Installing and operating the PC WORX SRT Software PLC User manual UM EN PC WORX SRT...
Page 2
User manual Installing and operating the PC WORX SRT Software PLC 2013-11-06 Designation: UM EN PC WORX SRT Revision: Order No.: — This user manual is valid for: Designation Revision Order No. PC WORX SRT 2701680 PHOENIX CONTACT 8681_en_00...
Page 3
How to contact us Internet Up-to-date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at: phoenixcontact.com Make sure you always use the latest documentation.
Page 4
The same applies to any technical changes that serve the purpose of technical progress. The receipt of technical documentation (in particular user documentation) does not constitute any further duty on the part of Phoenix Contact to furnish information on modifications to products and/or technical documentation. You are responsible to verify the suitability and intended use of the products in your specific application, in particular with regard to observing the applicable standards and regulations.
1.3.3 Programming software ................8 Requirements for correct operation of the Software PLC........8 Description of the PC WORX SRT Software PLC ...............9 General description ....................9 Interfaces, indication elements, and operating elements ........11 Assembly and electrical installation ..............11 Connecting the PC's supply voltage ..............
Page 6
Accessories ..................68 7.2.3 Software ....................68 7.2.4 Documentation ..................69 Appendix: interfaces of the PC WORX SRT Software PLC............71 Connecting an Ethernet/PROFINET network............71 Appendix for document lists......................73 List of figures ...................... 73 List of tables ....................... 77 Index........................79...
For more detailed information on the Valueline industrial PC, please refer to the device- specific user documentation (see Section “Documentation” on page 69). Validity of the user manual This manual is only valid for the PC WORX SRT Software PLC in the version indicated on the inner cover page. Additional information...
The minimum system requirements must be met in order to install and run the Software PLC approved PC hardware. Valueline industrial PCs from Phoenix Contact (such as the VL BPC ..., see Section “Ordering data” on page 68) offer optimum requirements for operating the Software PLC.
Description of the PC WORX SRT Software PLC Description of the PC WORX SRT Software PLC General description The PC WORX SRT Software PLC is a PC hardware-based PLC with integrated PROFINET and Modbus support. It can be used for simple automation tasks without hard realtime requirements.
PC WORX SRT Modbus functionality The Modbus TCP communication protocol can be used via the assigned network adapter on the PC. In this case, the Software PLC can be used as a Modbus client. The Software PLC can be used as a Modbus server with the aid of function blocks.
Section “Documentation” on page 69. Assembly and electrical installation We recommend installing and running the PC WORX SRT Software PLC on a Valueline industrial PC from Phoenix Contact (such as the VL BPC ...). For more detailed information on the Valueline industrial PC, especially assembly and electrical installation, please refer to the device-specific user documentation (see Section “Documentation”...
PC WORX SRT Connecting the PC's supply voltage • Once you have installed the PC according to the instructions in the device-specific user documentation and connected it to the power supply, switch on the supply voltage. PHOENIX CONTACT 8681_en_00...
Software PLC. If the installation program does not start automatically, execute the “start.exe” file from the DVD-ROM. • Follow the installation instructions displayed on screen. Once you have selected the language, the following dialog box appears. This shows the start screen for installing the Software PLC. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Figure 3-1 DVD start screen • Click on “Install”. If the dialog box now prompts you to execute or save the installation file, perform the necessary actions to execute the installation file. Installation via installation • In the Download Center, download the installation file to your PC.
• In the “Welcome” dialog box that opens, click on “Next”. Figure 3-3 PC WORX SRT installer Installation status The installation status of the programs that are needed to operate the Software PLC is displayed (see Figure 3-4). The installation program checks the software already installed.
Please note that installation of the Software PLC on a network drive is not supported. • Click on “Next”. Figure 3-5 “PC WORX SRT Setup” dialog box – destination folder Selecting the network • In the following dialog box (see Figure 3-6 on page 17), select the network adapter on adapter/project directory the PC which should allow the Software PLC to communicate with your application.
Page 17
We recommend establishing the connection at this point in the installation. Following successful installation, you can check the IP address in the “Information” dialog box (see Section “Project information about the Software PLC” on page 36). • Click on “Next” to apply your settings. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Installation options/start The selected installation options are displayed. of installation Figure 3-7 Start of installation • Click on “Install” to start installation. • The following dialog box shows the installation status of the Software PLC. Figure 3-8...
The Software PLC starts automatically after booting the PC. To prevent automatic startup, the mode selector switch is set to the STOP position when starting. Once installation has been completed, the demo version of the PC WORX SRT Software PLC is available.
PC WORX SRT 3.2.2 Updating the Software PLC The following steps must be performed if you want to update the Software PLC. When updating the Software PLC, certain settings are transferred from the initial installation. Therefore, following a successful update, the program that was loaded in the Software PLC prior to the update, including all the settings present (e.g., IP addresses),...
• In the “Welcome” dialog box that opens, click on “Next”. Figure 3-11 PC WORX SRT installer The installation program now searches for an existing installation of the Software PLC. Update: Software PLC An existing Software PLC installation is indicated by the following dialog box.
PC WORX SRT Update: installationstatus The installation status of the programs that are needed to operate the Software PLC is displayed (see Figure 3-13). The installation program checks the software already installed. All missing programs are installed automatically. Please note that the complete installation process may take a few minutes.
If required, you can adapt the directory to your application. Figure 3-14 “PC WORX SRT Setup” dialog box – destination folder Update: network adapter The “Directory for user project data ...” and “Network interface” settings transferred from the previously installed version of the Software PLC are shown in the following dialog box.
All previously made settings are shown in the following dialog box. options/start of installation Figure 3-16 “PC WORX SRT Setup” dialog box – settings for the installation • Click on “Install” to continue the update. • The following dialog box shows the update status of the Software PLC.
Once update installation has been completed, either the demo version or the full version of the PC WORX SRT Software PLC is available. This depends on whether you previously entered a license key. A previously entered valid license key is still valid for the update.
15 minutes before the end of the 60 minutes, a tooltip is displayed informing you that the demo version will expire after the specified time has elapsed. The display is updated minute by minute. Figure 4-3 PC WORX SRT: demo version will expire in x minutes 8681_en_00 PHOENIX CONTACT...
PC WORX SRT If the test period of the demo version has expired, this is indicated as follows: Figure 4-4 PC WORX SRT: demo version has expired Key: Demo version has expired Software PLC in the STOP state To switch the Software PLC from the demo version to fully functional operation, enter the license key.
Menu items of the Software PLC and status monitor Status monitor – additional information For information on the status monitor, especially its display and setting options, please refer to Section “Status monitor of the Software PLC” on page 32. 8681_en_00 PHOENIX CONTACT...
A popup dialog box shows both the Windows and runtime CPU usage (see Section “System system monitor monitor” on page 38). PC WORX SRT switch Displays a representation of the mode selector switch that differs from that of the status position/mode selector monitor.
Status monitor of the Software PLC If the status monitor is not displayed after switching on the PC, you can start it via the following path: “Start, All programs, Phoenix Contact, PC WORX SRT, PC WORX SRT Status Monitor”. Figure 4-10 Starting the status monitor...
Right-click on the icon in the taskbar to open the context menu of the status monitor. Figure 4-11 Context menu of the status monitor Depending on the operating state of the Software PLC, the following options are available in the context menu of the status monitor: 8681_en_00 PHOENIX CONTACT...
If the status monitor has been exited, it can be enabled again via “Start, All programs, Phoenix Contact, PC WORX SRT, PC WORX SRT Status Monitor”. After a brief moment, the status monitor icon appears in the taskbar. PHOENIX CONTACT...
The Software PLC is in the RUN state, the application program is processed. The PC Worx software can be used for program and configuration modifications. The monitoring and online functions can be used. STOP The Software PLC is in the STOP state, application program processing has been stopped. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Software PLC reset The mode selector switch does not have a reset function. The Software PLC must be in the STOP state in order to be reset. Then perform the reset using the “Reset” item in the status monitor context menu (see Figure 4-13).
Runtime Version – version of the runtime environment – Status monitor version – Serial number of the Software PLC license You can update the project information displayed by again clicking on “Show Information” in the context menu of the status monitor. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT 4.3.4 System monitor Figure 4-16 System monitor The system monitor shows both the Windows and runtime CPU usage. On PCs with multi- core CPUs, the usage of all cores used in different processes is shown. NOTE: Correct operation – observe system usage To ensure correct operation of the Software PLC, use the system monitor to check the usage of the runtime CPU and of the Windows CPUs used.
Status monitor: error affecting the correct operation of the Software PLC Error descriptions, possible causes, and remedies for operating errors of the Software PLC can be found in Table 4-4 “Errors affecting the correct operation of the Software PLC” on page 40: 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Table 4-4 Errors affecting the correct operation of the Software PLC Error Cause Remedy Connection errors – Invalid firewall settings Check the firewall settings on your communication errors on the PC PC. Correct any incorrect settings, if necessary. Disable the firewall as necessary to ensure correct connection of the Software PLC.
Page 41
Check the wiring of the outputs on by the output being short the Valueline IPC. The DO DIAG bit is set circuited to ground when the outputs are set Eliminate any existing short (GND). to zero due to circuits. overheating. 8681_en_00 PHOENIX CONTACT...
Page 42
PC WORX SRT Table 4-4 Errors affecting the correct operation of the Software PLC Error Cause Remedy Mini digital I/O: error 2 There is no supply Check the power supply at the voltage at the digital digital inputs and outputs of the inputs and outputs of the Valueline industrial PC.
For information on installing and using PC Worx, please refer to the online help for the software and the corresponding quick start guide. It can be downloaded at phoenixcontact.net/products and is supplied in an electronic form with the software. Example project structure PROFINET 8681A003 Figure 5-1 Example project structure 8681_en_00 PHOENIX CONTACT...
Figure 5-2 Creating a new project – “File, New Project...” menu • In the “New Project” dialog box, select the “PC WORX SRT V1.0” Software PLC. Figure 5-3 “New Project” dialog box: project templates • Confirm your selection with “OK”.
Software PLC and PC Worx – program creation • Enter a name for your project in the “Save/Zip project as” dialog box (here: PCWORXSRT_UM). • Click on “Save” to save the project. Figure 5-5 “Save/Zip project as” dialog box 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Checking/specifying project information • Switch to the bus configuration workspace. Figure 5-6 “Bus Configuration Workspace” button After creating a new project, the project information is displayed in the bus configuration workspace. • Adapt the project information to your project.
Page 47
(see Figure 5-8 on page 48). If any modifications are made to the project information that affect the IP settings for the controller, a warning is displayed. However, the modification is not implemented automatically. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Assigning/checking the IP address for the Software PLC According to the IP address settings in the project information (see Section “Checking/specifying project information” on page 46 and onwards), the IP address for the Software PLC must be set in the device details in the “IP Settings” tab.
TCP/IP protocol. Please note that with all networked devices/computers, there is a risk that third parties may access the Software PLC or the PC Worx PC and make changes, either intentionally or unintentionally. Prevent unauthorized access to the Software PLC and your PC. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT 5.5.2 Testing the localhost function You can test the localhost function in the bus configuration workspace. • In the bus configuration workspace in the “Bus Structure” window, select the “PC WORX SRT” Software PLC. • In the “Device Details” window, switch to the “Communication” tab.
In the context menu of the PROFINET node, select the “Read PROFINET...” command. Figure 5-11 PROFINET node: Read PROFINET In the “Read PROFINET” dialog box that opens, select the corresponding devices for your application one after the other. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT • Click on a device to select it (“ILB PN 24 DI16 DIO16-2TX” in Figure 5-12 on page 52). Figure 5-12 “Read PROFINET” dialog box • Click on the “Insert” button. • In the “Insert PROFINET Device” dialog box which opens, click “OK” to confirm the device to be inserted.
PC Worx and downloaded to the controller (see “Compiling and sending a PC Worx project to the Software PLC, and performing a cold restart” on page 54), that the Software PLC assigns the settings saved in the project on every power up. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Compiling and sending a PC Worx project to the Software PLC, and performing a cold restart The previous steps have prepared the project so that the example structure can be started Compiling a project Compile the project.
Section “System time” on page 65). Download changes The PC WORX SRT Software PLC supports the “Download changes” function. The “Download changes” function can be used to send project modifications to the controller(s) and activate them there without having to stop the active PLC.
Explorer FTP functionality” on page 58. • Switch to the bus configuration workspace in PC Worx. • Select the controller, e.g., PC WORX SRT, in the “Bus Structure” window. • Select the “Extended Settings” tab in the “Device Details” window. •...
Data may only be copied or deleted on the parameterization memory. Do not edit any files as Internet Explorer does not store modified data. For the current state to be displayed, refresh the display after every action by means of the “View, Refresh” command. 8681_en_00 PHOENIX CONTACT...
PC WORX SRT 5.10.1 Internet Explorer FTP functionality • Activate this setting in Internet Explorer under “Tools, Internet Options, Advanced”. Figure 5-21 Internet Options: Enable folder view for FTP sites 5.10.2 Activating/deactivating the HTTP server To protect the Software PLC against unauthorized access, it may be necessary to deactivate the HTTP server.
All file operations are subject to the following restrictions: No directory hierarchies are supported. All file operations only affect the root directory of the parameterization memory. The function blocks are valid for the PC WORX SRT Software PLC Version 1.0 or later. Table 5-1 Overview of function blocks...
Implement all time and connection monitoring in the application program. The function blocks are valid for the Software PLC version listed in the table below and support the specified maximum number of TCP/IP or UDP/IP communication connections: PC WORX SRT as of Ethernet connections to other Blocks...
Number of available system tasks. PLC_MAX_ERRORS DINT Maximum possible number of errors present. PLC_ERRORS DINT Number of errors currently present. PLC_TASK_DEFINED Number of PLC tasks used. PLC_TASK_1 Extended_ Task_Info Information on task 1 PLC_TASK_16 Extended_ Task_Info Information on task 16 8681_en_00 PHOENIX CONTACT...
PC WORX SRT Control processor (CPU) The system variables listed below show the states of the diagnostic status register on the control processor (CPU) of the Software PLC. The Software PLC runtime system runs on this processor. Table 6-2 System variables of the control processor...
At least one PROFINET device is indicating the “maintenance requirement” alarm (low-priority maintenance alarm) for the active connection. The device can be identified using the RALRM diagnostic block. PNIO_FORCE_FAILSAFE BOOL All PROFINET devices are prompted to set/assume their configured substitute values. 8681_en_00 PHOENIX CONTACT...
Page 64
The PROFINETcontroller configuration has not been applied due to a serious error and the PROFINET controller is not started. Please contact Phoenix Contact. If one of these values is set, it is now possible to decide from the program whether the system should continue operating.
System time Table 6-7 System variables of the system time System variable Type Meaning RTC_HOURS System time (hours) RTC_MINUTES System time (minutes) RTC_SECONDS System time (seconds) RTC_DAY System time (day) RTC_MONTH System time (month) RTC_YEAR System time (year) 8681_en_00 PHOENIX CONTACT...
Update time for inputs and outputs 1 ms, minimum, depending on the size of the bus system Conformance class Approvals Approvals depend on the device. For the latest approvals for the devices listed in the “Devices” ordering data, please visit phoenixcontact.com phoenixcontact.net/products. 8681_en_00 PHOENIX CONTACT...
Use the order number specified for PC Worx to order the current version of the software. The corresponding service pack can be downloaded from the Download Center on the Phoenix Contact homepage. AX OPC SERVER, communication interface for OPC-compatible...
PROFINET Installation Guideline for Cabling and Assembly, For the latest versions of the documents, visit Version 1.0, January 2009, Order No.: 8072 www.profibus.com/PNInstallationGuide “PROFINET_Guideline_Assembly_8072_V10_Jan09.pdf” or you can contact your nearest Phoenix Contact representative regarding the document. Modbus Application note AH EN MODBUS TCP –...
PC used. For more detailed information on the interfaces and extension options of the Phoenix Contact Valueline industrial PC used in the example, please refer to the device- specific user documentation.
Figure 3-15: “PC WORX SRT Setup” dialog box – additional settings ....23 Figure 3-16: “PC WORX SRT Setup” dialog box – settings for the installation ..24 Figure 3-17: Update status of the Software PLC ............. 24 Figure 3-18: Installation successful .................
Page 74
PC WORX SRT Figure 4-7: “PC WORX SRT Configuration” dialog box.......... 30 Figure 4-8: Mode selector switch ................31 Figure 4-9: Status monitor of the Software PLC ............ 32 Figure 4-10: Starting the status monitor ..............32 Figure 4-11: Context menu of the status monitor ............ 33 Figure 4-12: Switch positions of the mode selector switch ........
Page 75
PROFINET system variables (PROFINET controller function) ............63 Table 6-5: PROFINET system variables (PROFINET device functionality) ............64 Table 6-6: Special system variables of the Software PLC........65 Table 6-7: System variables of the system time............ 65 8681_en_00 PHOENIX CONTACT...
IEC 61131 control performance ........9 Saving the project........... 44 Installation status ........... 15, 22 PROFINET..............9 Installing the Software PLC Programming software........... 8 New installation ............13 Update..............20 Interfaces ..............71 Selecting the network adapter ........16 Interfaces, indication elements, and operating elements ..............11 8681_en_00 PHOENIX CONTACT...
Page 78
PC WORX SRT Scope of supply .............7 Software PLC Demo version ............27 IP address ............17, 19 Licensing ..............30 MINI I/O ..............38 Network adapter ......... 10, 23, 30 Operating states .............33 Project information ..........36 Reset..............36 Status monitor..........10, 31, 32 Context menu ............33...