Climatix Touch Panel HMI POL8Tx HMI-TM Climatix Text Matrix HMI POL871.xx HVAC Heating, Ventilating, Air Conditioning Room Unit (e.g. POL822.xx) SCADA Supervisory Control and Data Acquisition SELV Safety Extra-Low Voltage 4/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies About this document 2015-06-30...
This document may be duplicated and distributed only with the expressed permission of Siemens, and may be provided only to authorized persons or companies with the requisite technical knowledge. Siemens reserves the right to make any modification to this document without prior notice. 1.4.4 Quality assurance These documents were prepared with great care.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same. 1.4.6 Important notes Only authorized personnel are permitted to make diagnostics, to rectify faults and to restart the plant.
Data tag management Time sync with Climatix controller Graphical extendable database with HVAC pictures and animations Support C-like script language programming The 4.3" type touch panel does not support SD card. 7/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies 2015-06-30...
The following figures show examples of the communication between the Climatix touch panel, the PC, and the Climatix controller. With Climatix POL6XX controller Climatix POL6XX communication concept With Climatix POL4XX controller Climatix POL4XX communication concept 8/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies Overview 2015-06-30...
⑩ Description Description Display / touch screen Ethernet port LED indicators RS485/RS232 communication port Recesses for a mounting clip DIP switches USB-A port Label USB-B port Power supply connection 9/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies 2015-06-30 Overview...
Page 10
Display / touch screen 6/7 RS485/RS232 communication port LED indicators Ethernet port SD card slot USB-B port and DIP switches Recesses for a mounting clip Label USB-A port Power supply connection 10/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies Overview 2015-06-30...
Make sure that both ends of the cable are connected tightly and firmly. The RS485/RS232 port is a communication port. It cannot be used for programming. 12/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies...
Check the package content for visible signs of transport damage and for contents completeness. Note: Do not install parts damaged during shipment. Contact your Siemens representative in the event of damaged parts. Check operating Note the information in the following sections of these operating instructions before...
“G”, “GR”, “GRD”, “GND”, “GRND”, “Ground”, “Grounding”, or the like, the symbol (IEC Publication 417, Symbol 5019) may be used. 14/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies Mounting and connecting...
Climatix touch panel pin (0V) should not be directly connected to Ground of electrical panel to avoid equalizing currents. Note: Ensure that the wires are connected to the correct polarities. 15/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies 2015-06-30...
USB Type B male connector on one end. 1. Connect the USB cable to the USB-A port on the Climatix touch panel. 2. Connect the other end of the USB cable to the configuration PC. 16/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies...
Check the connected cables and change them as needed. Climatix touch panel has a DEMO application in order to show main functionalities and features. Please download your own application developed with HMI-TOOL configuration software. 17/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies 2015-06-30...
You can configure the customized keyboard for an operating element in the configuration software. ASCII keyboard Numeric keypad 18/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies Operating the Climatix touch panel 2015-06-30...
Preparation To create an upgrade image on an SD card or a USB stick: 1. Contact Siemens regional company to get an upgrade file (.raw) for your touch panel firmware. 2. Format the SD card or USB stick as FAT32 format.
Page 20
8. Shut down the Climatix touch panel and switch it on again. The upgraded firmware is available on the Climatix touch panel. The firmware revision is shown on the bottom right corner of the screen. 20/30 Siemens Climatix touch panel A6V10445442 _en--_a...
Insert the SD card or USB stick into Climatix touch panel. Confirm GUI download process. After upgrade process is completed, Climatix touch panel restarts automatically. Climatix touch panel runs new GUI application. 21/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies...
Press Brightness, and adjust the brightness of display. Set the time and date Press Date / time and use + or - to set the date and time, and press Ok. 22/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies...
Below is an example of the parameter settings: • Select serial port: COM1 • Baud rate: 9600 • Data bits: 8 • Parity: None • Stop bit: 1 23/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies 2015-06-30 Configuring the Climatix touch panel...
If the Receiving a character textbox displays the same data, the test is successful. Set the language Press Language, select the desired display language and press Ok. 24/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies Configuring the Climatix touch panel...
Do not clean the Climatix touch panel with compressed air or steam jet blowers. Do not use aggressive solvents or scouring powder. 25/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies...
UL 508 and CUL 508 Process Control Equipment The product environmental declaration (8000079408) contains data on environmentally compatible Environmental product design and assessments (RoHS compliance, materials composition, packaging, environmental compatibility benefit, disposal). 26/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies Technical specifications 2015-06-30...
Dimensions 173 mm POL8T1.4X/STD 161 mm 163 mm Cut-out 227 mm POL8T1.7X/STD 208 mm 210 mm Cut-out POL8T1.8X/STD C ut-out 29/30 Siemens Climatix touch panel A6V10445442 _en--_a Building Technologies 2015-06-30 Technical specifications...