13. Actuator positions
during the prepurge time
Menu level 1
Menu level 2
Params & Display
RatioControl
Β
14. Ignition positions
Menu level 1
Menu level 2
Params & Display
RatioControl
172/327
Building Technologies
The burner control stops startup during the prepurge phase (phase 24).
The positions of the actuators for prepurging can thus be set very straightforwardly.
Menu level 3
GasSettings
Note!
The prepurge position of auxiliary actuator 3 is approached in phase 32 (flue gas
recirculation (FGR)).
After the settings have been made, the program stop in the prepurge position should be
replaced by the program stop of the ignition position in phase 36.
The burner control continues the startup sequence until the ignition position (phase 36)
is reached. Then, it stops again, enabling the actuator's ignition positions to be set.
Menu level 3
GasSettings
To verify the ignition positions again, the control sequence can be stopped in interval
phase 44 or 52 (interval with ignited flame on completion of the relevant safety time).
Upon deactivation of the program stop, the burner continues its program until the
operating phase (phase 60) is reached.
If no point for the fuel-air ratio control system has as yet been predefined, the first
curvepoint «P1» to be adopted on a preliminary basis are the ignition positions of the
actuators.
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
Menu level 5
SpecialPositions
PrepurgePos
Menu level 4
Menu level 5
SpecialPositions
IgnitionPos
Menu level 6
PrepurgePosAir
PrepurgePosAux
1
PrepurgePosAux
Only LMV52
2
PrepurgePosAux
LMV50/LMV51.3/
3
LMV52
PrepurgePosVSD
Menu level 6
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux1
IgnitionPosAux2
Only LMV52
IgnitionPosAux3
LMV50/LMV51.3/
IgnitionPosVSD
LMV52
CC1P7550en
22.05.2018