Switched -VE outputs are available for signalling of power fault and power healthy
indication marked PO (power on) and PF (power fault). Under normal circumstances
(mains and battery connected and fuses intact) the -VE appears at the PO terminal.
Failure of the mains or battery supply will transfer the -VE to the PF terminal.
A volt free changeover contact is also available for fault/healthy signalling which can be
used to switch other voltages or signals.
750mA typical wiring connections (always read safety notice at front of manual before
making any connections)
7

Addressing the units

To enable the control panel to know whether any units that should be connected have been disconnected and
indicate a fault condition, each unit must be allocated an address. The address switch should never be set with
all switches off.
This is done by setting a binary number from 1 to 5 on the 4 way, DIL switch located at the bottom of the PCB.
The order of the addresses is not important but each unit must be allocated a different address.
The switch settings for each of the addresses are shown below.