COMMISSIONING
5.11
Record - Activation of screed function
Description of function
The control module of the TopTronic
screed drying, it is necessary for the individual functions to be set accordingly.
Flow temperature
Heating-up phase
(
04-061)
40 °C
35 °C
30 °C
5 K
25 °C
1 d
20 °C
0
1
2
Start
Function
Heating-up phase
Stabilisation temperature
Inertia phase
Cooling off phase
Activate screed function
NOTICE
The graphic/table shows the factory settings. The time profi le and the maximum fl ow temperature must be
discussed with the screed layer, otherwise there could be damage to the screen – and in particular, cracks.
REACTION screed function
• Start/stop: Switch parameter 04-060 ON (1) or OFF (0)
• Power failure in heating-up phase: program restart
• Failure in the steady-state phase: Retain maximum temperature and add the failure time to the steady-state phase
• Power failure in the cooling off phase: Measurement of actual fl ow value and continue cooling until start value
reached
• Program end: Previous basic program active again
Settings in the TopTronic
32
E contains a functional sequence used for drying out screed fl oors. To start the
®
Stabilisation temperature
(04-063)
Current heat generator temperature = start temperature
3
4
5
6
Parameters Value
04-061
04-063
04-064
04-062
04-060
E control module
®
Settings under Start screen > Main menu > Service > H-GEN >
Heating circuit > Heating circuit 1, 2, 3* > Screen > 04-060 to
04-064.
* If there are several heating circuits, a separate screed function must be assigned to each
heating circuit.
Inertia phase
(04-064)
7
8
9
10
11
Description
5 K/d
Kelvin per day (rising)
40.0 °C
Set maximum temperature
10
Number of days in stabilisation temperature
-5 K/d
Kelvin per day (falling)
1 (ON)
Start and stop screed drying
Can only be set in the corresponding user level.
Cool down phase
(
04-062)
1 d
12
13
14
15
4 217 214 / 02
-5 K
Days
16
End