While programming
the display shows
Display shows
Drive is not running or has stopped
running
Display shows
LED lamp will blink 10 times quickly
Display shows
Drive is not working
The display shows
The LED is on all the time
When you try to open the gate remotely,
The
drive
automatically
stops
passing 10cm
The display shows
Drive is not working
You hear a 'kaka' sound from the relay
The display shows
The
drive
stops
automatically
driving 10 cm
The display shows
The door opens but does not close and
the display shows
The drive is fully open and closes after a
few seconds
The LED lamp blinks 4 times
The garage door stops and the LED light
is on all the time
The route is set at less than 30 cm or more than
9 m
Too low voltage
The garage kit is in poor condition
The drive cannot lock up
Error while setting the end positions
Incorrect setting of the end positions
The control panel is damaged or the power
board is damaged.
The sensor cable or the engine speed sensor
after
itself is defective.
.
The cable between the gear motor and the
plate is broken
after
The cable between the motor and the board is
connected backwards
The photocells function has been activated but
no photocells have been connected.
The automatic closing function is enabled
The power board is damaged
power board
4. Check that the power cord is connected
5. Check whether the low voltage side of transformer is 26V AC, if there
is 26V AC, replace PCB. If not, replace transformer
Re-set the end positions
Check the power supply
The garage door and motor require maintenance
Replace drive
Re-program the UP / DOWN limit setting as instructed
Replace the control panel or power board
Open the casing and check: sensor cable reconnect it or replace the
sensor.
Open the hood and check the connection between the motor and the
board.
First, disconnect the power, open the cover and swap the wires
between the motor and the board. Re-set the end positions.
1. Disable the photocells function if they are not connected (see
manual)
2. Check that the photocells are properly connected or that there is no
obstacle in the light of their operation.
Set the shutdown time or disable the function
(See manual)
Replace the power board