** The resistance value of R is selected to ensure that when the Variac is set to its
Maximum setting the value of current, as measured on meter A, is approx. 10% higher
than the maximum Full Stroke current. For the purposes of this test circuit the resistor
is fixed, however, it can be a potentiometer and set to a value that permits a 10%
higher than the maximum Full Stroke current value.
Table 3-1. Shop Test Operating Values @ 70-74°F
Vane Torque
(Inch Grains)
Volts
(for ref. only)
325
2.9 – 3.3
Table 3-1 values represent nominal calibration values ± 5%. See Table 3-3 for
Note:
In-Service and Field Calibration Operating Values.
The digital ammeter should be set to display to only three decimal places. Values beyond
∗
three decimal place accuracy are insignificant to the calibration and should be ignored.
When the track energy is reduced to 1.7 volts or .028 amp, the vane must have touched
the lower roller stop. The values in
3-1
Table
are 13% higher than ideal and apply to test from single-phase supply with
∗
resistance in series with the track winding.
It's recommended that relays be taken out of service if the Drop-Away falls below the value
shown for field test.
Shop Test operating values may be affected by fluctuations
of local voltage, temperature, and test equipment being
used.
Table 3-2. Operating Values at Ideal Phase Relations
(Values shown are for technical use and for calibration tag information only.
Pick-Up (PU)
Volts
2.60 – 2.88
Note: Table 3-1 values represent nominal calibration values ± 5%.
Copyright 2019
Figure 3-1. AC Vane Relay Test Circuit
Pick-Up (PU)
Amps*
0.048 – 0.053
Not to be used for normal calibration purposes.)
Amps*
Volts
0.042 – 0.046
2.9 – 3.20
SM 4574F, Rev. 4, March 2019
Full Stroke (FS)
Volts
(for ref. only)
3.3 – 3.6
0.053 – 0.059
NOTE
Full-Stroke (FS)
Amps*
0.047 – 0.052
PV-250 Track Relay
Drop Away
% of Actual PU
Amps*
Shop
85 to 95
Drop-Away
% of Actual PU
85 to 95
3-4