Executing Commands With The Repetition Function; Testing Devices, Activating Alarms And Test Alarms; Testing The Device - Siemens FDUD293 Technical Manual

Intelligent detector tester
Table of Contents

Advertisement

5.7.5

5.8 Testing devices, activating alarms and test alarms

5.8.1
Building Technologies
Fire Safety

Executing commands with the repetition function

The repetition function is switched on.
The repetition function can be used for commands.
1. Execute the command.
The red, yellow, and green LEDs flash alternately and the device searches
for a detector.
As soon as transmission starts, the green and yellow LEDs flash
alternately.
The LEDs stop flashing once the command has been executed.
The command result is indicated by the LEDs.
If no deviation occurs, the red, yellow and green LEDs start to flash when
the service device is removed from the detector and the command can be
repeated.
If a deviation does occur, you should exit repetition mode.
2. To exit repetition mode, press the <
You can select and execute a new command.
See also
Executing commands - general procedure [
Setting the repetition function [

Testing the device

'2.1 Check' menu
The status and error register of the device are queried with the '2.1 Check'
command. The following is tested:
Parameter set
Operation mode
Line separator
Faults
The infrared signals of the forward scatterer and the backward scatterer are
also tested for neural fire detectors (FDOOT, FDOOTC) and smoke detectors
(FDO).
Procedure
Execute the '2.1 Check' command.
The device is tested.
If there is a deviation, this is indicated by the LEDs and on the display.
See also
Deviation list [
Executing commands - general procedure [
Testing devices, activating alarms and test alarms
> button.
41]
Operation
5
28]
40]
28]
009718_e_en_--
2014-04-11
33