Installation Location - Panasonic PAW-280PAH3M Basic Installation Instructions

Air handling unit kit
Hide thumbs Also See for PAW-280PAH3M:
Table of Contents

Advertisement

• Install this Air Handling Unit Kit vertically.
• When attaching this Air Handling Unit Kit, be sure to fix it in a proper way and
confirm that Air Handling Unit is fixed.
• The warranty does not cover the product if it falls from an elevated location.
• For the set up and commissioning please check the remote controller manual

2. Installation location

Install at the height of 100 mm or more (Due to space of wiring)
Keep a space around the Air Handling Unit Kit as detailed on the figure shown above.
Avoid the following locations for installation.
o In direct sunlight
o Location where vibrations can occur
o Location where too much dust or water occurs (The AHU-Kit Protection Code is
IP65)
o Location where condensation occurs
o Location near heat sources
Keep a distance of 1 m or more from TVs, radios, and PCs. (Image blur or related noise may
occur)
In the case of high humidity there is the possibility of condensation water inside the Air
Handling Unit Kit occurring, in this case retrofit the AHU-Kit with pressure equalization
(This measure is to be created on site if required)
Do not use in special environments.
Use in places with much oil (including machine oil), steam, flammable or corrosive gas,
voltage fluctuation, surrounding the metal body, may lead to severe decrease in
functionality and damage to parts.