Special Application - Siemens OpenAir GCA Series Technical Instructions

Electronic damper actuators
Hide thumbs Also See for OpenAir GCA Series:
Table of Contents

Advertisement

OpenAir™ GCA Series Spring Return 160 lb-in Electric Damper Actuators
4.
Start-Up
Commissioning
GCA15x
GCA16x
(Continued)
5. Check the Auxiliary Switch B:
Special
Modulating 4 to 20 mA control with GCA15x
Application
and an external 499-ohm resistor (985-124,
See Accessories).
NOTE:
Service
Siemens Industry, Inc.
Check the Auxiliary Switch A:
a.
Set the DMM dial to ohms (resistance) or continuity check.
b.
Connect wires S1 and S3 to the DMM. The DMM should indicate open circuit or no resistance.
c.
Apply the input signal as in Step 1d, to wire 8 (gray).
The DMM should indicate contact closure as the actuator shaft coupling reaches the setting of
switch A.
d.
Connect wires S1 and S2 to the DMM. The DMM should indicate open circuit or no resistance.
e.
Apply the input signal as in Step 1f, to wire 8 (gray).
The DMM should indicate contact closure as the actuator shaft coupling reaches the setting of
switch A.
a. Set the DMM dial to ohms (resistance) or continuity check.
b. Connect wires S4 and S6 to the DMM. The DMM should indicate open circuit or no
resistance.
c. Apply the input signal as in Step 1d, to wire 8 (gray).
The DMM should indicate contact closure as the actuator shaft coupling reaches the
setting of switch B.
d. Connect wires S4 and S5 to the DMM. The DMM should indicate open circuit or no
resistance.
e. Apply the input signal as in Step 1f, to wire 8 (gray).
The DMM should indicate contact closure as the actuator shaft coupling reaches the
setting of switch B.
985-124 is provided with the GCA15x
actuator.
WARNING:
Do not open the actuator. If the actuator is inoperative, replace the unit.
Technical Instructions
Document Number 155-173P25
Figure 28.
Wiring Diagram for Converting
4 to 20 mA into 2 to 10 Vdc.
May 19, 2014
Page 21