SiUS071735EA 1. Safety Cautions................... v 1.1 Warnings and Cautions Regarding Safety of Workers......... v 1.2 Warnings and Cautions Regarding Safety of Users........vii 2. Icons Used ....................x Part 1 List of Functions ..............1 1. Functions..................... 2 Part 2 Specifications ............... 3 1.
Page 4
SiUS071735EA 2.11 Electronic Expansion Valve Control ............40 2.12 Malfunctions ....................43 Part 5 Remote Controller ............... 44 1. Wired Remote Controller (BRC1E73) ............45 2. Wireless Remote Controller (BRC082A43)..........51 Part 6 Service Diagnosis..............53 1. General Problem Symptoms and Check Items .........55 2.
Page 5
SiUS071735EA 4.28 Output Overcurrent Detection ..............98 5. Check ...................... 100 5.1 Thermistor Resistance Check ..............100 5.2 Indoor Fan Motor Connector Check ............101 5.3 Power Supply Waveforms Check ............. 101 5.4 Electronic Expansion Valve Check............102 5.5 Four Way Valve Performance Check ............103 5.6 Inverter Unit Refrigerant System Check...........
Safety Cautions SiUS071735EA 1. Safety Cautions Be sure to read the following safety cautions before conducting repair work. After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer. This manual is for the person in charge of maintenance and...
Page 7
SiUS071735EA Safety Cautions Warning Be sure to discharge the capacitor completely before conducting repair work. The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. A charged capacitor may cause an electrical shock. Do not turn the air conditioner on or off by plugging in or unplugging the power cable.
Safety Cautions SiUS071735EA Caution Be sure to conduct repair work with appropriate tools. The use of inappropriate tools may cause injury. Be sure to check that the refrigerating cycle section has cooled down enough before conducting repair work. Working on the unit when the refrigerating cycle section is hot may cause burns.
Page 9
SiUS071735EA Safety Cautions Warning Be sure to use the specified cable for wiring between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals. Improper connections may cause excessive heat generation or fire.
Page 10
Safety Cautions SiUS071735EA Caution Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks. Do not install the equipment in a place where there is a possibility of combustible gas leaks.
SiUS071735EA Icons Used 2. Icons Used The following icons are used to attract the attention of the reader to specific information. Icon Type of Description Information Warning A Warning is used when there is danger of personal injury. Warning Caution A Caution is used when there is danger that the reader, through incorrect manipulation, may damage equipment, lose data, get Caution...
Indoor Unit SiUS071735EA 1. Indoor Unit FDMQ09/12/15/18/24RVJU Control PCB X15A Connector for float switch (A1P) X16A Connector for room temperature thermistor (suction air thermistor) X17A, X18A Connector for indoor heat exchanger thermistor X25A Connector for drain pump motor X27A Connector for terminal block (for power supply) X28A Connector for power supply wiring (option) X30A...
Page 21
SiUS071735EA Indoor Unit Indoor Fan PCB Connector for control PCB (A1P) (A2P) Connector for reactor Connector for indoor fan motor X10A Connector for terminal block (for power supply) Fuse (5 A, 250 V) Fuse (6.3 A, 250 V) LED for service monitor (green) X10A 2P442228-16 2P442228-17...
Outdoor Unit SiUS071735EA 4. Outdoor Unit RX09/12RMVJU(9) Main PCB (PCB1) 1) S20 Connector for electronic expansion valve coil 2) S30 Connector for compressor 3) S40 Connector for overload protector 4) S71 Connector for DC fan motor 5) S80 Connector for four way valve coil 6) S90 Connector for thermistors (outdoor temperature, outdoor heat exchanger, discharge pipe)
SiUS071735EA Outdoor Unit RX15/24RMVJU(A), RX18RMVJU(9)(A) Main PCB 1) S20 Connector for electronic expansion valve coil 2) S40 Connector for overload protector 3) S70 Connector for DC fan motor 4) S80 Connector for four way valve coil 5) S90 Connector for thermistors (outdoor temperature, outdoor heat exchanger, discharge pipe) 6) HL1, HN1, S Connector for terminal block...
SiUS071735EA Part 4 Functions and Control 1. Main Functions..................16 1.1 Temperature Control .................. 16 1.2 Frequency Principle..................16 1.3 Fan Speed Control for Indoor Unit ............. 18 1.4 Program Dry Operation ................19 1.5 Clock and Calendar Setting (With Wired Remote Controller BRC1E73) ... 20 1.6 Schedule TIMER Operation (With Wired Remote Controller BRC1E73) ...
SiUS071735EA Main Functions 1. Main Functions Temperature Control Definitions of The definitions of temperatures are classified as following. Temperatures Room temperature: temperature of lower part of the room Set temperature: temperature set by remote controller Room thermistor temperature: temperature detected by room temperature thermistor Target temperature: temperature determined by microcomputer Target temperature Room thermistor temperature...
Page 28
Main Functions SiUS071735EA The following drawing shows a schematic view of the inverter principle: Refrigerant circulation rate (high) high speed Amount of heat Amount of heat exchanged air (large) exchanged air (large) high f low f Amount of heat Amount of heat exchanged air (small) exchanged air (small) low speed...
SiUS071735EA Main Functions Fan Speed Control for Indoor Unit With Wired Remote Controller (BRC1E73) To change the fan speed, press Fan Speed button and select the fan speed from Low/Medium/High/Auto. Auto cannot be selected if the indoor unit does not have Auto Fan speed function. The system may change the fan speed automatically for equipment protection purposes.
Main Functions SiUS071735EA Program Dry Operation Outline Program dry operation removes humidity while preventing the room temperature from lowering. Since the microcomputer controls both the temperature and airflow rate, the temperature adjustment and FAN setting buttons are inoperable. Details The microcomputer automatically sets the temperature and airflow rate. The difference between the room thermistor temperature at start-up and the target temperature is divided into two zones.
SiUS071735EA Main Functions Clock and Calendar Setting (With Wired Remote Controller BRC1E73) Press Menu/OK button to display the main menu screen. Press buttons to select Clock & Calendar on the main menu screen. Press Menu/OK button to display the clock & calendar screen. Press buttons to select Date &...
Page 32
Main Functions SiUS071735EA Select Hour with buttons. Change the hour with buttons. Holding down the button causes the number to change continuously. Select Minute with buttons. Change the minute with buttons. Holding down the button causes the number to change continuously. Press Menu/OK button.
SiUS071735EA Main Functions Schedule TIMER Operation (With Wired Remote Controller BRC1E73) Outline Day settings are selected from 4 patterns: 7 Days Weekday/Sat/Sun Weekday/Weekend Everyday Up to 5 actions can be set for each day. Details Set the startup time and operation stop time. Startup time, cooling and heating temperature setpoints can be configured.
Page 34
Main Functions SiUS071735EA Daily Patterns The schedule screen will appear. Press buttons to select Daily Patterns on the schedule screen. The daily patterns screen will appear when Menu/OK button is pressed. Press buttons to select 7 Days Weekday/Sat/Sun Weekday/Weekend Everyday the daily patterns screen.
Page 35
SiUS071735EA Main Functions Press buttons to move the highlighted item and press buttons to configure ON/OFF/-- settings. --, ON, or OFF changes in sequence when buttons are pressed. ON: The temperature setpoints can be configured. OFF: The setback temperature setpoints can be configured.
Main Functions SiUS071735EA Enabling or disabling the schedule Display the schedule screen. Press buttons to select Enable / Disable on the schedule screen. Press Menu/OK button to display the enable/disable screen. Press buttons to select Enable Disable on the enable/disable screen.
Page 37
SiUS071735EA Main Functions 1.7.2 If the Float Switch is OFF with the Thermostat ON in Cooling Operation ∗2 ∗1 ∗4 ∗3 Float switch 5 sec. 5 sec. Thermostat (running) Error display Drain pump 5 min. 5 sec. 5 min. 5 sec. 5 min. 5 sec. (R24610) When the float switch stays OFF for 5 sec., the thermostat turns OFF.
Main Functions SiUS071735EA 1.7.4 If the Float Switch Turns OFF and ON Continuously, or the Float Switch Turns OFF While AF Displayed ∗1 ∗2 ∗3 Float Switch 5 sec. 5 sec. 5 sec. 5 sec. 5 sec. Thermostat (running) Error Display Drain Pump 5 min.
SiUS071735EA Main Functions Other Functions 1.9.1 Signal Receiving Sign When the indoor unit receives a signal from the remote controller, the unit emits a signal receiving sound. 1.9.2 Auto-restart Function If a power failure (even a momentary one) occurs during the operation, the system restarts automatically in the same conditions as before when the power supply is restored to the conditions prior to the power failure.
Control Specification SiUS071735EA 2. Control Specification Mode Hierarchy Outline The air conditioner control has normal operation mode, forced operation mode, and power transistor test mode for installation and servicing. Details Heat Pump Model Air conditioner control mode Forced operation mode Forced cooling operation (for pump down operation) Power transistor test mode Normal operation mode...
SiUS071735EA Control Specification Frequency Control Outline The compressor frequency is determined according to the difference between the room thermistor temperature and the target temperature. When the shift of the frequency is less than zero (∆F<0) by PI control, the target frequency is used as the command frequency. Dropping function Input current control, etc.
Page 42
Control Specification SiUS071735EA When starting the compressor, the frequency is initialized according to the ∆D value of the indoor Initial Frequency unit. ∆D signal: Indoor frequency command The difference between the room thermistor temperature and the target temperature is taken as the ∆D value and is used for ∆D signal of frequency command.
SiUS071735EA Control Specification Controls at Mode Changing/Start-up 2.3.1 Preheating Control Outline The inverter operation in open phase starts with the conditions of the outdoor temperature, the discharge pipe temperature, the radiation fin temperature and the preheating command from the indoor unit. Outdoor temperature ≥...
Page 44
Control Specification SiUS071735EA 2.3.3 Four Way Valve Operation Compensation Outline At the beginning of operation as the four way valve is switched, the pressure difference to activate the four way valve is acquired when the output frequency is higher than a certain fixed frequency, for a certain fixed time.
SiUS071735EA Control Specification Discharge Pipe Temperature Control Outline The discharge pipe temperature is used as the internal temperature of the compressor. If the discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep the discharge pipe temperature from rising further.
Control Specification SiUS071735EA Input Current Control Outline The microcomputer calculates the input current while the compressor is running, and sets the frequency upper limit based on the input current. In case of heat pump models, this control is the upper limit control of frequency and takes priority over the lower limit control of four way valve operation compensation.
SiUS071735EA Control Specification Freeze-up Protection Control Outline During cooling operation, the signal sent from the indoor unit determines the frequency upper limit and prevents the indoor heat exchanger from freezing. Details When the freeze-up protection control starts, the compressor stops, the airflow rate is fixed to L tap, and the drain pump turns ON.
Control Specification SiUS071735EA Heating Peak-cut Control During heating operation, the indoor heat exchanger temperature determines the frequency upper limit to prevent abnormal high pressure. The operating frequency limitation is judged with the indoor heat exchanger temperature. Stop zone Dropping zone Keep zone Up zone Reset zone...
SiUS071735EA Control Specification Outdoor Fan Control 1. Fan ON control to cool down the electrical box The outdoor fan is turned ON when the electrical box temperature is high while the compressor is OFF. 2. Fan OFF control during defrosting The outdoor fan is turned OFF during defrosting.
Control Specification SiUS071735EA 2.10 Defrost Control Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature must be more than a certain value to finish defrosting. Details Conditions for Starting Defrost The starting conditions are determined with the outdoor temperature and the outdoor heat exchanger temperature.
SiUS071735EA Control Specification 2.11 Electronic Expansion Valve Control Outline The following items are included in the electronic expansion valve control. Electronic expansion valve is fully closed 1. Electronic expansion valve is fully closed when turning on the power. 2. Pressure equalizing control Open Control 1.
Page 52
Control Specification SiUS071735EA 2.11.1 Initialization as Power Supply On The electronic expansion valve is initialized (fully closed) when the power is turned on. Then, the valve opening is set and the pressure is equalized. 2.11.2 Pressure Equalizing Control When the compressor is stopped, the pressure equalizing control is activated. The electronic expansion valve opens and the pressure is equalized.
Page 53
SiUS071735EA Control Specification 2. When the operation mode is heating When the following condition is fulfilled, the discharge pipe thermistor disconnection is ascertained. Discharge pipe temperature +6°C (+10.8°F) < indoor heat exchanger temperature 09/12 class 15/18/24 class A (seconds) When the thermistor is disconnected When the disconnection is ascertained, the compressor continues operation for 9 minutes and then stops.
Control Specification SiUS071735EA 2.12 Malfunctions 2.12.1 Sensor Malfunction Detection Sensor malfunction can be detected in the following thermistor: 1. Outdoor heat exchanger thermistor 2. Discharge pipe thermistor 3. Radiation fin thermistor 4. Outdoor temperature thermistor 2.12.2 Detection of Overcurrent and Overload Outline An excessive output current is detected and the OL temperature is observed to protect the compressor.
Page 57
SiUS071735EA Wired Remote Controller (BRC1E73) 1. Operation mode selector button 7. Left button • Press this button to select the operation • Used to highlight the next items on the mode of your preference. left-hand side. * Available modes vary with the indoor unit •...
Page 58
Wired Remote Controller (BRC1E73) SiUS071735EA Liquid Crystal Display • Three types of display mode (Standard, Detailed and Simple) are available. • Standard display is set by default. • Detailed and Simple displays can be selected in the main menu. Standard display 10.Changeover controlled 11.Setback by the master indoor unit...
Page 59
SiUS071735EA Wired Remote Controller (BRC1E73) Simple display 1.Operation mode 14.Selectable Display Item 3.Setpoint 11.Setback 2.Fan speed 4.Stand by for Defrost/ <Simple display example> Hot start Note for all display modes • Depending on the field settings, while the indoor unit is stopped, OFF may be displayed instead of the operation mode and/or the setpoint may not be displayed.
Page 60
Wired Remote Controller (BRC1E73) SiUS071735EA 1. Operation mode “Error: Push Menu button” “Warning: Push Menu button” • Used to display the current operation Displayed if an error or warning is detected. • mode: Cool, Heat, Vent, Fan, Dry or Auto. In Auto mode, the actual operation mode •...
Page 61
SiUS071735EA Wired Remote Controller (BRC1E73) 11. Setback “ ” • The setback icon flashes when the unit is turned on by the setback control. 12. Airflow Direction “ ” Displayed when the airflow direction and • swing are set. • If the connected indoor unit model does not include oscillating louvers this item will not be displayed.
Wireless Remote Controller (BRC082A43) SiUS071735EA 2. Wireless Remote Controller (BRC082A43) ON OFF ON OFF TEMP TIME DOWN DOWN RESERVE CANCEL TIMER MODE TEST TEST TEST The situation which opened the front cover of the remote control (R25006) (R25007) Remote Controller...
Page 63
SiUS071735EA Wireless Remote Controller (BRC082A43) TIMER MODE START/STOP BUTTON DISPLAY “ ” “ I ” (SIGNAL TRANSMISSION) Use this button for TIMER MODE setting. This lights up when a signal is being transmitted. TIMER RESERVE/CANCEL BUTTON DISPLAY “ ” “ ”...
SiUS071735EA Part 6 Service Diagnosis 1. General Problem Symptoms and Check Items .........55 2. Troubleshooting with LED .................56 2.1 Indoor Unit....................56 2.2 Outdoor Unit ....................56 3. Service Diagnosis ..................57 3.1 Wired Remote Controller (BRC1E73) ............57 3.2 Wireless Remote Controller (BRC082A43) ..........59 4.
Page 65
SiUS071735EA 5. Check ...................... 100 5.1 Thermistor Resistance Check ..............100 5.2 Indoor Fan Motor Connector Check ............101 5.3 Power Supply Waveforms Check ............. 101 5.4 Electronic Expansion Valve Check............102 5.5 Four Way Valve Performance Check ............103 5.6 Inverter Unit Refrigerant System Check...........
General Problem Symptoms and Check Items SiUS071735EA 1. General Problem Symptoms and Check Items Symptom Check Item Details Reference Page The unit does not operate. Check the power supply. Check if the rated voltage is supplied. — Check the type of the indoor unit. Check if the indoor unit type is compatible with the —...
SiUS071735EA Troubleshooting with LED 2. Troubleshooting with LED Indoor Unit Operation Lamp The operation lamp blinks when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor malfunctions.
Service Diagnosis SiUS071735EA 3. Service Diagnosis Wired Remote Controller (BRC1E73) Relations On power-up, the message “Checking the connection. Please standby.” will be displayed on the Between Modes remote controller screen temporarily and then the basic screen will be displayed. To access a mode from the basic screen, refer to the figure below.
Page 69
The error code will flash and the service Error Code: A1 Contact Info contact and model name or code may 0123-456-7890 be displayed. Indoor Model ---/000 Notify your Daikin dealer of the Error Outdoor Model ---/000 code and model name or code. Service Diagnosis...
Service Diagnosis SiUS071735EA Wireless Remote Controller (BRC082A43) Relations The following modes can be selected by using INSPECTION/TEST OPERATION button on the Between Modes remote controller. Service data can be obtained. Indoor unit settings can be made. Press INSPECTION/TEST Error code history Filter cleaning sign time OPERATION button for Field...
Page 71
SiUS071735EA Service Diagnosis Step Action Press UP or DOWN button and change the UNIT No. until the indoor unit starts to beep. UP button DOWN button (R15408) If you hear... Then... 3 short beeps Follow all steps below. 1 short beep Follow steps 3 and 4.
Page 72
Service Diagnosis SiUS071735EA Step Action Press UP or DOWN button to change the error code upper digit until the indoor unit beeps. DOWN UP button DOWN button (R15411) If you hear... Then... 2 short beeps The upper digit matches. 1 short beep No digits match.
Page 73
SiUS071735EA Service Diagnosis Step Action Press UP or DOWN button and change the error code lower digit until the indoor unit generates long beep. DOWN UP button DOWN button (R15413) If you hear... Then... 2 short beeps No digits match. 1 long beep Both upper and lower digits match.
Troubleshooting SiUS071735EA 4. Troubleshooting Error Codes and Description Reference Error Codes Description Page System 00 Normal — Low-voltage detection or over-voltage detection Signal transmission error (between indoor unit and outdoor unit) Mismatching of indoor unit and outdoor unit Indoor Indoor unit PCB abnormality Unit Drain level control system abnormality Indoor fan motor (DC motor) or related abnormality...
SiUS071735EA Troubleshooting Indoor Unit PCB Abnormality Error Code Method of Error The system checks the data from EEPROM. Detection Error Decision The data from the EEPROM is not received correctly. Conditions EEPROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds its content without power.
Troubleshooting SiUS071735EA Drain Level Control System Abnormality Error Code Method of Error The float switch detects error. Detection Error Decision The water level reaches its upper limit and the float switch turns OFF. Conditions Supposed Defective drain pump Causes Improper drain piping work Clogged drain piping Defective float switch Defective indoor unit PCB...
SiUS071735EA Troubleshooting Indoor Fan Motor (DC Motor) or Related Abnormality Error Code Method of Error Detection from the current flow on the fan PCB Detection Detection from the rotation speed of the fan motor in operation Error Decision The rotation speed is less than a certain level for 6 seconds. Conditions Supposed Clogged foreign matter...
Page 78
Troubleshooting SiUS071735EA The HAP lamp on the indoor unit control PCB is blinking while the HAP lamp on the fan PCB is not blinking. Turn OFF the power supply Turn OFF the power supply and wait for 10 minutes. and wait for 10 minutes. Check No.02 Check the fan motor connectors.
SiUS071735EA Troubleshooting Indoor Fan PCB Abnormality Error Code Method of Error Microcomputer checks the voltage state of the fan PCB. Detection Error Decision Overvoltage or voltage drop is detected on the fan PCB. Conditions Supposed Defective fan PCB Causes External factor such as noise Troubleshooting Be sure to turn off the power switch before connecting Caution...
Troubleshooting SiUS071735EA Humidifier or Related Abnormality Error Code Method of Error Water leakage from humidifier(s) is detected based on the float switch ON/OFF changeover while Detection the system is not operating. Error Decision The float switch changes from ON to OFF while the system is OFF. Conditions Supposed Defective float switch...
SiUS071735EA Troubleshooting Thermistor or Related Abnormality C4, C5, C9 Error Code Method of Error The temperatures detected by the thermistors determine thermistor errors. Detection Error Decision The thermistor is disconnected or shorted while the unit is running. Conditions Supposed Disconnection of connector Causes Defective thermistor(s) Breaking of wires...
Troubleshooting SiUS071735EA Remote Controller Thermistor Abnormality Error Code Method of Error Even if remote controller thermistor is faulty, system is possible to operate by system thermistor. Detection Malfunction detection is carried out by the temperature detected by the remote controller thermistor.
SiUS071735EA Troubleshooting Signal Transmission Error (Between Indoor Unit and Remote Controller) Error Code Method of Error In case of controlling 1 indoor unit with 2 remote controllers, check the system using microcomputer Detection if signal transmission between indoor unit and remote controller (main and sub) is normal. Error Decision Normal transmission does not continue for specified period.
Troubleshooting SiUS071735EA 4.10 Signal Transmission Error (Between MAIN Remote Controller and SUB Remote Controller) Error Code Method of Error In case of controlling 1 indoor unit with 2 remote controllers, check the system using microcomputer Detection if signal transmission between MAIN remote controller and SUB remote controller is normal. Error Decision Normal transmission does not continue for specified period.
SiUS071735EA Troubleshooting 4.11 Low-voltage Detection or Over-voltage Detection Error Code Method of Error Low-voltage detection: Detection An abnormal voltage drop is detected by the DC voltage detection circuit. Over-voltage detection: An abnormal voltage rise is detected by the over-voltage detection circuit. Error Decision Low-voltage detection: Conditions...
Page 86
Troubleshooting SiUS071735EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check the power supply voltage. Is the voltage fluctuation Correct the power supply. within ±10% from the rated value? Check the connection of the compressor harness.
SiUS071735EA Troubleshooting 4.12 Signal Transmission Error (Between Indoor Unit and Outdoor Unit) Error Code Method of Error The signal transmission data from the outdoor unit is checked whether it is normal. Detection Error Decision The data sent from the outdoor unit cannot be received normally, or the content of the data is Conditions abnormal.
Page 88
Troubleshooting SiUS071735EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.11 Check the power supply voltage. Refer to P.101 Is the voltage fluctuation Correct the power supply. within ±10% from the rated value? Check the connection wires...
SiUS071735EA Troubleshooting 4.13 Mismatching of Indoor Unit and Outdoor Unit Error Code Error Decision Improper combination of indoor and outdoor units Conditions Supposed Defective indoor unit PCB Causes Indoor-outdoor unit transmission wiring error Defective optional unit(s) wirings Improper power supply wiring of indoor unit Improper wiring of connecting wires between indoor/outdoor units Troubleshooting Be sure to turn off the power switch before connecting or disconnecting...
Troubleshooting SiUS071735EA 4.14 Outdoor Unit PCB Abnormality Error Code Method of Error The system checks if the microprocessor is working in order. Detection The system checks if the zero-cross signal comes in properly. Error Decision The microprocessor program runs out of control. Conditions The zero-cross signal is not detected.
SiUS071735EA Troubleshooting 4.15 OL Activation (Compressor Overload) Error Code Method of Error A compressor overload is detected through compressor OL. Detection Error Decision If the error repeats, the system is shut down. Conditions Reset condition: Continuous run for about 60 minutes without any other error Supposed Disconnection of discharge pipe thermistor Defective discharge pipe thermistor...
Page 92
Troubleshooting SiUS071735EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.100 Discharge pipe thermistor Insert the thermistor in disconnected? position. Check No.12 Refer to P.102 Check No.
SiUS071735EA Troubleshooting 4.16 Compressor Lock Error Code Method of Error A compressor lock is detected by the current waveform generated when applying high-frequency Detection voltage to the motor. Error Decision If the error repeats, the system is shut down. Conditions Reset condition: Continuous run for about 11 minutes without any other error Supposed Closed stop valve...
Troubleshooting SiUS071735EA 4.17 DC Fan Lock (Outdoor Fan Motor) Error Code Method of Error An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC. Detection Error Decision The fan does not start in 15 ~ 30 seconds even when the fan motor is running. Conditions If the error repeats, the system is shut down.
SiUS071735EA Troubleshooting 4.18 Input Overcurrent Detection Error Code Method of Error An input overcurrent is detected by checking the input current value with the compressor running. Detection Error Decision The current exceeds about 12.0 ~ 18.0 A (depending on the model) for 2.5 seconds with the Conditions compressor running.
Troubleshooting SiUS071735EA 4.19 Four Way Valve Abnormality Error Code Method of Error The room temperature thermistor and the indoor heat exchanger thermistor are checked if they Detection function within their normal ranges in each operation mode. Error Decision The following condition continues over 10 minutes after operating for 5 minutes. Conditions Cooling/Dry A –...
Page 97
SiUS071735EA Troubleshooting Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Four way valve coil Refer to P.100 Correct the four way valve disconnected (loose)? coil. Check No.13 Refer to P.103 Harness disconnected? Reconnect the harness.
Troubleshooting SiUS071735EA 4.20 Discharge Pipe Temperature Control Error Code Method of Error An error is determined with the temperature detected by the discharge pipe thermistor. Detection Error Decision If the temperature detected by the discharge pipe thermistor rises above A, the compressor stops.
SiUS071735EA Troubleshooting 4.21 High Pressure Control in Cooling Error Code Method of Error High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the Detection temperature sensed by the outdoor heat exchanger thermistor exceeds the limit. Error Decision The temperature sensed by the outdoor heat exchanger thermistor rise above 57.5 ~ 61°C Conditions (135.5 ~ 141.8°F) (depending on the model).
Page 100
Troubleshooting SiUS071735EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Check the installation space. Refer to P.100 Check No. 17 Check No.12 Change the installation Check the installation location or direction.
SiUS071735EA Troubleshooting 4.22 System Shutdown due to Compressor Internal Temperature Abnormality Error Code Method of Error Operation is halted when the temperature detected by the discharge pipe thermistor exceeds the Detection determined limit. Error Decision Temperature exceeds the detection threshold of 127.5°C (261.5°F) during forced cooling operation. Conditions Supposed Abnormal operation due to air intrusion...
Troubleshooting SiUS071735EA 4.23 Compressor System Sensor Abnormality Error Code Method of Error The system checks the DC current before the compressor starts. Detection Error Decision The voltage converted from the DC current before compressor start-up is out of the range 0.5 ~ Conditions 4.5 V.
SiUS071735EA Troubleshooting 4.24 Position Sensor Abnormality Error Code Method of Error A compressor start-up failure is detected by checking the compressor running condition through the Detection position detection circuit. Error Decision If the error repeats, the system is shut down. Conditions Reset condition: Continuous run for about 11 minutes without any other error Supposed...
Page 104
Troubleshooting SiUS071735EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.15 Turn off the power. Refer to P.104 Check the power supply voltage. Check No.18 Refer to P.107 Is the power supply voltage fluctuation within...
SiUS071735EA Troubleshooting 4.25 Thermistor or Related Abnormality (Outdoor Unit) H9, J3, J6, P4 Error Code Method of Error This fault is identified based on the thermistor input voltage to the microcomputer. Detection A thermistor fault is identified based on the temperature sensed by each thermistor. Error Decision The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less Conditions...
Page 106
Troubleshooting SiUS071735EA Troubleshooting In case of H9, J3, J6 Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Turn on the power again. Refer to P.100 Error displayed Reconnect the connectors again on remote or thermistors.
SiUS071735EA Troubleshooting 4.26 Electrical Box Temperature Rise Error Code Method of Error An electrical box temperature rise is detected by checking the radiation fin thermistor with the Detection compressor off. Error Decision With the compressor off, the radiation fin temperature is above A. Conditions The error is cleared when the radiation fin temperature drops below B.
Troubleshooting SiUS071735EA 4.27 Radiation Fin Temperature Rise Error Code Method of Error A radiation fin temperature rise is detected by checking the radiation fin thermistor with the compressor on. Detection Error Decision If the radiation fin temperature with the compressor on is above A. Conditions The error is cleared when the radiation fin temperature drops below B.
SiUS071735EA Troubleshooting 4.28 Output Overcurrent Detection Error Code Method of Error An output overcurrent is detected by checking the current that flows in the inverter DC section. Detection Error Decision A position signal error occurs while the compressor is running. Conditions A rotation speed error occurs while the compressor is running.
Page 110
Troubleshooting SiUS071735EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. ∗ An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output Check No.15 overcurrent after the wires have been disconnected and reconnected for part replacement, check the wiring again.
SiUS071735EA Check 5. Check Thermistor Resistance Check Check No.01 Disconnect the connectors of the thermistors from the PCB, and measure the resistance of each thermistor using a multimeter. The data is for reference purpose only. Thermistor temperature Resistance (kΩ) °C °F –20 –4...
Check SiUS071735EA Indoor Fan Motor Connector Check Check No.02 1. Turn the power supply OFF. 2. With the fan motor connector disconnected, measure the resistance between each pin, then make sure that the resistance is more than the value mentioned in the following table. Measuring points Judgement White - Blue...
SiUS071735EA Check Electronic Expansion Valve Check Check No.12 Conduct the following to check the electronic expansion valve (EV). 1. Check if the EV connector is correctly connected to the PCB. 2. Turn the power off and on again, and check if the EV generates a latching sound. 3.
Check SiUS071735EA Four Way Valve Performance Check Check No.13 Turn the power off and then on again. ∗ Four way valve coil Start heating operation. Cooling / Dry / Defrost: Not energized Heating: energized voltage at 208 - 230 Replace the outdoor unit VAC with compressor PCB (main PCB).
SiUS071735EA Check Inverter Analyzer Check Check No.15 Characteristics Inverter analyzer: RSUK0917C If an abnormal stop occurs due to compressor startup failure or overcurrent output when using an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or some other failure (main PCB, power module, etc.).
Page 116
Check SiUS071735EA Step 3 Activate power transistor test operation from the outdoor unit. Start method of power transistor test operation Note: Power transistor test operation can be activated only once after turning on the power supply. If reactivation of the power supply transistor operation is needed, turn the power supply off and then on again.
SiUS071735EA Check Caution 1. When the output frequency is low, the LEDs blink slowly. As the output frequency increases, the LEDs blink quicker. (The LEDs look like they are lit.) 2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals. Otherwise, the terminals may be burned due to loosening.
Check SiUS071735EA Installation Condition Check Check No.17 Installation condition check Check the allowable dimensions of the air Change the installation suction and location or direction. discharge area. Is the discharged air Change the installation short-circuited? location or direction. Is the outdoor heat Clean the outdoor heat exchanger very dirty? exchanger.
SiUS071735EA Check 5.11 Outdoor Fan System Check Check No.19 DC motor Check the outdoor fan system. Fan motor Is the lead wire connector outdoor fan running? Go to Check No. 16. disconnected? Reconnect the connector. Outdoor fan system is functioning. (R21195) 5.12 Main Circuit Short Check Check No.20...
Page 120
Check SiUS071735EA 15/18/24 class Multimeter (R25105) Service Diagnosis...
SiUS071735EA Check 5.13 Power Module Check Check No.22 Check to make sure that the voltage between (+) and (–) of the power module is approximately 0 V before checking. Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector.
Page 122
Check SiUS071735EA 15/18/24 class DC_P1: + (R20704) DC_N1: – Service Diagnosis...
SiUS071735EA Part 7 Trial Operation and Field Settings 1. Pump Down Operation................113 2. Forced Cooling Operation ...............114 3. Trial Operation ..................115 4. Field Settings ..................118 4.1 How to Change the Field Settings............118 4.2 Overview of the Field Settings..............121 4.3 MAIN/SUB and Address Setting for Wireless Remote Controller ....
Pump Down Operation SiUS071735EA 1. Pump Down Operation Outline In order to protect the environment, be sure to pump down when relocating or disposing of the unit. Details 1. Remove the valve cap from the liquid stop valve and the gas stop valve. 2.
SiUS071735EA Forced Cooling Operation 2. Forced Cooling Operation Outline The forced cooling operation is allowed when both the following conditions are met. 1. The outdoor unit is not abnormal and not in the 3-minute standby mode. 2. The outdoor unit is not operating. Protection functions have priority over all other functions during forced cooling operation.
Trial Operation SiUS071735EA 3. Trial Operation Outline Make sure to install the decoration panel before carrying out trial operation if the wireless remote controller is used. Trial operation should be carried out in either COOL or HEAT operation. 1. Measure the supply voltage and make sure that it is within the specified range. 2.
Page 127
SiUS071735EA Trial Operation With Wired Remote Controller (BRC1E73) 1. Set to COOL or HEAT operation using the Basic screen remote controller. Cool Set to 2. Press and hold Cancel button for 4 seconds Press and hold Cancel or longer. Service settings menu is button for 4 seconds or displayed.
Page 128
Trial Operation SiUS071735EA With Wireless Remote Controller (BRC082A43) 1. Press button and select the COOL or HEAT operation. 2. Press button twice. “TEST” is displayed. 3. Press button within 10 seconds, and the test operation starts. Monitor the operation of the indoor unit for a minimum of 10 minutes. During test operation, the indoor unit will continue to cool/heat regardless of the temperature setpoint and room temperature.
SiUS071735EA Field Settings 4. Field Settings How to Change the Field Settings Outline If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed. Refer to the instruction manual for each optional accessory. Note: When using 2 remote controllers for 1 indoor unit, change the field settings from MAIN remote controller.
Page 130
Field Settings SiUS071735EA 3. Highlight the mode, and select desired “Mode No.” by using (Up/Down) button. 4. In the case of setting per indoor unit during group control (When Mode No. such as 20 22 23 25 are selected), highlight the unit No.and select “Indoor unit No.” to be set by using (Up/Down) button.
Page 131
SiUS071735EA Field Settings Wireless Remote Controller (BRC082A43) UP button Mode No. DOWN button Field setting mode First code No. RESERVE button MODE button Second code No. INSPECTION/TEST button (R25096) To set the field settings, you have to change: Mode No. First code No.
Field Settings SiUS071735EA Overview of the Field Settings : Factory setting First Second Code No. Mode Code Description of setting Filter cleaning Approx. Approx. Longlife sign interval 2,500 1,250 — — — — filter (used to change hrs. hrs. filter cleaning display interval Standard Approx.
SiUS071735EA Field Settings MAIN/SUB and Address Setting for Wireless Remote Controller Outline If setting multiple wireless remote controllers to operate in one room, perform address setting for the receiver and the wireless remote controller. If using both a wired remote controller and a wireless remote controller with 1 indoor unit, change the MAIN/SUB switch of the signal receiver PCB.
Page 134
Field Settings SiUS071735EA Wireless Remote Factory set is 1. Change the wireless remote controller address setting by the following steps, if necessary. Controller 1. Hold down button and /TEST button at the same time for at least 4 seconds to enter the Address field setting mode.
SiUS071735EA Field Settings After Setting Stick the Unit No. label on the receiver and the back of the wireless remote controller. Unit No. label (5) Wireless remote controller (2) (R25081) Note: Set the Unit No. of the receiver and the wireless remote controller to be the equal. If the settings differ, the signal from the remote controller cannot be transmitted.
Silicone Grease on Power Transistor/Diode Bridge SiUS071735EA 5. Silicone Grease on Power Transistor/Diode Bridge Outline Apply the specified silicone grease to the heat radiation part of a power transistor/diode bridge when you replace an outdoor unit PCB. The silicone grease encourages the heat radiation of a power transistor/diode bridge.
SiUS071735EA Piping Diagrams Outdoor Unit RX09/12RMVJU(9) OUTDOOR UNIT OUTDOOR TEMPERATURE HEAT EXCHANGER THERMISTOR 9/32 CuT 9/32 CuT HEAT EXCHANGER THERMISTOR 3/16 CuT 1/4 CuT 1/4 CuT 3/16 CuT MUFFLER WITH MOTOR FILTER OPERATED PROPELLER FAN VALVE MUFFLER WITH 3/8 CuT FILTER FOUR WAY VALVE...
SiUS071735EA Wiring Diagrams 2. Wiring Diagrams Indoor Unit FDMQ09/12/15/18/24RVJU 3D112629A Note: A1P: Control PCB A2P: Indoor fan PCB Refer to Part 3 for Printed Circuit Board Connector Wiring Diagram. Appendix...
Wiring Diagrams SiUS071735EA Outdoor Unit RX09/12RMVJU(9) 3D112531A Note: PCB1: Main PCB Refer to Part 3 for Printed Circuit Board Connector Wiring Diagram. Appendix...
Page 143
SiUS071735EA Wiring Diagrams RX15/24RMVJU(A), RX18RMVJU(9)(A) WIRING DIAGRAM FIELD WIRING INDOOR MRM20 IPM1 TO INDOOR UNIT MRM10 L2 2 3.15A 3.15A W V U POWER SUPPLY MRCW X11A OUTDOOR NOTE 1. REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS. t˚ t˚ t˚...
Operation Limit SiUS071735EA 3. Operation Limit RX09/12RMVJU(9), RX15/24RMVJU(A), RX18RMVJU(9)(A) Heating Cooling 64.4 114.8 *NOTE 2 57.2 68 73.4 82.4 Indoor temp. (˚FWB) Indoor temp. (˚FDB) Notes: 1. The graphs are based on the following conditions. • Equivalent piping length 25ft •...
Page 145
Revision History Month / Year Version Revised contents 01 / 2018 SiUS071735E First edition 06 / 2020 SiUS071735EA Model addition: RX09/12RMVJU9, RX15/24RMVJUA, RX18RMVJU9(A)
Page 146
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.