Walktesting Groups; Duration And Termination - Siemens FIREFINDER-XLS Operation Manual

Table of Contents

Advertisement

PMI OPERATION MANUAL

Walktesting Groups

Duration And Termination

3-18
MAINTENANCE MODE
Technical Manuals Online! - http://www.tech-man.com
Press the Enable soft key to begin the Walktest. The Trouble LED flashes and the
Walktest Enabled screen displays (See Figure 3-30). If a printer is installed, the
trouble is also printed on the report printer. The PMI Trouble Event Screen will display
one trouble for each DLC placed in Walktest (ASD disabled for test) and one trouble
showing the Control Panel in Walktest.
The Walktest status screen indicates the time remaining in Walktest. The time is
indicated as HH:MM (hours:minutes).
Menu:Walktest
PHY:FireFinder@1, DLC@1
AT: FireFinder@1, DLC@1
WALKTEST:
ENABLED
SETTINGS:
No Bells
TIME REMAINING (HH:MM):4:00
Cancel
Settings
Disable
Figure 3-30
Walktest Enabled Screen
Only one Walktest may be active on a system at any one time.
When a Walktest is performed on a Geographic group, all walktestable devices in
the group are placed in walktest. All non-walktestable devices are not affected.
The Group Bells mode is available when walktesting groups. When this option is
selected, all applicable ZIC/voice devices in that group will activate. This will enable
the technician to walktest all devices on a floor, and have only the audibles on that
floor activate, provided the system is configured in floor-specific groups.
Once enabled, the Walktest remains in effect for four hours. At any time during the
Walktest, the user may extend the Walktest by pressing the Extend soft key on the
Walktest status screen. This will reset the Time Remaining to four hours. The
Walktest may be extended up to four times.
The user may cancel the walktest at any time by pressing the Disable soft key on the
Walktest status screen. After returning to the Alert Screen, Acknowledge the
"Walktest Activated" trouble and reset the panel.
If there is no activity acknowledging Walktest events on the PMI for five minutes, the
display will default to the Alert mode and the remaining time will display on the Alert
mode screen. The Walktest remains in effect until the time expires or the Walktest is
disabled. To view the Waltkest status screen, however, the Walktest password must be
entered again.
firealarmresources.com
WALKTEST
Extend
| CHAPTER 3