)
ITU-T G.703 I/F
(1)
No reception data
Data based on
MUX
G.703
6F2S1916 (0.5)
MUX
MUX
GIF200

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gif200

Table of Contents