Recommended Mccb, Earth Leakage Circuit Breaker (Elb) And Magnetic Contactor Specification; Recommendable Ac/Dc Reactor - LG SV-iC5 Series Instruction Manual

Lg inverter instructions manual
Hide thumbs Also See for SV-iC5 Series:
Table of Contents

Advertisement

4. Basic configuration
4.2

Recommended MCCB, Earth leakage circuit breaker (ELB) and Magnetic contactor specification

Model
004iC5-1, 1F
008iC5-1, 1F
015iC5-1, 1F
022iC5-1, 1F
4.3

Recommendable AC/DC Reactor

Model
004iC5-1, 1F
008iC5-1, 1F
015iC5-1, 1F
022iC5-1, 1F
MCCB/
ELB(LG)
ABS33b, EBS333
ABS33b, EBS333
ABS33b, EBS333
ABS33b, EBS333
AC input fuse
10A
20A
30A
40A
Magnetic
Contactor
GMC-12
GMC-18
GMC-25
GMC-32
AC reactor
2.13mH, 5.7A
1.20mH, 10A
0.88mH, 14A
0.56mH, 20A
4-2
Note
DC reactor
7.00mH, 5.4A
4.05mH, 9.2A
2.92mH, 13 A
1.98mH, 19 A
SV-iC5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents