CAUTION:
THE
EQUIPMENT
THESE INSTRUCTIONS SHOULD BE INSTALLED
AND SERVICED ONLY BY COMPETENT
SONNEL FAMILIAR WITH GOOD SAFETY PRAC ­
TICES.
THIS INSTRUCTION IS
SUCH PERSONNEL AND IS NOT INTENDED AS A
SUBSTITUTE FOR
ADEQUATE
EXPERIENCE IN SAFE PROCEDURES FOR THIS
TYPE OF EQUIPMENT.
GENERAL
The nameplate rating should be checked to ascer­
tain that the maximum circuit line-to-ground volt­
age under any condition of operation, including fault
conditions, will not exceed the voltage rating of the
arrester.
Application of higher-than-rated power
voltages may result in the failure of the arrester.
EffiCient operation of the lightning arrester re­
quires a permanent low-resistance ground
best protection is obtained by connecting the arrester
directly across the line and ground terminals of the
apparatus being protected, using a common ground
connection for both apparatus and arrester.
is not physically possible, the arrester should be so
connected that its grounding resistance does not ex­
ceed five ohms.
INSTALLATION
CAUTION:
CARE SHOULD B E
IN
HANDLING
ARRESTERS
BRE A K AGE .
The arrester preferably should be mounted ver­
tically and installed as close as possible to the ap­
paratus being protected.
tions should be short and direct.
terminal nuts or bolts should be tightened firmly on
their respective leads, but with no more than 15
lb-ft torque.
The arrester should be clamped securely in its
hanger and in a location where it will not be sub­
jected to sustained vibration.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to
installation, operation or maintenance. Should further information
purchaser's purposes, the matter should
INSTRUCTIONS
DISTRIBUTION SURGE ARRESTERS
COVERED
BY
PER­
WRITTEN FOR
TRAINING AND
The
If this
TAKEN
TO
AVOID
Line and ground connec­
Line and ground
be
desired or should particular problems arise which are not covered sufficiently far
be
referred to the General Electric Company.
Fig. 1.
Distribution arrester
Fig. 2. Distribution arrester, externally gapped.
Arresters may also be mounted horizontally.
However, a slight inclination with the line end ele­
vated may be desirable.
NOTE: Precautions to be taken in instal ­
ling direct-connected arresters are shown
in Fig. 3.
GEH-29068
Supersedes GfH-29NA
and GfH-2903A
with
disconnector.
be met
in connection with
the

Advertisement

loading

Summary of Contents for GE GEH-2906B

  • Page 1 GEH-29068 INSTRUCTIONS Supersedes GfH-29NA and GfH-2903A DISTRIBUTION SURGE ARRESTERS CAUTION: EQUIPMENT COVERED THESE INSTRUCTIONS SHOULD BE INSTALLED AND SERVICED ONLY BY COMPETENT PER­ SONNEL FAMILIAR WITH GOOD SAFETY PRAC ­ TICES. THIS INSTRUCTION IS WRITTEN FOR SUCH PERSONNEL AND IS NOT INTENDED AS A SUBSTITUTE FOR ADEQUATE TRAINING AND...