WARNING Daikin website (publicly accessible). Make sure installation, servicing, maintenance and repair ▪ The full set of latest technical data is available on the Daikin comply with instructions from Daikin and with applicable Business Portal (authentication required). legislation (for example national gas regulation) and are executed only by authorised persons.
User interface (front plate, rear plate, screws, and wall plugs) Discharge grille Screws for discharge grille 2 After opening the unit (see "4.3.1 To open the outdoor unit" [ 4 10]), remove the accessory inside the unit. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
Unit installation WARNING Make sure installation, servicing, maintenance and repair Preparing the installation site comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. 4.1.1 Installation site requirements of the...
If the unit CANNOT be installed fully level, always make sure that the inclination is towards the backside of the unit. This is required to guarantee proper drainage. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
89°C 60°C 4.3.2 To close the outdoor unit NOTICE Speed nut. Make sure the speed nut for the top screw is correctly attached to the service cover. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
5.1.2 Third-party tank requirements In case of a third-party tank, the tank shall adhere to the following requirements: ▪ The heat exchanger coil of the tank is ≥1.05 m². EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
–15°C NOTICE –20°C — If you add glycol to the water, you also need to install a –25°C — flow switch (EKFLSW1). –30°C — Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Maximum running current: 100 mA Grid" [ 4 25]. For the main zone: ▪ [2.9] Control ▪ [2.A] Thermostat type For the additional zone: ▪ [3.A] Thermostat type ▪ [3.9] (read-only) Control Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Page 15
[1.6] Room sensor offset The following illustration shows the location of the extra components that you need to install on the outdoor unit when using certain option kits. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
In case of normal kWh rate power supply Normal kWh rate Wires: 1N+GND, OR 3N+GND power supply Maximum running current: Refer to name plate on unit. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Page 17
X19A X11YB X11Y X11YA 1N~, 50 Hz, 230 V AC, 6.3 A X19A X11YA X11Y X11YB 6 Fix the cables with cable ties to the cable tie mountings. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
1 Connect the backup heater power supply. A 4‑pole fuse is used for F1B. 2 If required, modify the connection on terminal X14M. 3 Fix the cable with cable ties to the cable tie mountings. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Page 20
EKMBHBP1 is required if condensation is expected inside the backup heater. 1 Integrate components B and D as follows in the system: Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
▪ (if necessary) Opening the user interface after it is installed. ×2 Connecting the user interface cable to the outdoor unit Wires: 4×(0.75~1.25 mm²) Maximum length: 200 m Front plate EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
2 Connect the valve control cable to the appropriate terminals as ▪ The connector pins are automatically inserted correctly. shown in the illustration below. NOTICE Only connect NO (normally open) valves. X2M.3 X2M.4 (NO) Positioning pins Connector pins Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Wires connected to the alarm output Wire between X2M and A4P A4P Installation of EKRP1HBAA is required. A4P.Y1 3 Fix the cable with cable ties to the cable tie mountings. X2M.7 EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
Wire between X2M and A4P A4P.X2 A4P Installation of EKRP1HBAA is required. A4P.Y2 X2M.7 Installation of EKRP1HBAA is required. 3 Fix the cable with cable ties to the cable tie mountings. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
[9.8.8] Limit setting kw The wiring of the Smart Grid in case of low voltage contacts is as X5M.14 follows: X5M.13 S11S S10S EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
Page 26
Jumper (factory-mounted). If you also connect a safety thermostat (Q4L), replace the jumper with the safety thermostat wires. Smart Grid pulse meter 1 Install the components of the Smart Grid relay kit as follows: Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
You can change the user permission level as follows: refrigerant in the compressor. 3 Measure the insulation resistance again. Configuration INFORMATION Cooling is only applicable in case of reversible models. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
> Time/date) once the unit is initialised. field settings. 8.2.3 Configuration wizard: System Backup heater type ▪ For models with integrated backup heater, this is fixed to 3V. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Page 29
To manually recover it via the user interface, go to the Malfunctioning main menu screen and confirm whether the backup heater and/or booster heater can take over the heat load or not. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
During normal operation, the capacity of the second step of NOTICE the backup heater at nominal voltage is equal to If you add glycol to the water, you also need to install a [6‑03]+[6‑04]. flow switch (EKFLSW1). Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
Influence of the LWT setpoint mode [2.4] is as follows: ▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving water temperatures, either preset or custom. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
"8.3.4 Using weather-dependent 8.3.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) Example Weather-dependent curve when offset is selected: EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
The following table describes how to fine-tune the weather- [2.4] Main zone > Setpoint Weather dependent dependent curve of a zone or tank: mode Additional zone – Heating Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
▪ 2: 2 contacts 8.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
Averaging time [9.C] Bivalent Bivalent Boiler efficiency Temperature Hysteresis Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
There are NO loose connections or damaged electrical commissioning checklist is also available on the Daikin components in the switch box. Business Portal (authentication required). There are NO damaged components or squeezed The general commissioning checklist is complementary to pipes on the inside of the outdoor unit.
Purpose Perform an actuator test run to confirm the operation of the different actuators. For example, when you select Pump, a test run of the pump will start. Installation manual EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620239-1 – 2020.06...
▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...
11 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 11.1 Piping diagram: Outdoor unit...
Page 41
Air heat exchanger Distributor Air heat exchanger, middle Heat exchanger Service port 5/16" flare Refrigerant flow: Accumulator Heating Muffler Cooling Connections: Screw connection Flare connection Quick coupling Brazed connection EBLA09~16DA + EDLA09~16DA Installation manual Daikin Altherma 3 M 4P620239-1 – 2020.06...