Siemens SIMEAS R-PMU Manual page 252

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

16
16.1 Technical Data of the SIMEAS R-PMU
Electromagnetic compatibility
Electromagnetic HF field
amplitude-modulated
Electromagnetic HF field
single frequencies
Magnetic field with
power system frequency
Electrostatic discharge
High frequency, unsymmetrical
amplitude-modulated
Fast transients (bursts)
Power supply AC/DC
Signal lines, control and
communications lines, data and
printer lines
Repetition frequency
System frequency, unsymmetrical
1 MHz HF test
Power supply, system
and communications lines
Signal lines, data and
printer lines
252
IEC 61000-4-3
Test level 3, 10 V/m
80 MHz to 1000 MHz,
80 % amplitude modulation
IEC 60255-22-3
Test level 3, 10 V/m
Frequencies:
80 MHz ±0.4 MHz
160 MHz ±0.8 MHz
450 MHz ±2.25 MHz
900 MHz ±5 MHz
80 % amplitude modulation
900 MHz ±5 MHz
50 % pulse modulation
IEC 61000-4-8; EN 61000-4-8
Permanent field
Test level 5, 100 A/m
IEC 61000-4-2; EN 61000-4-2
Contact discharge
Test level 4, test voltage 8 kV
Air discharge
Test level 4, test voltage 15 kV
IEC 61000-4-6; EN 61000-4-6
Test level 3
Voltage level 10 V
Frequency range 150 kHz to 80 MHz
IEC 61000-4-4; EN 61000-4-4
Test level 4, test voltage 4 kV,
direct coupling
Test level 4, test voltage 2 kV,
coupling, cap. data link
5 kHz
IEC 60770
Test level 10 V and
Test level 250 V (customer-specific)
IEC 60255-22-1
Direct and differential-mode voltage 2.5 kV
Common-mode voltage 2.5 kV
Differential-mode voltage 1.0 kV
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents