SK 54xE – Users Manual for Frequency Inverters
SK 540E
Relevance
Terminals X5:
21
DIN1
Designation
Terminal Function
[factory setting]
21
Digital input 1
[ON right] 7.5...30V, R
22
Digital input 2
[ON left]
23
Digital input 3
[parameter set bit0]
24
Digital input 4
[Fixed frequency 1,
P429]
25
Digital input 5
[no function]
39
Thermistor input -
38
Thermistor input +
41
5V supply voltage
output
44
Size 1 to Size 4
VI 24V supply
voltage input
Size 5 and above
VO 24V supply
voltage output
40
Reference potential
for digital signals
Pos: 84 /Anleitungen/Elektronik/FU und Starter/2. Montage und Installation/Elektrischer Anschluss/SK 500E/2.10.5 Elektrischer Anschluss Steuerteil- Klemmenblock X6 – Encoder [SK 54xE] @ 2\mod_1355475336807_388.docx @ 52162 @ 5 @ 1
64
SK 545E
SK 510E
SK 511E
22
23
24
DIN2
DIN3
DIN4
Data
=6.1kΩ
i
Not suitable for thermistor
evaluation.
HTL encoders can only be
connected to DIN2 and
DIN4
Limiting frequency:
max.
10 kHz
available: above size 5
available: Size 1 - 4
Potential isolated
thermistor input, which
cannot be disabled, for
monitoring the motor
temperature with a PTC
available: size 5 and above
5V ± 10%
max. 250 mA (output) not
short-circuit resistant
18...30V
min. 800mA (input)
24V ± 25%
max. 200 mA (output)
short circuit resistant
0V digital
SK 515E
SK 520E
SK 530E
25 / 39
41 / 38
DIN5 / TF-
VO 5V / TF+
Description / wiring suggestion
Each digital input has a reaction time of
≤ 5ms.
Size 1 to 4:
21
22
23
24
39
motor - PTC
38
44
40
Above size 5:
21
22
23
24
25
41
44
40
Voltage supply for the FI control unit. Is
essential for the function of the
frequency inverter.
Supply voltage provided by the
frequency inverter for connection to the
digital inputs or for the supply of a 10-
30V encoder.
The 24V control voltage is generated by
the FI, however it can also be supplied
via the terminals X12:44/40 (Size 8 and
above: X15:44/40). Supply via terminal
X5:44 is not possible.
Reference potential
SK 535E
* Terminal 44:
44*
40
up to Size 4: VI
V...24V
GND/0V
Size 5 and
above: VO
Parameter
P420 [-01]
P420 [-02]
P420 [-03]
18 ... 30V
P420 [-04]
GND / 0V
P420 [-05]
18 ... 30V
GND / 0V
BU 0505 EN-3021

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NORDAC PRO SK 500E Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Nordac pro sk 50 e seriesNordac pro sk 51 e seriesNordac pro sk 511e seriesNordac pro sk 520e seriesNordac pro sk 53 e seriesNordac pro sk 54 e series ... Show all

Table of Contents

Save PDF