Diagnostics via AS-i
Sorted device diagnosis, output circuit 2
If answer to data call (1) = 101X:
Data call / Value
(8) / 0111
Number of devices
not green, output
circuit 2
Data call / Value
(9) / 0110
Device address
HIGH, output
circuit 2
Data call / Value
(A) / 0101
Device address
LOW, output circuit 2
Data call / Value
(B) / 0100
Colour of device,
output circuit 2
Notice!
Data calls (C) 0011 to (F) 0000 are reserved.
80
Answer
Meaning
D3 ... D0
0XXX
XXX = 0:
XXX = 1 ... 6:
XXX = 7:
Answer
Meaning
D3 ... D0
1HHH
HHH = I5,I4,I3: diagnosis index of device in output circuit 2 of
Answer
Meaning
D3 ... D0
0LLL
LLL = I2,I1,I0:
Answer
Meaning
D3 ... D0
1CCC
CCC = colour (see table 13.1 on page 77)
Operating manual for the AS-i safety monitor V 3.08 M
no devices, answers to data calls (5) ... (7)
not relevant
number of devices in output circuit 2
number of devices is > 6 in output circuit 2
configuration
(HHHLLL = diagnosis index)
diagnosis index of device in output circuit 2 of
configuration
(HHHLLL = diagnosis index)