EN
7.4

Constant current line drive accelerometers (CCS) channel 1-12

Constant current line drive accelerometers (CCS)
Page 22 of 42
This type of sensors needs a constant current, which is
supplied by the VCM-3 unit. Examples of high quality
accelerometers offered by Brüel & Kjær Vibro includes:
AS-062; 100 mV/g
(multi-purpose, integral cable)
AS-667; 100mV/g
(multi-purpose, radial connector M12).
AS-447; 500mV/g
(high sensitivity, axial connector M12).
AS-068; 10 mV/g
(low sensitivity, integral cable)
UNRESTRICTED DOCUMENT
NOTE!
The current source for the CCS
sensors must be enabled in the
channel setup of the VCM-3
monitoring template. If buffered
output signals from existing machine
protection systems or external
powered sensors are used CCS
should be disabled.
Maximum current output is
10 mA/Channel
© Brüel & Kjær Vibro ● C107758.002 / V04