Installation, Operation, and Maintenance Solid State Starter Conversion RTHA, RTHB, RTHC, RTHD RTHA 50/60 hz units RTHB 50/60 hz units RTHC 50/60 hz units RTHC 50/60 hz units This manual covers both Benshaw MX and MX2 solid state starters MX starter used for units manufactured until November 2010...
Page 2
Introduction This manual is intended to assist in the conversion of RTHA, RTHB, RTHC or RTHD starters to a Benshaw solid WARNING state starter configuration. Proper Field Wiring and Grounding Read this manual thoroughly before operating or Required! servicing this unit.
Page 3
Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Identify Existing Solid State Starter Trane has used three styles of solid state starters over the past several years. Determine whether the SSS is an A515, Figure 3. Cutler-Hammer EasySTART EasySTART or Intelligent Technology (IT) by comparing the unit to the photographs below.
UL listing. • If the unit was built with a circuit breaker, contact Trane Service Parts for shunt option or source locally. • The customer must obtain a UL inspection if a UL listing is required.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
The following components of an Wye -Delta starter need Install per your state and local codes. to be removed prior to installing the RediStart starter: • 2R1-2R6 Resistors Figure 5. Remove the highlighted components (wye-delta starter) — RTHA-YD 2TB2 2TB3 2R1-2R6 2TB1 2CB1...
8 are removed, refer to Figure 7, p. 9 for the noted below. approximate locations of the new Redistart components. Figure 7. Location of Benshaw starter and additional components (highlighted) — RTHA 2TB2 2K300 2K400 2TB3 2K300 Benshaw Shunt...
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
Page 11
RTHA Units with Wye-Delta Starters Figure 8. Control power wiring (new wiring bold/highlighted in red) — RTHA (MX starter) 1K400 1K400 1K400 to shunt trip coil RLC-SVN005B-EN...
Page 12
RTHA Units with Wye-Delta Starters Figure 9. Control power wiring (new wiring bold/highlighted in red) — RTHA (MX2 starter) To Shunt Trip 2K400 2TB2-5 2TB2-6 2K400 2U1-B To motor 1TB5-9 oil valve To start and 1TB5-10 1TB5-10 hour meters OT SWITCH...
Page 13
RTHA Units with Wye-Delta Starters Figure 10. Power wire (new wiring bold/highlighted in red) — RTHA RLC-SVN005B-EN...
For variable frequency drives • 2CR1 control relay or other energy storing components provided by Trane For units with wye-delta starters, remove the associated or others, refer to the appropriate manufacturer’s contactors and resistors. See “RTHA Units with Wye-Delta...
RTHB Units with A515 (or Wye-Delta) Starters Figure 12. Photograph of A515 solid state starter Installation of Benshaw Starter Once all of the A515 components in Figure , p. 15 the approximate locations of the new Redistart removed, the 2T4 transformer needs to be moved to make components.
For variable frequency drives or other energy with the Benshaw starters. storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable Additional Components waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have “Additional Components,”...
Page 17
RTHB Units with A515 (or Wye-Delta) Starters Figure 15. Control power wiring (new wiring bold/highlighted in red) — RTHB (MX Starter) To Shunt Trip 2K400 120/240 VAC (input) Benshaw 2K400 2K400 2TR1 2K300 2K300 to shunt trip coil RLC-SVN005B-EN...
Page 18
RTHB Units with A515 (or Wye-Delta) Starters Figure 16. Control power wiring (new wiring bold/highlighted in red) — RTHB (MX2 Starter) TO SHUNT TRIP (Breaker) 2K11/ 2K400 120/240 VAC (input) 2K11/ 2K11/ OT SWITCH 2K400 2K400 Optional contact. See note 1. To T1 To T1 To T2...
Page 19
RTHB Units with A515 (or Wye-Delta) Starters Figure 17. Power wiring (new wiring bold/highlighted in red) — RTHB To UCP2, J16-1 To TB nuetral To J5-1 on UCP2 To J5-2 on UCP2 To J5-3 on UCP2 UCP2 CT’s To J5-4 on UCP2 To J5-5 on UCP2 To J5-6 on UCP2 2CT1...
For units with wye-delta starters, remove the associated inadvertently energized. For variable frequency drives contactors and resistors. See “RTHA Units with Wye-Delta or other energy storing components provided by Trane Starters,” p. 8 for an example. or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors.
RTHC Units with EasySTART (or Wye-Delta) Starter Installation of Benshaw Starter Figure 19. Photograph of EasySTART — RTHC Once the EasySTART solid state starter is removed, mount the fan and the Benshaw solid state starter in the cabinet. Figure 20, p. 21 for an approximate location of components.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
Page 23
RTHC Units with EasySTART (or Wye-Delta) Starter Figure 21. Control power wiring (new wiring bold/highlighted in red) — RTHC (MX Starter) To Shunt Trip 1K400 120/240 VAC (input) Benshaw 1K400 1K400 To 1T1 To 1T2 To 1T3 1K300 2K300 1K11/ 1K400 Chiller Module...
Page 24
RTHC Units with EasySTART (or Wye-Delta) Starter Figure 22. Control power wiring (new wiring bold/highlighted in red) — RTHC(MX2 Starter) TO SHUNT TRIP (Breaker) 1K11/ 1K400 120/240 VAC (input) 1K11/ 1K11/ OT SWITCH 1K400 1K400 Optional contact. See note 1. To T1 To T1 To T2...
Page 25
RTHC Units with EasySTART (or Wye-Delta) Starter Figure 23. Power wiring (new wiring bold/highlighted in red) — RTHC To UCP2, J16-1 To TB nuetral To J5-1 on UCP2 To J5-2 on UCP2 To J5-3 on UCP2 UCP2 CT’s To J5-4 on UCP2 To J5-5 on UCP2 To J5-6 on UCP2 To TB3 - CT1...
For variable frequency drives or other energy • 1K400 (replace) storing components provided by Trane or others, refer to • 1TB1 the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with...
RTHC Units with IT (or Wye-Delta) Starter Installation of Benshaw Starter Figure 25. Photograph of IT solid state starter — RTHC Once all of the above components are removed, see Figure 26, p. 27 for the approximate locations of the new components.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
Page 29
RTHC Units with IT (or Wye-Delta) Starter Figure 27. Control power wiring (new wiring bold/highlighted in red) — RTHC(MX Starter) To Shunt Trip 1K400 120/240 VAC (input) Benshaw 1K400 1K400 1K300 2K300 1K11/ Chiller 1K400 Module J22-1 To J22-1 to shunt Master Oil wire 75A, B trip coil...
Page 30
RTHC Units with IT (or Wye-Delta) Starter Figure 28. Control power wiring (new wiring bold/highlighted in red) — RTHC - MX2 Starter TO SHUNT TRIP (Breaker) 1K11/ 1K400 120/240 VAC (input) 1K11/ 1K11/ OT SWITCH 1K400 1K400 Optional contact. See note 1.
Page 31
RTHC Units with IT (or Wye-Delta) Starter Figure 29. Power wiring (new wiring bold/highlighted in red)— RTHC To UCP2, J16-1 To TB nuetral To J5-1 on UCP2 To J5-2 on UCP2 To J5-3 on UCP2 UCP2 CT’s To J5-4 on UCP2 To J5-5 on UCP2 To J5-6 on UCP2 To TB3 - CT1...
For variable frequency drives or other energy Starters,” p. 8 for an example. storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable Figure 30, p. 32 shows the basic layout of the IT starter waiting periods for discharge of capacitors.
RTHD Units with IT Starter Installation of Benshaw Starter Figure 31. Photo of IT solid state starter (PFCC Once the IT starter is removed, refer to Figure 32, p. 33 customer supplied) — RTHD the approximate location of the new components. The Benshaw Redistart SSS is supplied with current transformers.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
Page 35
RTHD Units with IT Starter Figure 34. Control power wiring (new wiring bold/highlighted in red) — RTHD - MX Starter To Shunt Trip Coil RLC-SVN005B-EN...
Page 36
RTHD Units with IT Starter Figure 35. Control power wiring (new wiring bold/highlighted in red) — RTHD - MX2 Starter Optional contact. See note 1. To Shunt Trip Coil NOTE: 1. Connection to start signal is required. If you don’t use this contact, you need to place a wire to the start signal. RLC-SVN005B-EN...
Page 37
RTHD Units with IT Starter Figure 36. Power wiring (new wiring bold/highlighted in red) — RTHD RLC-SVN005B-EN...
For variable frequency drives or other energy speed, the starter will hold the current at the maximum storing components provided by Trane or others, refer to current level until the UTS timer expires, the motor the appropriate manufacturer’s literature for allowable reaches full speed, or the overload trips.
Page 39
“Current Transformer Set-up (MX Only),” p. settings. P6 Software Part Number The software part number is useful for future service reasons. If calling Benshaw for service, this number Table 1. Parameter settings MX/MX2 — Trane ONLY software Parameter Description Setting Range Units Default...
Page 40
Quick Start, Initial Parameters Current Transformer Set-up (MX Only) Figure 37. RTHB - Installation of CTs CT Switch Settings When the starter is shipped from the factory, CT settings are set to match CT ratios supplied with the starter. If the MX control is changed the CT settings must be changed to match the CT ratios for that given current rating.
Remote Keypad “Parts Ordering,” p. 43for appropriate part numbers. Meeting NFPA 70 Figure 40. Benshaw remote keypad MX/MX2 A remote keypad for the Benshaw Redistart is available. In some instances, the remote keypad can be used to meet NFPA 70 guidelines for arc flash protection. The remote keypad has several features some of which are listed below: •...
Troubleshooting Troubleshooting Table 3. Troubleshooting chart Description of the Problem Possible Causes Chiller starts but only runs for a few seconds. • Typically caused from a mis-wire of the low voltage. Compressor starts immediately when power is applied. • Start command of the Benshaw Redistart wired incorrectly directly to 120 Vdc. Compressor starts, runs less than 10 seconds and...
Note:For further information on the Benshaw Redistart starters refer to “Benshaw Redistart SSS Hardware Manual #890023-02-01”. Higher amp rated starters are available upon request. Contact technical support or the local Trane parts center for further details. In the Delta RLA = (unit nameplate RLA)*1.05/1.15/1.55 (a) Digit 5 indicates Std (S) or High (H) interrupt rating.
Parts Ordering Mounting Dimensions MX Starter Figure 41. Dimensional drawing of Benshaw solid state starter 1.8.1.1.1.1.1.1.1 Table 5. Mounting dimensions for Benshaw starter Frame Weight Size in (mm) in (mm) in (mm) in (mm) in (mm) in (mm) in (mm) in (mm) in (mm) lbs (kg)
NO LONGER AVAILABLE. See Table 9 starter panel to the compressor motor terminals can be information on MX-to-MX2 logic module conversion. obtained locally or ordered from Trane Service Parts. Table 9. Service components Two wiring kits are necessary for each unit.
Page 48
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.