Operation Options; Structure And Function Of The Operating Menu; Commissioning - Endress+Hauser Nivector FTI26 Brief Operating Instructions

Capacitance point level switch for powdered and fine-grained solids
Hide thumbs Also See for Nivector FTI26:
Table of Contents

Advertisement

Nivector FTI26
7

Operation options

7.1

Structure and function of the operating menu

7.1.1
IO-Link
IO-Link information
IO-Link is a point-to-point connection for communication between the device and an IO-Link
master. The device features an IO-Link communication interface type 2 with a second IO
function on pin 4. This requires an IO-Link-compatible assembly (IO-Link master) for
operation. The IO-Link communication interface enables direct access to the process and
diagnostic data. It also provides the option of configuring the device while in operation.
Physical layer, the devices supports the following features:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• SIO mode: yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 6 msec.
• Process data width: 16 bit
• IO-Link data storage: yes
• Block configuration: no
IO-Link download
http://www.endress.com/download
• Select "Software" as the media type.
• Select "Device Driver" as the software type.
Select IO-Link (IODD).
• In the "Text Search" field enter the device name.
https://ioddfinder.io-link.com/
Search by
• Manufacturer
• Article number
• Product type
7.1.2
Structure of the operating menu
The menu structure has been implemented according to VDMA 24574-1 and complemented
by Endress+Hauser-specific menu items.
8

Commissioning

If an existing configuration is changed, measuring operation continues! The new or modified
entries are only accepted once the setting has been made.
Endress+Hauser
Operation options
19