Triggering A Preset Value With The Preset Pushbutton - SICK EtherNet/IP AFS60 Operating Instructions Manual

Absolute encoder
Table of Contents

Advertisement

4.2.2

Triggering a preset value with the preset pushbutton

8014213/1EF3/2021-12-08 | SICK
Subject to change without notice
Table 30: Address switch – meaning of the adjustable values
Value
888
The encoder obtains its IP address from a DHCP server.
001 ... 254
Fixed IP address.
Only the least significant byte (1 ... 254) can be changed.
Address range 192.168.1.xxx is fixed
Subnet mask 255.255.255.0 is fixed
Gateway address 0.0.0.0 is fixed
000/999
The encoder loads the IP address from non-volatile memory when switched
on.
Fixed IP address via address switch
Use the left address switch to set the hundreds place of the address.
b
Use the middle address switch to set the tens place of the address.
b
Use the right address switch to set the ones place of the address.
b
Obtaining the IP address via DHCP
1.
Switch off the encoder.
2.
Set the address switches to 888.
3.
Switch the encoder back on.
The absolute encoder now obtains its IP address from a DHCP server and stores it in
non-volatile memory. Detailed step-by-step instructions for assigning the IP address via
DHCP can be found in the
If necessary, deactivate the DHCP function in the encoder
IP address", page
49).
The following procedure ensures that the encoder retains the IP address assigned via
DHCP even after it is switched on again:
Set the address switches to 000.
b
From now on, the encoder loads the IP address from the non-volatile memory
every time it is switched on.
To trigger the preset value, press the preset pushbutton.
The value from attribute 13h of the position sensor object is used as the new position
value
(see table 24, page
DANGER
Before using the Preset function, check whether there is any danger from the machine
or system in which the encoder is integrated!
The Preset function can lead to an immediate change of the position value output by
the encoder.
This could cause an unexpected movement that could endanger people or damage the
system or other objects.
NOTE
The Preset function should only be used when the encoder is at a standstill.
The preset value must be within the configured measuring range.
Do not press the preset pushbutton for longer than 5 seconds, as this may reset
the encoder to the factory settings.
Meaning
chapter
5.2.2.
29).
O P E R A T I N G I N S T R U C T I O N S | AFS/AFM60 EtherNet/IP
COMMISSIONING
(see "Freezing the assigned
4