Page 2
Customer Service will work with production facility to have the replacement product shipped as soon as possible. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee.
Enclosure Grounding ......................7 Setup and Test Setting Overfill Alarm Horn Delay Time ................9 Testing the Overfill Alarm with the Acknowledgment Switch ..........9 Setting the Overfill Alarm Horn’s Volume Level ..............9 Testing the Overfill Alarm with the Console ..............9 Testing Overfill Alarm W/o Acknowledgment Switch..........10 Testing Overfill Alarm With Acknowledgment Switch ..........10...
577013-879 TLS-4XX Site Prep Manual Contractor Certification Requirements Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual: Service Technician Certification (Previously known as Level 2/3): Contractors holding valid Technician...
Veeder-Root TLS-450 Series Tank Monitoring Systems, including Line Leak Detection and associated accessories. All service personal on site must comply with all recommended safety practices identified by OSHA and your employer.
ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH. Fire or explosion resulting in serious injury or death could result if the Overfill Alarm and Ack switch units are installed in a volatile, combustible or explosive (Class I, Division I and Division II) atmosphere.
Mounting Instructions Overfill Alarm 1. Select a mounting location where the Overfill Alarm can be seen and heard clearly from the area where the fuel tanks are filled. In addition, consider the ease of routing interconnection conduit. 2. Locate and mark mounting holes using the hole pattern in Figure 1.
Wiring Overfill Alarm with Acknowledgment Switch 1. Pull two wires from the switch to the Overfill Alarm. 2. Pull two wires for line and neutral from the switch to the power panel. 3. Pull one wire from the switch to the TLS Console for connection to the alarm relay.
If using a properly grounded rigid metal conduit or equivalent to enclose the external wiring for the Overfill Alarm, the ground hub that terminates the conduit provides an adequate grounding provision for the Overfill Alarm.
Setup and Test Setting Overfill Alarm Horn Delay Time 1. Loosen the four screws that secure the Overfill Alarm cover clamps to the case. Slide the clamps away from the retaining lip on the door. Open the door. 2. Locate the Horn Time Delay Relay (see Figure 3).
1. Reapply power. If the Overfill Alarm was wired properly, the alarm horn will sound immediately followed by the red alarm light flashing. 2. Turn Off power to the console and to the Overfill Alarm. Remove the test jumper between the Output Relay connections.