Service And Cleaning; Clean The Firetubes; Cleaning Of Rsa Boiler - Burnham BOILERS Operating/Service Instructions Manual

Installation, operating and service instructions for rsa series boilers
Table of Contents

Advertisement

VIII. Service and Cleaning
NOTICE
BUR NER S HU TD O WN : O p e n S e rv ic e
Switch to turn off burner.
Manual Oil Supply Valve should be closed
and Electric Service to boiler turned off if
boiler will not be operated for an extended
period of time.
A
. General. Inspection service and cleaning should be
conducted annually. Turn off electric power and close
oil supply valve while conducting service or mainte-
nance.
B
. Firetubes and Combustion Chamber. (See Figure 25)
Figure 25: Cleaning of RSA Boiler
36

1. CLEAN THE FIRETUBES

a. Disconnect electric to burner and remove stack.
b. For access to the firetubes, pull top jacket panel
off. Loosen wing nuts, that hold canopy down.
Without taking wing nuts off carriage bolts,
disengage bolts from slots on tubesheet. Pull
canopy off.
c. Remove turbulators.
d. Using a firetube brush clean firetubes. DO NOT
extend brush past the end of the bottom
tubesheet.
e. Assemble the boiler in reverse order.
Units should be cleaned at least once a year, preferably
at the end of each heating season.
It is not necessary to remove burner to clean boiler.
Brush, scrape, or vacuum from top.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BOILERS and is the answer not in the manual?

Questions and answers

Keith Burke
February 23, 2025

what size cleaning brush do i need to clean my rs111 boiler and how many gallons of water does a rs111 hold?

This manual is also suitable for:

Rsa170Rsa195Rsa240Rsa285

Table of Contents

Save PDF