Separate 9954 expander units allow connection of a further 16 wired zones to a 9751 or 24 wired zones to a 9752. Alternatively, a 9955 expander allows connection of 16 wirefree zones to a 9751 or 24 to a 9752. Both control units can use a combination of wired and wireless expanders.
Page 8
715rEUR 725rEUR-55 Wire free PIR Telecommand 726rEUR detector 735rEUR 9955 Universal transmitter 719rEUR Smoke detector Keypads Wired 9954 Detectors Keypads Control Unit Keyswitch PIRs Door contacts Fused mains spur Figure 1. 9751/2 System Layout 496792...
1. Introduction Operator Controls and Displays - 9930 Figure 2. 9930 Remote Keypad. The 9930 keypad has a single line 16 character LCD display that shows first to alarm information, level status, and programming commands. In addition there are three LEDs with the following functions: Glows steadily when mains power is present.
In addition each expander also provides for up to eight telecommands or PA transmitters. Note: The 9751 can only use a maximum of 24 zones. The 9752 can only use a maximum of 32 zones. The 9955 unit can work with the following devices on 868.6625MHz: 719r.
Part Set B, C or D Selected zones are omitted. You must program the zones to be omitted during installation. (Part set D is not avail- able on the 9751.) Set with Omit One or more zones temporarily omitted. The user selects the zones to be omitted during setting.
Conforms to EN50131-6 Type A power supply for Grade 1 systems. Outputs O/P 1, 2, 3 9751: open collector transistor outputs, 500mA, 12VDC. negative applied 9752: O/P 1 and 2 voltage free relay contacts, O/P 3 open collector transistor outputs, 500mA, 12VDC. negative applied can support two parallel connected externally mounted 16 Ohm loudspeakers for internal sounder or EE tones.
2. Technical Description Control Unit PCB Figures 3 and 4 show the layout of the 9751 and 9752 PCBs. 12V Aux fuse 21VAC from transformer Kick start pins Outputs Battery fuses Battery connector Aux Power NVM Reset pins Communica- Tamper switch...
Page 15
Figure 4. 9752 Control Unit PCB Layout Note that, compared with the 9751, the 9752 contains extra terminal blocks for the relay based outputs, a connector for the lid tamper switch, and a connector for a local cable to a PC for <Downloader>.
2. Technical Description 9954 Expander The 9954 Expander provides connectors for either eight four-wire CC loop zones, FSL or EOL zones. Figure 5 shows the layout of the PCB. CC/FSL/EOL Jumpers CCT1 Zone CCT2 Connectors Zone Connectors CCT5 CCT6 CCT3 CCT4 CCT7 Lid Tamper...
3. Installation 3. INSTALLATION Caution: Always remove mains power before opening the case lid. Do not work inside the control unit with mains power present. Overview A typical installation comprises the following main steps: Survey the site and decide on positions for wired detectors, 9954 wired expanders, control unit, keypads, external and internal sounders.
3. Installation Cabling Keypads and Expanders Cooper Security recommend that you use 8-core 7/0.2 or 16/0.2 alarm cable for wiring keypads and expanders. You can connect the keypads and expanders in either a star or bus configu- ration (see Figure 6). If you are intending to use long cable runs then Cooper Security recommend that you use star wiring.
3. Installation 2. Make sure that the voltage between 0V and 12V of the keypad bus at the furthest point from the control unit is at least 12.0VDC when all the keypad backlights are on. Note: The following instructions assume that you have already run the necessary cabling.
3. Installation Cooper Security recommend that you mount the keypad using No 8 or 6 screws (M4/M3.5) as follows: Select which cable entry you are going to use and break out the appro- priate plastic sections. Hold the backplate in place against the wall and mark the position of the centre hole in the adjustable cam (see Figure 7).
3. Installation To Control Panel Transformer 230V ~50Hz 200mA T 250mA 250V Figure 8. Mains Connection Connect the 21VAC lead from the mains transformer to the main pcb. See Figure 3 or 4 for the location of the 21VAC connector. Caution: Do not apply mains power at this point.
3. Installation Keypad Backlight When supplied from the factory the control unit is configured with the keypad backlight ON. To turn the keypad backlight OFF remove the jumper from the "ON BACKLIGHT" link, shown in Figure 9. Connecting Keypads, Exit Terminate Buttons, Lock Switches and Sounders Figure 10 shows the connections for any of the remote keypads.
Page 25
9751Control (9751) Unit Bell -ve Hold Off -ve Tamper Return +ve Hold Off -ve Apply trig 12V AUX 12V AUX Internal Sounder as for 9751 9752Control Unit Bell Strobe Typical SAB (9752) Bell -ve Hold Off -ve Tamper Return +ve Hold Off...
3. Installation Detector Circuit Connections The left hand edge of the main PCB provides 14 connectors that can be used for up to 8 FSL zones, or 8 Closed Circuit zones. During programming use command 21 to configure these connectors as either CC zones, or two wire FSL zones.
3. Installation Alarm contacts Zone 1 2K2 EOL Tamper contacts Zone 2 Note: You can leave the global Alarm contacts 2K2 EOL anti tamper Tamper contacts connectors unlinked if you are using FSL wiring. Yellow Violet Gold Gold Figure 12. FSL Connections Connecting Expanders Figure 13 shows how to wire 9954 and 9955 Expanders to the control unit.
"learn" radio detectors to the expander. Using Programmable Outputs In the 9751 OP1, 2 and 3 are "pull down type" outputs that provide negative applied control signals. The system adjusts the output polarity when you select the output type.
Note: Ideally, no other equipment should be connected to an exclusive line. Three Way Calling The 9751 and 9752 also provide a Three Way Calling facility to make sure the built in communicator can always use a shared telephone line.
Response (programming command 106). Test Calls The 9751 and 9752 can be programmed to make test report calls to an Alarm Receiving Centre. "Static" test calls can be programmed to occur at a set time every day. "Dynamic" test calls occur 24 hours after the last call made by the control unit.
4. A BT provided telephone is assumed to have a REN value of 1. Safety Notice The terminals on the 9751 and 9752 control unit main pcbs are described as Safety Extra-Low Voltage circuits (SELV), according to the definitions in Safety Standard EN60 950.
T.N.V. cct. Keypad Connector S.E.L.V. cct Figure 17. SELV and TNV Connectors on the 9751/2 Connecting the Telephone Line Direct connection, or interconnection via other apparatus, to the terminals on the built in communicator can produce hazardous conditions on the tel- ephone network.
Page 33
Using a three core cable (type 1/05mm CW1308), strip back 5mm of two cores and feed through one of the cable entries in the rear of the 9751 or 9752 casing. Connect the two cores to the terminals, A and B on the built communicator.
3. Installation Fitting a Plug-by Communicator The 9751 or 9752 can be fitted with a communicator or speech dialler (for example the Scantronic 8400, 8440, 660 or RedCare STU). To fit a commu- nicator, follow the instructions below. Caution: Follow the instructions in the order shown, or you may dam- age the control unit and/or communicator.
Page 35
3. Installation Com Connector Cable, Part No. 485210 Comms O/P1 (Brown) -ve applied (+ve removed) in alarm Comms O/P2 (Orange) -ve applied (+ve removed) in alarm Comms O/P3 (Yellow) -ve applied (+ve removed) in alarm Comms O/P4 (Green) -ve applied (+ve removed) in alarm Comms O/P5 (Blue) -ve applied (+ve removed) in alarm Comms O/P6 (Purple) -ve applied (+ve removed) in alarm Comms O/P7 (White) -ve applied (+ve removed) in alarm...
3. Installation If the system has already been installed: Re-connect the battery. Fit the case lid. Apply mains power. Test communicator operation (see programming commands 151 to 158). Fitting a Battery Fit a rechargeable battery into the back of the case. If using a Junior Combi Box the case provides space for a 12V 7AH battery.
3. Installation Initial Start Up Before applying power to the control unit, ensure that: • All remote keypads and expanders have been addressed and con- nected. • All external and internal sounder are connected. • All wired zone circuits are connected. •...
1. The factory default Access Codes 02 to 16 and the Duress Code must be changed by USER 1 to a four digit number to activate them. See “9751 User Guide” or “9752 User Guide” for a more detailed explanation of changing user access codes.
Page 40
4. Programming To change: Key-in: Notes Default Country Selection nn = country, one of: 0 = UK (Y) 5 = France 1 = Ireland 6 = Denmark 1 = Italy 6 = Belgium 2 = OEM 1 7 = Sweden 2 = Spain 7 = Germany 3 = OEM 2...
Page 41
4. Programming To change: Key-in: Notes Default Zone Configuration 0 Close Circuit 4 wire 1 Fully Supervised Loop LS Chime Output n Loudspeaker chime volume 0 = Off ( Keypad only) 1=low, 9=max RedCare Reset 0 Off 1 On Show Panel Account Name 24 (keypad displays name) Return to programming mode Internal Sounder...
Page 42
4. Programming To change: Key-in: Notes Default Level A Exit Mode 0 Timed 1 Terminated 2 Final door set 3 Lock Set System Auto Re-Arm 0 Rearm Never 1 Rearm 1 2 Rearm 2 3 Rearm 3 4 Rearm Always Bell Delay 0 No delay 1 1.5 minutes...
Page 43
4. Programming To change: Key-in: Notes Default Set Time and Date ..see “Setting Time and Date” Omit Tamper Allowed 0 Alarm contacts only 1 Alarm plus tamper contacts Abort reset 0 Abort System 1 Abort User BVVO Superv’n Response 54 0 Disabled (9752 only) 1 Enabled...
Page 44
4. Programming To change: Key-in: Notes Default Level C Final Exit 0 C=FE = FE (Final exit) 1 C=FE = NA (Normal alarm) Level C Entry Route 0 C=ER = ER (Entry route) 1 C=ER = FE (Start entry timer) Level C Exit Mode 0 Timed plus low tone 1 Instant set...
Page 45
4. Programming To change: Key-in: Notes Default Level D Exit Time 1 10 Seconds (9752 only) 2 20 seconds 3 30 seconds 4 45 seconds 5 60 seconds 6 120 seconds Output 1 Type, one of Where n is one of the following: Bell (default) Smoke sensor reset EE follow...
4. Programming To change: Key-in: Notes Default Test Internal Sounder Internal sounders operate, press end test. Test Keypad Sounder Keypad sounders operate, press end test. Engineer Walk Test* Zn indication and chime operate when * See “5. Testing” cct open (Clear) End walk test Load Defaults Load defaults...
Page 47
4. Programming To change: Key-in: Notes Default Answer On One Ring 0 One ring off Downloading option 1 One ring on Access Mode 0 Callback off (Attended) 1 Callback on 2 Callback any (Unattended) Communicator Tel No 1 Maximum 31 digits Communicator Tel No 2 Maximum 31 digits Account No 1...
Page 48
4. Programming To change: Key-in: Notes Default Radio Zone Supervision 0 Full alarm (all sounders plus comms) Fail Response 1 Internal, external and keypad sounder 2 Keypad sounders 3 Comms only 4 Inhibit set Telecommand requires 0 Yes Entry Door to Unset 1 No Extended Report Mode 0 Basic...
4. Programming To change: Key-in: Notes Default Note: The following Commands are available if you select option 1 for Com- mand 89. Confirm Timer nnn is a time in the range 001 to 999 minutes. Default 030 minutes. Internal Sounder 0 Sounder on Unconfirmed Alarm 1 Sounder on Confirmed Alarm External Sounder...
4. Programming Restoring the Access Codes (1st stage reset) If the user and/or engineer codes are lost, then: First remove mains power and then open the case and disconnect the battery. Identify the NVM Reset pins and Kick Start pins on the main pcb (see Figure 4).
4. Programming Zone Programming (Commands 01 to 24 (32 on 9752)) The zone programming Commands 01 to 32 take three or more digits. The first two digits describe the zone type, subsequent digits describe the zone attributes. The format for a zone Command number changes, depending on whether the zone is connected to the control unit or to an expander.
4. Programming Zone Types The following types are available: Not Used (NU) The system ignores Zones with this type. Key in 00 for a zone that will not be used. Note: If a zone is programmed as ‘Not Used’, it is not necessary to link the circuit or anti-tamper connections.
Page 53
4. Programming Technical (TC) (Key in 08). Use this zone type when you want to monitor equipment, for example a freezer, without raising a full alarm. If a technical alarm zone is activated while the system is set, the system makes no audible alarm. However, when a user unsets the system the keypad indicates a fault.If a technical alarm zone is activated while the system is unset then the system starts a pulsed...
4. Programming To set Level A do not assign a Keyswitch zone to levels B, C or D. To set any other level assign the Keyswitch zone to a single level. Momentary - KM (Key in 11). Use this zone type to connect a momentary keyswitch to a single zone.
Page 55
4. Programming days after you return the control unit to user mode. If the zone is opened while the system is set then the Service LED glows and the control unit logs the event as a “Soak Test Fail Zn” (n is the zone number) without sounding any bells or starting signalling.
4. Programming Change Engineer Code (Command 20) To change the Engineer access code: Make sure you are in programming mode. Key in 20 and press 20:Code The display shows: Key in a new four digit Engineer access code. 20:Code **** The display shows: Press Zone Configuration (Command 21)
4. Programming Continuous Sounder (Command 25) Option 0 of this Command makes the internal sounder follow the external bell delay and duration times. Option 1 makes the internal sounder continue after the external bell times out. Local Sounder Delay on Entry (Command 26) This Command controls the time at which local sounders operate in response to an entry alarm.
4. Programming This Command determines what the system will do if a user strays from an entry route during entry. (This Command is available to provide compliance with EN 50131-1.) Use option 0 to make the system give an alarm immediately if the user strays from an entry route during entry.
4. Programming PA Reset (Command 34) If you wish to make the system engineer reset after a PA alarm then use option 1. For user reset use option 0. First Circuit Response (Command 35) If you select option 0 (Lock out) then the complete system rearms at the end of the programmed bell run time, but excludes the first zone to activate during the set cycle.
4. Programming select option 1 (engineer) then you must enter the engineer access code at a keypad to reset the system after a system tamper alarm. Level A Exit Mode (Command 39) Use this Command to select the exit mode for Level A (full set): Option 0 Timed.
4. Programming Note that the keypads give a double beep confirmation tone at the end of all setting modes. If you select Timed (options 0), Terminate (option 1), or Final Door (option 2) exit modes the system allows a seven second settling time after pressing an exit terminate button or closing a final door.
4. Programming Entry/Exit Tone Volume (Command 45) Use this Command to set the volume of entry/exit tones from the internal sounder. If you select option 0 then the internal sounder gives no entry/exit tones. If you select option 1 then the internal sounder gives quiet entry/exit tones, while option 9 gives the loudest entry/exit tones.
4. Programming displays it on the keypad. The user calls the ARC and tells them the number shown on the keypad display. The ARC verifies the user's identity, then enters the code number into a special programmer. The programmer gener- ates an ‘Anti Code’, which the ARC gives back to the user.
4. Programming contact with the control unit for more than 15 minutes. If a detector loses contact for more than two hours the control unit raises an alarm (see Com- mand 128). If you select option 0 the control unit will report supervision failure as de- scribed for Command 128.
4. Programming Level B Final Exit Operation (Command 60) Command 60 controls how the system will treat Final Exit zones in Part Set Level B. When the Command option is set to 0 any Final Exit zones included in Part Set B will continue to act as Final Exit zones during Part Set B. When the option is set to 1 any Final Exit zones included in Part Set B will act as Normal Alarm zones during Part Set B.
4. Programming Level B Exit Time (Command 65) This Command sets the exit time for Level B. See “Programming Com- mands” for options. Level C Final Exit Operation (Command 70) Command 70 controls how the system will treat Final Exit zones in Part Set Level C.
4. Programming Level C Entry Time (Command 74) This Command sets the entry time for Level C. See “Programming Com- mands” for options. Level C Exit Time (Command 75) This Command sets the exit time for Level C. See “Programming Com- mands”...
4. Programming Output Type Bell (Key in 00) The control unit operates this output during an alarm. Use Command 41 to control bell delay and 42 to control bell duration. If you enable Alarm Confirmation (Command 89) then use Command 162 to select whether the control unit activates the bell on a first or a confirmed alarm.
4. Programming Strobe (Key in 08) In an alarm the system operates the output. The output remains active until the user disarms the system. Smoke Reset (Key in 09) This output is designed to be connected to low voltage smoke detector reset terminals. The control unit operates the output for 3 seconds when the system is reset after any alarm has occurred.
4. Programming 3. If Alarm Abort is enabled (Command 36 1) Channel 3 restores if the user unsets the system. Dual Ply Entry Warning (Command 86) Note: Disable Alarm Confirmation (Command 89) to gain access to this Command. If users habitually exceed the entry time use option 1 to add a 30 second extension during which the internal sounders give a warning tone.
4. Programming Press 1. (You can press to stop the procedure if you change your mind at this stage.) Press The system loads the factory default Command values, erasing all previously programmed values. Notes:The log is protected and cannot be erased by the Installer. Leave Programming Mode (Command 99) To leave programming mode: Key in 99...
4. Programming Dual (3) Reports to two different receiver numbers (see Com- mands 115 and 116). Operation: The communicator dials the first telephone number and attempts to connect to the first ARC. If received and acknowledged, the communicator dials the second number and attempts to transmit to the second ARC.
4. Programming Line Fail Response (Command 106) This Command lets you program the system to respond with either audible or silent alarms when the system detects a fault on an attached telephone line. The exact response depends on whether the system is set or unset, as follows: Disabled (0) The control unit does not monitor the telephone line.
The control unit can be programmed from a PC using <Downloader> soft- ware. You can connect the PC to both the 9751 and 9752 control units over the telephone network. In addition, you can connect the PC to the 9752 control unit locally using a cable.
4. Programming alarm system now knows to expect a call within the next 10 to 90 seconds. <Downloader> then rings the alarm system again, within 10 to 90 seconds. The alarm system answers after the first ring. Note: When using "Answer on 1 Ring" set the number of rings in "Rings to Answer" (C112) to a higher number than that used by the equipment sharing the telephone line with the alarm system.
4. Programming Communicator Telephone Numbers (Command 115/116) Use this Command to store the telephone numbers that the communicator will use to report alarms. The system will accept one telephone number if you choose Single call mode in Command 101, or two telephone numbers if you select Alternate or Dual call mode.
4. Programming Downloader Telephone Numbers (Commands 118/119) Use this option to program up to two separate, 31-digit telephone numbers that the system will use during downloading. When a connection has been made, the remote PC operator selects the telephone number which the control unit will call back to (for example home or office).
4. Programming Notes:1. 13 Open and 14 Close provide the same functions as 4 Open/Close, but on two separate channels. 2. 15 Zone omitted - the control unit sends this signal for five seconds when a user omits a zone. 3.
4. Programming No Closing Signal if More Than One Circuit Omitted (Command 125 (9752 only)) Note: This Command is required for Belgian BVVO approval. This option is only available if you have selected Scancom Fast format. When this option is enabled the control unit will NOT transmit a Close signal if a user has omitted two or more zones.
4. Programming Report Mode (Command 131) SIA reports are called ‘Telegrams’. Each telegram contains the site identifica- tion number (normally six digits long) and relevant event information. The amount of information reported depends on the SIA mode you select: Basic, Summary, Intermediate, or Full.
4. Programming If the keypad display shows “Custom” when you enter Command 143 then <Downloader> has been used to program this Command. Plug by Communicator Outputs (Commands 151 to 158) The main circuit board of the control unit provides eight programmable outputs that can be used to control a plug-by communicator.
4. Programming Internal Sounder (Command 161) Note: Enable Alarm Confirmation (Command 89) to access this Command. This Command selects whether the control unit will operate the internal sounder for a confirmed alarm of for an unconfirmed alarm. Option 0 The control unit operates the internal sounder for an unconfirmed alarm.
4. Programming Option 2 ensures that if the user unsets the system by means of a proximity reader or telecommand, they cannot cause a confirmed alarm by wandering from the entry route. However, if an intruder goes through the front door, they will eventually cause a confirmed alarm if they are still wondering around the premises after the entry time has expired.
4. Programming ACPO DD243: 2002 Compliance Please study this section If you are installing an intruder alarm system in England, Wales and Northern Ireland which has remote signalling, requires the local Police Authority to issue a URN (Unique Reference Number) and you have chosen to use “Sequential Alarm Confirmation”...
4. Programming Confirm After Entry = 2 = The control unit starts a confirmed alarm if an intruder activates two separate zones after the entry timer expires. Use this option to comply with section 6.4.5. Command 164 – User Reset After Confirmed Alarm = 1 = enabled to allow users to reset the system after a confirmed alarm.
5. Testing 5. Testing Reading the Log (Command 90) The control unit keeps a 250 event log of recent events. Each event is represented by a short text message, shown below and on the next page. To review the event log, make sure the system is in programming mode, then: Key in 90 The display shows the most recent event in the log.
Page 88
5. Testing Al Confirm Znn Confirmed alarm on zone nn Defaults Loaded All programming defaults loaded Download OK Download completed successfully Unn Dload Fail Download failed EEProm Fail, Control unit memory damaged Expander Missing Expander disconnected Expander Restore Expander reconnected Expander Tmp Expander tamper alarm Expander Tmp Rst...
5. Testing Telecmmd PA PA started from telecommand Unn Change Unn User nn changed access code for user nn Unn Delete Unn User nn deleted access code for user nn Unn Off-Site Engineer exited programming mode Unn On-Site Engineer entered programming mode Bypass Supr.
Page 93
Index Humidity ............ 7 Mains connection ........16 Inputs ............7 No close if..........73 Installation overview ....... 13 Normal alarm .......... 46 Internal sounder Not used ..........46 confirmed alarm ............ 77 Internal sounder test ....... 83 Omit ............5 Omit allow ........
Page 94
Index Report mode ........... 74 contact ID .............. 75 fast format ............. 71 Tamper alarm annunciation ....56 SIA ................ 74 Tamper as burglary ......... 75 Report restorals ........72 Tamper communication ......53 Contact ID ............. 75 Reporting type ........66 Technical ..........
Page 96
ECLARATION OF CONFORMA NCE Cooper Security Ltd issues this certificate to certify that the equipment known as: 9751 or 9752 Complies with the following directive: 1995/5/EC R&TTE Directive Signed Mr S. Taylor, Technical Director Date: 4 September 2002 Cooper Security Ltd...
Need help?
Do you have a question about the 9751 and is the answer not in the manual?
Questions and answers