Descripti on
Global industrial Portable Air Conditi oners are specialized for
"SPOT COOLING" where central cooling is impracti cal.
Global industrial air conditi oners can also be used in enclosed
areas just like conventi onal air conditi oners. Simple digital
controller and self-diagnosti c functi ons allow users to easily
operate the unit. Built-in Caster wheels enable users to move
the unit without any hassle. The unit can be installed in
5minutes and does not require any extra materials or certi fi ed
technician for installati on.
Global industrial Portable Air Conditi oner, anywhere,
everywhere. Plug-and-Go!
Unpacking
Aft er unpacking the unit, carefully inspect unit for any damage that may have occurred during
transit. Check for any loose, missing, or damaged parts.
Specifi cati ons
Model No.
Power Supply Ph-V-Hz
293119
3Phases - 460V - 60Hz
Weight (Net / Gross)
Model No.
293119
Model No.
293119
Lbs(kg)
1168/1245lbs.
(530/565kg)
Indoor Air Flow CFM
4000
High Capacity
TM
Air Conditioner
(For Indoor & Outdoor)
Cooling Capacity Btu/h
144,400
Ambient temperature
range °F( °C)
64~113(18~45)
293119
Figure 1
Power Con-
Rated Current
sumpti on Watt s
21.5kW
Dimensions
W x D x H - in. (mm)
34.3 x 75 x 71
(870 x 1904 x 1801 )
Refrigerant Type / oz(g)
R-410A / 278.7(7900)
293119
Amps
27A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 293119 and is the answer not in the manual?

Questions and answers

Summary of Contents for Global Industrial 293119

  • Page 1 Global industrial Portable Air Conditi oners are specialized for “SPOT COOLING” where central cooling is impracti cal. Global industrial air conditi oners can also be used in enclosed areas just like conventi onal air conditi oners. Simple digital controller and self-diagnosti c functi ons allow users to easily operate the unit.
  • Page 2: General Safety Information

    Owner’s Manual 293119 Specifications (Continued) Compressor overload protector, Anti-freezing thermister, Automatic restart (Power interruption), Safety Devices Compressor time delay program, High pressure switch Temperature control, Self-diagnostic function, Features Optional drain pump kit, Washable filters, °C display, Off-timer The unit is integrated with “PUMP-DOWN” function.
  • Page 3 Owner’s Manual 293119 DO NOT use the unit in wet environments, such as a laundry room, to avoid the risk of electrical shock. 10. DO NOT place any foreign objects on the unit. 11. DO NOT operate the unit with wet or damp hands.
  • Page 4: Component Parts

    Owner’s Manual 293119 Assembly (WPC-36003) COMPONENT PARTS Controls Emergency Stop Figure 3 Controls Electrical Panel Cold Air Inlet I BOLT Cold Air Inlet Filter Figure 2 Front and Right Side View Handle Hot Air Exhaust Condensate outlet Figure 4 Caster...
  • Page 5: Duct Connections

    Owner’s Manual 293119 DUCT CONNECTIONS Cool Air Out Duct(EVA) The Cool air duct connections are labeled “AIR OUT”. The connection size is 350Ø in diameter. Connect the flexible air ducting as follows: 1. Attach the flexible air ducting to the unit’s duct collars making sure that air will not leak past the connection collar by using appropriate round flexible ducting clamps.
  • Page 6: Installation

    Owner’s Manual 293119 Installation WARNINGS REGARDING PROPER LOCATION FOR INSTALLATION Do not use the unit in explosive environments or in areas where flammable gas leakage may occur. Do not use the unit in areas where it will be exposed to rain or water.
  • Page 7: Operation

    Owner’s Manual 293119 Operation CONTROL PANEL Figure 8 1. POWER BUTTON: Activates unit when POWER BUTTON is pressed. If POWER BUTTON is pressed during operation, unit stops. 2. BLOWER BUTTON: Indicates fan speed. (Not available for 3 phase model) 3. COOL BUTTON: Activates compressor and begins producing cool air in 5 seconds after button is pressed.
  • Page 8 Owner’s Manual 293119 Operation CONTROL PANEL 9. CURRENT TEMP: Displays ambient temperature (In ROOM/COOL mode only) / Displays outlet (cool air) temperature during normal operations (In SPOT/COOL mode only) In order to change ℃ to ℉, press BLOWER and COOL buttons together for 2 seconds.
  • Page 9: Maintenance

    Owner’s Manual 293119 Maintenance FILTER CLEANING (See Figures 11 and 12) 1. loosen up 6 bolts on the front filter guard. 2. Slide filter up and use a vacuum cleaner to remove the dust from the filter. 3. If the filter is heavily covered with dust and dirt, warm water and mild soap or neutral deter- gent may be used to wash the filter.
  • Page 10: Self Diagnostic Codes

    Owner’s Manual 293119 Maintenance (Continued) – To ensure your product is covered by warranty, the complete faulty product along with your original purchase receipt must be provided at the place of purchase. Product Portable Air Conditioner Customer: Please read and keep this Model No.
  • Page 11 Owner’s Manual 293119 SELF-DIAGNOSTIC ALARM CODES Alarm Display Problem Cause Corrective Action • Blocked air filter • Clean air filter Refrigerant high • Blocked / kinked • Ensure exhaust duct is pressure switch exhaust duct not blocked / kinked • Ambient tempera- •...
  • Page 12: Wiring Diagram

    Owner’s Manual 293119 Wiring Diagram PS (HP) Figure 14 - Circuit Wiring Diagram (WPC-36003)
  • Page 13: Troubleshooting Chart

    Owner’s Manual 293119 Troubleshooting chart Symptom Possible Cause(s) Corrective Action 1. Reset the circuit breaker and 1. Check the power supply to verify that power is restart the unit available to the unit The unit doesn’t work 2. Verify that the power 2.
  • Page 14 Owner’s Manual 293119...
  • Page 15 Owner’s Manual 293119...
  • Page 16 While attempts are made to assure that Global industrial products comply with such codes, Global industrial cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase and use of a product, review the product applications, and all applicable national and local codes and regulations, and be sure that the product, installation, and use will comply with them.