Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Contents Introduction ..............................5 General Information for the users ......................5 Manufacturer Warranty .........................5 Explosion Proof Warning (Only for Intrinsic safety type positioners) ............6 Product Description ...........................7 General ..............................7 Main Features and Functions .......................7 Label Description ..........................8 Product Code ............................9...
Page 3
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Connection ............................29 Ground ............................... 30 Adjustments ............................. 31 A/M switch adjustment ........................31 Orifice Installment ..........................32 Maintenance ............................. 33 Supply air ............................33 Seals ..............................33 Typical connection of YT-3300 with Profibus PA and Foundation Fieldbus ........
Page 4
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 9.8.7 Acting Type (SINGLE / dOUBLE) ....................50 9.8.8 Lever Type (STd / AdT) ......................... 51 Diagnostic (dIAGNO) ......................... 52 9.9.1 Diagnosis Limit Configuration (LIMT CFG) ..................52 9.9.1.1 Deviation (dEV) ........................
Introduction General Information for the users Thank you for purchasing Rotork YTC Limited products. Each product has been fully inspected after its production to offer you the highest quality and reliable performance. Please read the product manual carefully prior to installing and commissioning the product.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Explosion Proof Warning (Only for Intrinsic safety type positioners) Please ensure the unit is being used and installed in conformity with local, regional, and national explosion proof within the proper safety barrier environment. ➢...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Product Description General YT-3300 / 3350 (PA/FF) series Smart Valve Positioner accurately controls valve stroke in response to an input signal of Communication from the controller. Built-in micro-processor optimizes the positioner’s performance and provides unique functions such as Auto-Calibration, Profibus PA or Foundation fieldbus Protocol Communications.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Product Code YT-3300 / 3350 (PA/FF) series follows suffix symbols as follows. 2.4.1 YT-3300 / 3350 1 Linear (Positioner is attached the right yoke of actuator.) Motion Type Rotary Single Acting type...
2 kg (4.4 lb) 5.1 kg (11.2 lb) Painting Polyester Powder Coating Tested under ambient temperature of 20 °C, absolute pressure of 760 mmHg, and humidity of 65 %. Please contact Rotork YTC Limited for detailed testing specification. Ver. 1.00...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Certifications ※ All certifications below are posted on Rotork YTC Limited homepage(www.ytc.co.kr). ATEX ➢ Type : Intrinsic safety Rating : II 2G Ex ia IIC T5/T6 Gb, II 2D Ex ia IIIC T100°C/T85°C Db, IP6X Certification No.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Parts and Assembly Fig. 2-1: exploded view 1. Base Cover 8. Pilot Block 2. PCB Cover 9. Base body 3. Main PCB 10. Feedback Lever 4. Torque Motor 11.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Installation Safety When installing a positioner, please ensure to read and follow safety instructions. ➢ Any input or supply pressures to valve, actuator, and / or to other related devices must be turned off.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Linear positioner Installation Linear positioner should be installed on linear motion valves such as globe or gate type which uses spring return type diaphragm or piston actuators. Linear positioner Installation of Standard lever type 3.3.1 Fig.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 3.3.1.2 Standard lever type positioner Installation Steps 1) Assemble the positioner or remote sensor with the bracket made in previous step by fastening the bolts. Fig. 3-3: Standard Lever Type 2) Attach the positioner (or remote sensor) with the bracket to the actuator yoke –...
Page 18
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 5) Insert the connection bar between the feedback lever and lever spring. The connection bar must be located upward from the lever spring as shown below left figure. If it is located downward from the lever spring as shown below right figure, the connection bar or the lever spring will be worn out quickly because of excessive strong tension.
Page 19
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 7) Check the valve stroke. The stroke numbers are engraved on the feedback lever of the positioner. Position the connection bar at the number on the feedback lever which corresponds with the desired valve stroke.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Installation of Adapter lever type (on tubeless actuator) 3.3.2 Installation of adapter lever type example Fig. 3-9: Before proceeding with the installation, ensure following components are available. ➢...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 3.3.2.2 Adapter lever type positioner Installation Steps 1) Remove Out1 Plug(Fig. 3-11) on the bottom of the positioner. Plug up out1 port of gauge block with 1/4 plug using sealant. 2) Check the valve stroke.
Page 22
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Fig. 3-12: Adapter Lever Type 5) Connect Air-filter regulator to Supply port of the positioner. 6) Turn the Auto/Manual switch counterclockwise (toward “M”). Refer to 6.1 for more detail. Supply enough air pressure to the actuator in order to position the valve stroke at 50 % of the total stroke.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Rotary positioner Installation Rotary positioner should be installed on rotary motion valve such as ball or butterfly type which uses rack and pinion, scotch yoke or other type of actuators which its stem rotates 90 degrees. Before proceeding with the installation, ensure following components are available.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Rotary Bracket Information 3.4.2 The rotary bracket set (included with the positioner) contains two components. (but the upper brackets of Fork lever type and Namur type are different.) The bracket is designed to fit onto the actuator with 20 mm, 30 mm and 50 mm stem height (H) according to VDI/VDE 3845 standard.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Fig. 3-16: Actuator stem Height Fig. 3-17: Exploded Brackets Rotary positioner Installation Steps 3.4.3 1) Please check the actuator’s stem height and adjust the brackets by referring to the above bracket table.
Page 26
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 5) (Only Fork lever type) After setting fork lever position, fasten lock nuts which are located on the bottom of the fork lever. Ensure to set the gap between the top of upper bracket and the top of the fork lever within 23 ~ 28 mm.
Always recommended to use air filter regulator (i.e. YT-200 series). ➢ ➢ Rotork YTC Limited has not tested positioner’s operation with any other gases other than clean air. Please contact Rotork YTC Limited for any questions. Supply Pressure Condition ➢...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Connection – Piping with actuator Single acting actuator 4.4.1 Singe acting type positioner is set to use only OUT1 port. OUT1 port of positioner should be connected with supply port of actuator when using spring return actuator of single acting type.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Connection – Power Safety ➢ There are two conduit entries on the product. See “2.4 Product Code” for conduit entry threads. Before connecting terminal, ensure that the power is off completely. ➢...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Ground 1) Ground must be done before operating the positioner. 2) Open base cover and there is an internal ground “F.G” on the left hand. An external ground bolt is located next to the conduit entry. Please make sure that the resistance is less than 100 ohm.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Adjustments A/M switch adjustment 1) On the right hand bottom of positioner, there is A/M switch (Auto/Manual). A/M Switch allows the positioner to be functioned as by-pass. If the switch is turned clockwise (toward “A”) and it is fasten tightly, then the supply pressure will be transferred to actuator through outport by positioner control.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Orifice Installment Hunting can be occurred when the actuator’s volume is too small. In order to prevent hunting, orifice can be used. By installing the plate type orifice, the flow rate of the supply pressure to actuator can be reduced.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Maintenance Supply air If Supply air pressure is not stable or Supply air is not clean, the positioner may not function properly. Air quality and pressure should be checked regularly to see if the air is clean and pressure set is normal. Seals Once a year, it is recommended to check if there are any damaged parts of the positioner.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Typical connection of YT-3300 with Profibus PA and Foundation Fieldbus Profibus PA The diagram below shows how to connect YT-3300 PA using EDD for Simens SIMATIC PDM. Commands from the host PC are transmitted to the DP/PA coupler through the Profibus DP interface module, and then converted into low-speed signals and transmitted to the positioner.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Configurations for high speed solution & low speed solution Fig. 8-2: High Speed solution with Profibus PA Link & Low speed solution with DP/PA coupler Foundation Fieldbus YT-3300 is connected to junction box of Foundation Fieldbus HI bus system (31.25 kbps) and its signals are transmitted to HSE (High Speed Ethernet) through Fieldbus controller (or linking device).
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Auto Calibration and PCB Operation Warning Following process will operate valve and actuator. Before proceeding with any Auto Calibration, please separate valve from the entire system by using bypass valve, so Auto Calibration will not affect entire valve process.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual ※ By pressing <ESC> button several times from any MODES, it will return to “RUN PV” mode. Therefore, if the users have entered the wrong mode by mistake or do not wish to proceed with their current work, they could return to “RUN PV”...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual AUTO2 Calibration (AUTO2) 9.4.2 AUTO2 changes all of the parameters. It is recommended to perform AUTO2 when the positioner has been installed on the valve for the first time or the positioner has been reinstalled after disassemble from an actuator.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Manual Mode (MANUAL) Manual mode is used to manually raise or lower the valve stem. In the manual mode, the positioner does not control the valve according to the electric signal inputted from the outside but the stroke of the valve can be adjusted only by the operation of <UP>...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Dead-Zone (dEAdZONE, %) 9.6.1 Dead-Zone indicates the percentage of error allowance. In case of high level of packing friction, which may cause hunting, increasing the value of Dead-Zone can stable the valve operation. 3 seconds →...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual I Value (KI) 9.6.3 I value indicates the additional compensation signal based on the percentage of error allowance. As the value increase, it is more likely to have hunting. As the value decreases, the positioner will move slowly to the target position.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual KF Up Value (KFUP) 9.6.6 KF Up control value corrects valve friction when moving from 0 % to 100 %, reducing the dead time. <UP>/<DOWN> → → →...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Control mode (CTRL) 9.6.8 This function is used to select the PID tuning set that already stored corresponding to the stability or responsiveness, not in the way the user changes the KP, KI, or KD manually. •...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Hand Calibration Mode (HAND CAL) Hand Calibration mode is used when the zero-point or end point of the valve is required to be readjusted after Auto Calibration has been performed. Zero-Point (PV ZERO) and End-Point (PV END) for Valves 9.7.1 PZ ZERO adjusts the zero point of the valve, and PV END adjusts the end point of the valve.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Valve Mode (VALVE) Valve mode offers useful and various function settings for operating the control valve. Below is the list of functions which could be set from Valve mode. 1) Acting Adjustment (ACT RA / dA) 2) Characteristic Adjustment (CHAR) 3) User Characteristics (USER SET)
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Valve flow Characteristic Adjustment (CHAR) 9.8.2 The valve flow characteristic can be set on the field’s requirement. There are 4 types of characteristics – linear (LIN), user setting (USR), quick open (QO), and equal percentage (EQ).
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual User defining flow Characteristics (USER SET) 9.8.3 User can make its own flow characteristic curve with this mode. USER SET can be set in two ways, 5 points and 11 points.
Page 48
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 2) 11 points setting can be set with 1mA intervals. The initial positions are P0(0 %), P1(10 %), P2(20 %), … P9(90 %) and P10(100 %) but user can change the % values to different values. User can change all 11 points or only change partially and exit the menu by pressing <ESC>...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Tight Shut Open (TSHUT OP) 9.8.4 Tight shut open shows the current value in percentage (%). Input current of 4 mA is 0 %, 20 mA is 100 %.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Interpolation Mode (ITP ON/OFF, ITP USER SET) 9.8.6 In case of linear positioner, the error of accuracy occurs when the linear motion of actuator changes into the rotary motion of feedback lever. After the auto calibration, the positioner turns on ITP function with an appropriate value of interpolation automatically.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Lever Type (STd / AdT) 9.8.8 Displays or changes current lever type into standard type or adapter type. If the Lever type mode is set correctly, the accuracy will be worse at ITP ON than at ITP OFF. <UP>/<DOWN>...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Diagnostic (dIAGNO) Below is the list of functions which could be set from Diagnostic mode. 1) Diagnosis Limit Configuration (LIMT CFG) Deviation (dEV) Deviation Time (dEV TIME) C.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 9.9.1.1 Deviation (dEV) This is used to set the deviation in % between the target position and actual position. Default is 10 %. Alarm is triggered if actual deviation greater than the preset deviation “dEV” persists longer than the preset Deviation Time “dEV TIME”.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 9.9.1.5 Low Low Limit Alarm (LL ALRM) and High High Limit Alarm (HH ALRM) This is used to set a position to trigger Low Low Limit Alarm or High High Limit Alarm when the valve moves to the position lower than LL ALRM or higher than HH ALRM.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual PST Introduction 9.9.2 Unlike FST (Full Stroke Test) where a valve is fully closed and opened, PST (Partial Stroke Test) is a method used to test a percentage of the possible failure of the valve by slightly closing and opening the valve.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual PST Mode (PST) 9.9.3 To run PST, select a PST mode. There are 3 mode for running PST. Mode Description PST OFF Turn off PST. It’s a default mode Run PST once immediately.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 9.9.4.1 Start Position (START PO) It is used to set a start position when PST initiates. The position must be in between 0 and 100 %, and default value is 100 %.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 9.9.4.4 Interval (INTERVAL) Interval time (days) between 1 PST and the next PST. The value must be between 1 ~ 365, and default value is 365 (days). <UP>/<DOWN>...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual 9.9.4.7 Latency (LATENCY) Latency for next movement after valve move. The value must be between 1 ~ 60 sec, and default value is 10 (sec). <UP>/<DOWN> → →...
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual View Mode (VIEW) 9.10 Displays various information of the positioner. <DOWN> 3 seconds → → → Press <UP> or <DOWN> button if the above is not displayed. <DOWN>...
Page 62
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual bIAS 25 BIAS value when valve position is at 25 % bIAS 75 BIAS value when valve position is at 75 % Total operation time. If the device is used for less than 1 hour, the time does not accumulate.
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Warning / Alarm Code This is the status and alarm code displayed on the LCD screen when a change in the state of the product and process occurs while using the product. Please refer to the table below to check the code for the status and alarm and take the appropriate action.
Page 64
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Category Alarm Code Code Description and Cause Action ➢ Displayed when the valve does not move even though the positioner sends “Full Open” signal during ➢ Check if air pressure is Auto Calibration.
Page 65
Smart Positioner YT-3300 / 3350 series (Profibus PA & Foundation Fieldbus) Product Manual Warning Category Code Description and Cause Action Code ➢ Warning is triggered when the actual position (PV) is lower than ➢ Make sure that the "LO setting in "LO ALARM". LO ALRM ALRM"...