SECTION 14 42 13
INCLINE WHEELCHAIR LIFTS
Display hidden notes to specifier by using "Tools"/"Options"/"View"/"Hidden Text".

PART 1 GENERAL

PART 1 1SECTION INCLUDES
A.
Indoor inclined platform wheelchair lifts.
B.
Portable emergency evacuation device.
PART 1 2RELATED SECTIONS
A.
Section 03300 - Cast-In-Place Concrete: Anchor placement in concrete.
B.
Section 04800 - Masonry Assemblies: Anchor placement in masonry.
C.
Section 06100 - Rough Carpentry: Blocking in framed construction for lift
attachment.
D.
Section 09260 - Gypsum Board Assemblies: Stair walls.
E.
Section 13650 - Fire Alarm System: Building Fire Alarm Integration system to
connect the lift control system with the building fire alarm system.
F.
Division 16 - Electrical: Electrical power service and wiring connections.
G.
Division 16 - Electrical: Concealed low voltage control wiring.
H.
Division 16 - Electrical: Intercom and wiring.
PART 1 3REFERENCES
A.
ASME A17.5 - Elevator and Escalator Electrical Equipment.
B.
ASME A18.1a 2001 - Safety Standard for Platform Lifts and Stairway Chairlifts.
C.
ASME A18.1, Section 6, Private Residence Inclined Platforms.
X3 Specification 23265-A-DS Section 14 42 13
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the X3 and is the answer not in the manual?

Questions and answers

Summary of Contents for Garaventa Lift X3

  • Page 1 PART 1 3REFERENCES ASME A17.5 - Elevator and Escalator Electrical Equipment. ASME A18.1a 2001 - Safety Standard for Platform Lifts and Stairway Chairlifts. ASME A18.1, Section 6, Private Residence Inclined Platforms. X3 Specification 23265-A-DS Section 14 42 13 Page 1...
  • Page 2 Provide platform lifts in compliance with: 1.CSA B355 - Lifts for Persons with Physical Disabilities. 2.CSA B44.1/ASME A17.5 - Elevator and Escalator Electrical Equipment. 3.CSA - National Electric Code. PART 1 7DELIVERY, STORAGE, AND HANDLING X3 Specification 23265-A-DS Section 14 42 13 Page 2...
  • Page 3 Section 01600. PART 2 2STAIR LIFT FOR STRAIGHT STAIRWAYS Inclined Platform Lift: Garaventa Lift Stair-Lift Model X3 to serve one flight of straight stairs, with two landings and two stops. Lift consists of an extruded aluminum guide rail, a folding platform that is moved along the guide rail by an integrated rack and pinion drive system, overspeed safety system and call stations at each landing.
  • Page 4 4 lb/f (20 N) of pressure is encountered from either inside or outside of the platform. Platform is permitted to travel in the opposite direction of obstruction to allow clearing. 10. Platform Kick Plate: X3 Specification 23265-A-DS Section 14 42 13 Page 4...
  • Page 5 (11.9 kg/m) with integrally mounted zinc plated gear rack. Lower Rail: 1-1/2 inches (38 mm) by 2-1/2 inches (64 mm) anodized aluminum extrusion. Rail Mounting: Direct Mount Solid Walls: Rails directly mounted to the stairway wall. X3 Specification 23265-A-DS Section 14 42 13 Page 5...
  • Page 6 Steel cabinet and door panel. Available only in Satin Gray, left hinged only. Size: Height 45-3/8 inches (1151 mm), width 20 inches (508 mm), depth 11 inches (279 mm). PART 3 EXECUTION PART 3 1EXAMINATION X3 Specification 23265-A-DS Section 14 42 13 Page 6...
  • Page 7 Schedule tests with agencies and Architect, Owner, and Contractor present. PART 3 5PROTECTION Protect installed products until completion of project. Touch-up, repair or replace damaged products before Substantial Completion. END OF SECTION X3 Specification 23265-A-DS Section 14 42 13 Page 7...