. Multiple outdoor units control
Hydrobox
CNP1(WHT)
1
3
TBO.1
1
CNV1
(WHT)
10
5
11
12
13
14
FT C 4
TBO.2
LED3
10
11
12
13
14
1
CNPWM
1
CNBH
CNIH
(WHT)
(WHT)
LED2
 (ORN)
3
7
3
1
CN22
1
CNBC
CNBHT
(BLU)
2
 (GLY)
 (BLK)
3
1
3
1
CN21
CN2F
CNW12
CNW5
CN20
(YLW)
(YLW)
(RED)
(WHT)
(RED)
1
1
1
1
1
2
3
2
3
4
10
12 14
10
12 14
11 13
11 13
TBI.1
TBI.2
<Fig. ..5>
Signal inputs
Name Terminal block Connector
RC
TBI.2 13-14
CN22
IN2
TBI.1 3-4
CN2F
Wiring specification and field supply parts
Model and specifications
Item
Name
Signal input
Signal input
Use sheathed vinyl coated cord or cable.
function
wire
Max. 10 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Switch
Non-voltage "a" contact signals
Remote switch: minimum applicable load 12V DC, 1mA
Thermistor inputs
Name
Terminal block Connector
TH2
CN21
THW1
CNW12 1-2 Thermistor (Flow water temp.)
THW2
CNW12 3-4 Thermistor (Return water temp.)
Note:
Do not splice the wiring to extend or shorten it, or this could affect correct monitoring of each temperature.
If the wiring is too long, bundle it with a strap to adjust the length.
Outputs
Name
Terminal block Connector Item
OUT1
TBO.1 3-4
CNP1
OUT4
TBO.1 9-11
CNV1
OUT13 TBO.2 7-8
N L
N
L
1 2
3 4 5
6 7 8
9 10 11
TBO.1
OUT1
OUT4
Wiring specification and field supply parts
Model and specifications
Item
Name
External
Outputs
Use sheathed vinyl coated cord or cable.
output
wire
Max. 30 m
function
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Solid wire: ø0.65 mm to ø1.2 mm
Note: Do not connect multiple water circulation pumps directly to each output (OUT1). In such a case, connect them via (a) relay(s).
CN01
5
(BLK)
1
CN3C
1
(BLU)
3
1
CN105
(RED)
5
1
CNRF
(WHT)
5
LED4
CN108
SW4
LED1
1
6
SW2
SW1
8
8
1
1
SW3
8
1
Item
Communication cable between indoor units
Flow switch input
Solid wire: ø0.65 mm to ø1.2 mm
Item
Thermistor (Ref. liquid temp.)
Water circulation pump 1 output
3-way valve (2-way valve 1) output
2-way valve 2 output
12 13 14
1 2
3 4 5
TBO.2
<Fig. ..2>
OFF (Open)
OFF (Short)
Refer to SW2-2 in <9.6 Dip Switch Functions>.
Optional part model
OFF
ON
OFF
ON
Heating
DHW
DHW
Heating
N L
6 7 8
9 10 11
12 13 14
OUT13
Signal/Max current
230V AC 1.0 A Max
230V AC 0.1 A Max
230V AC 0.1 A Max