USER MANUAL
OLC/OLCT100
GAS DETECTOR
NPO100GB-Rev.M.1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OLC and is the answer not in the manual?

Questions and answers

Summary of Contents for TELEDYNE OLDHAM SIMTRONICS OLC

  • Page 1 USER MANUAL OLC/OLCT100 GAS DETECTOR NPO100GB-Rev.M.1...
  • Page 2 User Manuals in other languages are available on Website https://teledynegasandflamedetection.com Copyright  March 2021 by TELEDYNE OLDHAM SIMTRONICS S.A.S. All rights reserved. No reproduction of all or part of this document, in any form, is permitted without the written consent of TELEDYNE OLDHAM SIMTRONICS S.A.S.
  • Page 3 TELEDYNE OLDHAM SIMTRONICS does not support or authorise any business, person, or legal entity in assuming responsibility on behalf of TELEDYNE OLDHAM SIMTRONICS, even though they may be involved in the sale of TELEDYNE OLDHAM SIMTRONICS products.
  • Page 4 • Halogenated compounds (r134a, hfo, etc.) • Organo-phosphorus compounds (e.g. Herbicides, insecticides, and phosphate esters in fireproof hydraulic fluids TELEDYNE OLDHAM SIMTRONICS recommends regular testing of fixed gas detection installations (read Chapter 5). Guarantee Under normal conditions of use and on return to the factory, parts and workmanship are guaranteed for 3 years, excluding such consumables as sensors, filters, etc.
  • Page 5: Table Of Contents

    Composition of the detector ................ 1 Internal elements ....................2 Identifiers ....................... 3 Ranges ....................5 OLC 100 and OLCT 100 ranges ..............5 Installation ..................6 Regulations and conditions of use ............. 6 Necessary equipment ..................6 Electrical power supply ................... 7 Location of the detector ................
  • Page 6 OLC/OLCT100 GAS DETECTOR USER MANUAL Opening the cover ................... 23 Checking the current generator ..............24 Possible errors ...................... 25 Replacing sensor block ................... 26 Accessories ..................29 Cable gland ......................32 Spare parts ..................33 Declarations of EU conformity ............. 35 10 Technical specifications ...............
  • Page 7: Presentation

    • Either conducted directly via a connecting cable to a dedicated central measurement unit (as with the OLC 100 explosimeter) that operates on the principle of the Wheatstone bridge. Such a measurement unit is available in the TELEDYNE OLDHAM SIMTRONICS range.
  • Page 8: Internal Elements

    Sensor block connector. Calibration ribbon connector. 4 mA adjustment. Push button access for 4 mA adjustment. Zeroing. Sensitivity adjustment. OLC 100 detector OLCT 100 explosimeter OLCT 100 detector for toxic gases Figure 2 : internal view of the detectors NPO100GB Revision M.1...
  • Page 9: Identifiers

    Manufacturer's name Name of product ATEX Marking CE symbol and the number of the organisation that provided the TELEDYNE OLDHAM SIMTRONICS production quality certification (INERIS ) Figure 3 : Firmplate (example) Warning Type of gas detected and range of measurement...
  • Page 10 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Revision M.1...
  • Page 11: Ranges

    Ranges OLC 100 and OLCT 100 ranges The OLC 100 range is reserved for the detection of explosive vapor by using a Wheatstone bridge sensor. The OLCT 100 range of detectors is provided with an amplifier producing a 2 or 3 wire 4-20 mA analog output.
  • Page 12: Installation

    OLC/OLCT100 GAS DETECTOR USER MANUAL Installation It is recommended that the guides relating to the installation, use, and maintenance of flammable gas and oxygen detectors (standard EN/IEC 60079-29-2) and toxic gas detectors (standard EN 45544-4) should be clearly understood. Installation shall be in accordance with the standards in force, classification of the zone, and in conformity with standards EN/IEC 60079-14 and EN/IEC 61241-14, the editions in force, or with other national and/or local standards.
  • Page 13: Electrical Power Supply

    OLCT 100 IS EC 11 to 32 23,5 OLCT 100 XP SC 15,5 to 32 1550 By TELEDYNE OLDHAM OLC 100 (VQ1) SIMTRONICS controller By TELEDYNE OLDHAM OLC 100 (4F) SIMTRONICS controller (1) Depends on the gas controller Location of the detector...
  • Page 14: Connector Cable

    OLC/OLCT100 GAS DETECTOR USER MANUAL Installation of the enclosure shall be secured with 4 x M6 screws and the appropriate plugs for the supporting material Figure 6 : fixing template for the enclosure A special holder is available for mounting the detector on the ceiling (see section on accessories.
  • Page 15 OLC/OLCT100 GAS DETECTOR USER MANUAL Type of detector Type of sensor Maximum length (km) for cable Maximum load of cross-section as indicated resistance for 4- 20 Ma 0,5 mm² 0,9 mm² 1,5 mm² Upstream line voltage (Vcc) OLCT 100 XP...
  • Page 16: Cable Connection

    OLC/OLCT100 GAS DETECTOR USER MANUAL Cable connection 3.7.1 Switch off line power supply On the controller: 1. Inhibit any installation alarms to avoid unexpected triggering during operation. 2. In accordance with the manufacturer’s instructions, switch off the power to the module in order to be connected to the detector.
  • Page 17 OLC/OLCT100 GAS DETECTOR USER MANUAL 4 - Insert the part back into the OLC/OLCT100 then mount the cable gland (not supplied). Ca b le c o n n e c tio n 3.7.4 The connection of the cable between the detector and controller should be made with the power off.
  • Page 18 OLC/OLCT100 GAS DETECTOR USER MANUAL Figure 11: connection for a 3-wire OLC 100 type detector 3.7.5 Connecting the enclosure to ground Connect the enclosure ground terminal to earth according to the regulations. This ground connection may, however, be taken from the terminal on the screw fixing the PCB to the inside of the housing.
  • Page 19: Calibration

    OLC/OLCT100 GAS DETECTOR USER MANUAL Calibration The tasks described in this chapter are reserved for authorised trained personnel only, since these tasks are liable to affect detection reliability This procedure describes: • Zero adjustment; • Sensitivity adjustment. Necessary equipment • Multimeter (ranges 0-30 mA and 0-2 V), intrinsically safe if necessary.
  • Page 20: Stabilization Time

    30 by using the recommended gas and corresponding coefficient. 4.4.1 Zeroing Proceed as follows : Figure 13 : Zeroing (OLC 100) NPO100GB Revision M.1...
  • Page 21: Calibrating The Olct 100

    OLC/OLCT100 GAS DETECTOR USER MANUAL 1. Inhibit any alarm signals on the controller. 2.Place the calibration cup onto the detector head ( Figure 13, "A"). 3. Connect the calibrator cup to the pure air cylinder "D" using a flexible hose "B".
  • Page 22 OLC/OLCT100 GAS DETECTOR USER MANUAL 4.5.1 Zeroing (OLCT 100) Proceed as follows: Figure 14: Zeroing and Sensitivity adjustment (OLCT 100) Inhibit any alarm signals on the controller. 2. Insert the blue and green plugs on the measurement lead into the + and - multimeter sockets, respectively (Figure 14, "H")
  • Page 23 OLC/OLCT100 GAS DETECTOR USER MANUAL 4.5.2 Sensitivity adjustment (OLCT 100) This procedure enables the measurement to be adjusted corresponding to x% gas. Proceed as follows 1. Inhibit any alarm signals on the controller. 2. Insert the blue and green plugs on the measurement lead into the + and - multimeter sockets, respectively (Figure 14Figure 14: Zeroing and Sensitivity adjustment (OLCT 100), "H").
  • Page 24 OLC/OLCT100 GAS DETECTOR USER MANUAL Calibration coefficients of explosive gases for catalytic detectors When a VQ1 type sensor is used (available for OLC 100 and OLCT 100), the coefficients are as follows: Chemical Flash Vapor Coefficient- Coefficient- Coefficient - Coefficient -...
  • Page 25 OLC/OLCT100 GAS DETECTOR USER MANUAL Chemical Flash Vapor Coefficient- Coefficient- Coefficient - Coefficient - Formula point density Calibration gas Calibration gas Calibration gas Calibration (°C) CH4 (methane) C4H10 (Hydrogen) (Butane) C5H12 (Pentane) Isopropanol C3H8O 2.15 13.50 11.7 1.60 0.85 0.80 Kerosene C10 - C16 0.70...
  • Page 26 OLC/OLCT100 GAS DETECTOR USER MANUAL When an anti-poison 4F type sensor is used (only available for OLCT 100), the coefficients are as follows: Chemical LEL % Vapor Coef Coef Coef Formula density Acetone 2.15 13.0 2.24 1.03 Acetylene 1.91 Ammoniac 15.0...
  • Page 27: Preventive Maintenance

    IEC 60079-17, with whatever editions are in force or with other national standards. Frequency of maintenance Gas detectors are safety devices. TELEDYNE OLDHAM SIMTRONICS recommends the regular testing of fixed gas detection installations. This type of test consists of injecting the calibration gas into the detector at a sufficient concentration to activate the pre-set alarms.
  • Page 28: Actions

    OLC/OLCT100 GAS DETECTOR USER MANUAL Actions Periodic maintenance comprises the following actions: • Removal of dust from the sensor’s protective housing, using only a dry cloth. No water or solvents should be used. Severely dusty heads or sensors should be replaced immediately.
  • Page 29: Maintenance

    The 4 mA level is factory-set. This value cannot be changed or adjusted. This check does not concern explosimeter OLC 100. Opening the cover This stage is necessary for the 4 mA check, zeroing, and calibration of the detector. Unscrew the lid of the enclosure by using a tool positioned like a cross.
  • Page 30: Checking The Current Generator

    OLC/OLCT100 GAS DETECTOR USER MANUAL Checking the current generator Although this setting is made in the factory, it is possible that the transmitter and controller may have to be matched. In this case, proceed as follows Figure 15: checking the current generator 1.
  • Page 31: Possible Errors

    OLC/OLCT100 GAS DETECTOR USER MANUAL Possible errors The table below summarizes the various possible detector errors: OLC 100 explosimeter Observed fault Possible cause Action Zero setting not possible Sensor Replace the sensor Cable Check cable Main unit detector module Check module...
  • Page 32: Replacing Sensor Block

    OLC/OLCT100 GAS DETECTOR USER MANUAL Replacing sensor block 6.4.1 Standard Version Opening the cover First follow the instructions in the section The sensor block encloses the actual detector sensor itself. A sensor block can only be associated with a defined detector. A guide pin ensures that the sensor...
  • Page 33 OLC/OLCT100 GAS DETECTOR USER MANUAL Figure 17 : OLCT 100 HT – elements specific to changing the high temperature sensor • Screw the detector head back on again and tighten the locking screws. • Re-establish the supply to the detector from the controller.
  • Page 34 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Revision M.1...
  • Page 35: Accessories

    OLC/OLCT100 GAS DETECTOR USER MANUAL Accessories Accessory Utilization Illustration Reference Tools kit Tool kit for OLCT 100 including 6147879 calibration cup, Allen key, sensor removal key and connector cable humidifier kit Used for the calibration of the semi- 6335918 conductor transmitters...
  • Page 36 OLC/OLCT100 GAS DETECTOR USER MANUAL Accessory Utilization Illustration Reference Remote Enables the detection of ambient 6327911 calibration gases simultaneously with Plastic material. calibration gas injection pipe. Risk Effect on measurement: no effect. electrostatic charges. Wipe Effect on response time: negligible.
  • Page 37 OLC/OLCT100 GAS DETECTOR USER MANUAL Accessory Utilization Illustration Reference Ceiling Allows the sensor to detect more 6331168 collector quickly the gas. (Ceiling) Effect on measurement: no effect. Effect on response time: response time can increase up to 10%. Replacement Enables replacement of an existing...
  • Page 38: Cable Gland

    OLC/OLCT100 GAS DETECTOR USER MANUAL Cable gland Purpose Reference M20 cable gland for non-armoured cable 6343493 Material: stainless steel M20 cable gland for non-armoured cable 6343499 Material: Nickel-plated brass (not recommended for use with ammonia or acetylene) M20 cable gland for armoured cable...
  • Page 39: Spare Parts

    Spare parts List of spares for the various detectors Part Number Description Catalytic sensor 0-100% LEL VQ1 for OLC 100 and OLCT 100 (Standard 6 314 010 version only) Catalytic sensor 0-100% LEL 4F for OLCT 100 (poison resistant version only.
  • Page 40 Semiconductor sensor for ethanol, toluene, isopropanol, 2-butanone and 6 314 039 xylene for OLCT 100 6 451 626 OLC 100 Board 6 451 646 OLCT 100 IR Board (CO 6 451 700 OLCT 100 IR Board (R1234yf, R134a, R407f and SF6)
  • Page 41: Declarations Of Eu Conformity

    OLC/OLCT100 GAS DETECTOR USER MANUAL Declarations of EU conformity The document hereafter (2 pages) reproduces the EU declaration of conformity. NPO100GB Revision M.1...
  • Page 42 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Revision M.1...
  • Page 43 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Revision M.1...
  • Page 44 OLC/OLCT100 GAS DETECTOR USER MANUAL The document below (1 page) reproduces the 2014/90/UE Marine Directive declaration of conformity. NPO100GB Revision M.1...
  • Page 45 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Revision M.1...
  • Page 46 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Revision M.1...
  • Page 47: Technical Specifications

    OLC/OLCT100 GAS DETECTOR USER MANUAL Technical specifications 10.1 Dimensional characteristics Figure 18: dimensional characteristics of the detectors NPO100GB Revision M.1...
  • Page 48: General Specifications

    OLC/OLCT100 GAS DETECTOR USER MANUAL 10.2 General Specifications • OLC 100 : 340 mA (current supply) Supply voltage detector terminals (Vdc) : • OLCT 100 XP HT : 15.5 V to 32 V • OLCT 100 XP LEL : 15.5 V to 32 V •...
  • Page 49: Catalytic Sensor (Olct 100 Xp)

    Performance approved according to EN 60079-29-1:16 (VQ1 catalytic bead) Performance approved according to EN 50104:10 (oxygen detectors) • OLC 100 : 0.950 kg Weight : • OLCT 100 XP HT : 1.8 kg • OLCT 100 XP LEL : 1.0 kg •...
  • Page 50: Toxic Sensors (Olct 100 Xp And Olct 100 Is)

    -40 to +70°C (sensor with identifying OLCT 100 : 2% of the measurement between 71 and mark) 100% LEL OLC 100 : 5% of the measurement between 71 and 100 % LEL sensor, high 1% LEL between 0-70%LEL -20 to +200°C...
  • Page 51 OLC/OLCT100 GAS DETECTOR USER MANUAL Type of gas Measureme XP Version IS Version Temperature % RH Accuracy Lyfe Reponse Storage Warm-up nt range range °C (ppm) (months) time conditions time max (h) (at 20°C) (ppm) Arsine 1.00 ● -20 to +40 20 - 90 +/- 0.05...
  • Page 52 OLC/OLCT100 GAS DETECTOR USER MANUAL Type of gas Measureme XP Version IS Version Temperature % RH Accuracy Lyfe Reponse Storage Warm-up nt range range °C (ppm) (months) time conditions time max (h) (at 20°C) (ppm) +/- 0,5% vol. from 0 to +50°C...
  • Page 53: Semiconductor Sensors (Olct 100 Xp)

    OLC/OLCT100 GAS DETECTOR USER MANUAL 10.5 Semiconductor sensors (OLCT 100 XP) Common characteristics Measurement principle : semiconductor Temperature range : -20°C to +55°C Relative humidity : 20 to 95% RH (non-condensing relative humidity) Pressure : atmospheric ± 10% Lifetime (typical) :...
  • Page 54: Infrared Sensors (Olct 100 Xp-Ir)

    OLC/OLCT100 GAS DETECTOR USER MANUAL Type of gas Measurement range Accuracy 2-butanone ( MEK) 500 ppm Xylene 500 ppm R1234yf 1000ppm R1234ze 1000ppm 10.6 Infrared sensors (OLCT 100 XP-IR) Measurement range : 0-100% LEL R1234yf 0-2000 ppm R1234yf, R134a, R407f, SF R32, R1234ze 0 –...
  • Page 55 OLC/OLCT100 GAS DETECTOR USER MANUAL Type of gas Measureme XP Version Temperature % RH Accuracy Lyfe Reponse time Storage Warm-up nt range range °C (ppm) (months) conditions time max (h) (ppm) 5,000 ● +/- 150 ● +/- 0.15% carbon dioxide...
  • Page 56 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Rev.M.0...
  • Page 57: Specific Instructions For Use In Explosive Atmospheres And Operational Safety

    Dust and Gas atmospheres. On account of their metrological performance as tested by the accredited organization INERIS (in process), the OLC/OLCT 100 transmitter detectors intended for the measurement of explosive gases are classed as safety devices in the sense of the European Directive and may, therefore, contribute to limiting the risks of explosion.
  • Page 58: Threaded Joints

    60079-1. TELEDYNE OLDHAM SIMTRONICS does not allow repairs and disclaims any responsibility for material modifications. The threaded joints on the OLC(T) 100 may be lubricated to maintain fire-proof protection. Only non-hardening lubricants or non-corrosive agents having no volatile solvents may be used.
  • Page 59: Scope Of Use

    The detector has been developed in conformity with standard EN/CEI 61508. The safety function of the OLC/OLCT 100 detector is the detection of flammable gases using catalytic technology and a 4-20 mA current output proportional to the gas concentration expressed as a percentage of LEL, respectively from 0 to 100% LEL.
  • Page 60: Reliability Data

    OLC/OLCT100 GAS DETECTOR USER MANUAL The safety function is no longer valid: • After power has been switched on, while the measurement sensor is stabilizing and during start-up tests, the output current shall be in maintenance mode (2 mA). • When the push button is pressed (forcing the current to 4 mA), the output current will be frozen at 4 mA.
  • Page 61: Appendix | Ordering Information

    GAS DETECTOR USER MANUAL Appendix | Ordering information 12.1 Gas List Please find below the list of gases that the OLC/OLCT 100 detector can detect. Gas Code Methane 0-100 % LEL Methane 0-100% LEL (4.4% vol) Hydrogen 0-100% LEL Butane 0-100% LEL...
  • Page 62 OLC/OLCT100 GAS DETECTOR USER MANUAL Gas Code Hexane 0-100% LEL Isobutane 0-100% LEL Isobutene 0-100% LEL Isopropanol 0-100% LEL Kerosene (JP4) 0-100% LEL Methyl Methacrylate 0-100% LEL Methanol 0-100% LEL Methylamine 0-100% LEL Naphta 0-100% LEL Naphtalene 0-100% LEL Nonane 0-100% LEL...
  • Page 63 OLC/OLCT100 GAS DETECTOR USER MANUAL Gas Code , 0-10 ppm , 0-30 ppm , 0-10 ppm , 0-30 ppm , 0-100 ppm , 0-10 ppm , 0-20 ppm , 0-2,000 ppm , 0-4% volume HCl, 0-30 ppm HCl, 0-100 ppm...
  • Page 64 OLC/OLCT100 GAS DETECTOR USER MANUAL Gas Code Chloromethane (Methylchloride), 0-500 ppm R123, 0-2,000 ppm FX56, 0-2,000 ppm R143a, 0-2,000 ppm R404a, 0-2,000 ppm R507, 0-2,000 ppm R410a, 0-1,000 ppm R32, 0-1,000 ppm R407c, 0-1,000 ppm R408a, 0-4,000 ppm R407f, 0-1,000ppm...
  • Page 65 OLC/OLCT100 GAS DETECTOR USER MANUAL To know you part number, please follow these instructions: NPO100GB Revision M.1...
  • Page 66 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Rev.M.0...
  • Page 67 OLC/OLCT100 GAS DETECTOR USER MANUAL NPO100GB Rev.M.0...
  • Page 68 Z.I. Est – CS 20417 Ruiping Road, Xuhui District TX 77429, 62027 ARRAS Cedex, SHANGHAI FRANCE CHINA Tel.: +1-713-559-9200 Tel.: +33 (0)3 21 60 80 80 Tel.: +86-134-8229-5057 www.teledynegasandflamedetection.com © 2021 TELEDYNE OLDHAM SIMTRONICS. All right reserved. NPO100GB Revision M.1 / March 2021...

This manual is also suitable for:

Olct 100Olct 100 xpOlct 100 xpirOlct 100 isOlct 100 htOlct 100 xp ht ... Show all