Swing and Fold Door Opus Control Wiring and Programming Installation Manual
P/N C-00139
SECTION 3.5: Output Power Guidelines
TOTAL current draw from the Opus Control must not exceed 0.7A when providing power to:
Sensors
X
An auxiliary power supply, (e.g. NABCO Transformer 24VDC power supply p/n V-00022) must be utilized if TOTAL current draw
exceeds 0.7A.
The Opus Control must Not be used to power: Magnetic Locks nor Electric Locks
CAUTION
To determine if an auxiliary power supply must be used, add the total current draw of all devices. Please refer to the formula below:
1 x Cp/RX Radio Control Receiver @ 50 mA = 50 mA
SECTION 3.6: The Opus Control for Swing Doors
Note: The Hold Close feature is enabled when the LCD screen is OFF, or disabled when the LCD screen is LIT.
1 CN3 I/O Terminal Strip
2 CN5 Relay Output Terminal Strip
3 CN4 CAN Bus Communication
4 -
SECTION 3.7: Navigate with the Rotary Dial
DN 1242
Push down on the Rotary Dial:
X
1. Long push (2) seconds to gain access to LCD Category Screens.
2. Short push under (2) seconds to access Sub-level screens, and to selected/unselect menu items.
3. Long push (2) seconds to go back to Main screen.
4. Long push (2) seconds to go back to Main screen.
6 of 32
Modules
X
2 x Acusensor M @ 150 mA = 300 mA
Example: An Automatic Door System is to be fitted with the following devices:
350mA does not exceed total current draw .
An Auxiliary Power Supply does not need to be used .
DN 2415
Rotary Dial
11
Rotary Dial
20
Accessories
X
Total = 350 mA
5 -
LCD Screen
6 CN2 Motor Connector
7 CN1 Power Connector
8 -
Fuse
UNIT SPECIFICATIONS
Type:
GT710 Swing
Status:
Fully Closed
Slow Closing
Error:
-----
Ac va on: IN EXT
Posi on:
> > > > > >
Other:
BA 6B SWL
Push and Hold Dial
Go to Se ng Mode
Auxiliary Equipment
X
10
LCD Screen
Figure 1 The Rotary Dial
12
www.NabcoEntrances.com
Rev 8-11-21