Download Print this page

Advertisement

Quick Links

TRIGA Life Safety Systems, LLC
7600 Olde Eight Rd, Hudson, Ohio, 44236-1057
Tel: +1 330-577-5199, Email: info@trigaglobal.com
1 Description
The Triga Series, Emergency Communication System uses the
TR-NIC (Network Interface Card) to connect to the Triga Series
Fire, Alarm Control Panels. The TR-NIC supports two types of
fiber-option modules to convert the wire to the fiber.
TR-FML (Fiber-Optic Multi-Mode, Receiver)
TR-FSL (Fiber-Optic Single-Mode Transmitter)
1.1 TR-FML (Fiber-Optic Multi-Mode,
Receiver)
The TR-FML is a fiber module that is used as one channel to
transmit or receive communications with the ECS-NVCM (Net-
work Voice Control Module) or TR-NIC (Network Interface
Card). It allows the multi-mode fiber to network between the TR-
FML module boards. Figure 1 shows the TR-FML fiber module.
Figure 1 TR-FML Fiber Modules
1.2 TR-FSL (Fiber-Optic Single-Mode,
Transmitter)
The TR-FSL is a fiber module that is used as one channel to
transmit or receive communications with the ECS-NVCM (Net-
work Voice Control Module) or TR-NIC (Network Interface
Card). It allows the single-mode fiber to network between the
TR-FSL module boards. Figure 2 shows the TR-FSL fiber mod-
ule.
Figure 2 TR-FSL Fiber Modules
Table 1 lists the models that are assigned to the ECS and TR-
NIC.
ECS
TR-2100ECSR
TR-2100R
Table 1 Network Voice and Interface Card Modules
TR-FML/TR-FSL Fiber Option Modules
TR-NIC
Product Installation Document
PN LSL10178-003TR-E:A 02/03/21 ECN: 151608
1.3 Compatibility
The TR-FML/TR-FSL fiber option modules can be used with the
compatible Triga Series, Fire Alarm Control Panels (FACP's).
For additional information, refer to the following FACP docu-
ments that are located on the Triga ESD Website,
www.trigaglobal.com.
Document
TR-2100ECSR Manual
TR-NIC Installation Sheet
TR-RPS1 Manual
Triga ECS Manual
1.4 TR-FML/TR-FSL Specifications
Table 2 lists the TR-FML multi-mode fiber-optic and the TR-
FSL single-mode fiber-optic modules, digital audio ports specifi-
cations.
Specifications
Type of Connector: Type ST
Maximum
8 dbB for multi-mode
Attenuation:
with 62.5/125
micrometer cable
@ 200 µ.
Current Draw:
Standby Current:
0.053 A
Alarm Current:
0.053 A
Environment Rating: 32° to 120°F
(0° to 49°C), 0% to
93%
Relative Humidity:
Non-condensing at
90°F (30°C)
Table 2 TR-FML/TR-FSL Specifications
2 Installation
CAUTION: STATIC SENSITIVE EQUIPMENT:
!
THIS EQUIPMENT IS SENSITIVE TO STATIC
ELECTRICITY. IT MAY BE DAMAGED IF NOT
PROPERLY HANDLED. TRANSPORT AND STORE
THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT
COULD CAUSE LATENT DAMAGE TO THE
EQUIPMENT WHICH MIGHT NOT MANIFEST ITSELF
UNTIL AFTER THE EQUIPMENT IS PLACED IN
SERVICE.
DISCONNECT ALL POWER:
REMOVE ALL SOURCES OF POWER BEFORE YOU
SERVICE, REMOVE OR INSTALL ANY UNITS.
Document
Part Number
LS10143-003TR-E
LS10171-002TR-E
LS10259-002TR-E
LS10262-002TR-E
TR-FML
TR-FSL
Type LC
30 dB for multi-mode
with 9/125 micrometer
cable @ 1310 nm.
0.079 A
0.079 A
32° to 120°F
(0° to 49°C), 0% to
93%
Non-condensing at
90°F (30°C)

Advertisement

loading
Need help?

Need help?

Do you have a question about the TR-FML and is the answer not in the manual?

Questions and answers

Summary of Contents for TRIGA TR-FML

  • Page 1 1.1 TR-FML (Fiber-Optic Multi-Mode, TR-2100ECSR Manual LS10143-003TR-E Receiver) TR-NIC Installation Sheet LS10171-002TR-E The TR-FML is a fiber module that is used as one channel to TR-RPS1 Manual LS10259-002TR-E transmit or receive communications with the ECS-NVCM (Net- Triga ECS Manual LS10262-002TR-E work Voice Control Module) or TR-NIC (Network Interface 1.4 TR-FML/TR-FSL Specifications...
  • Page 2 Figure 3 illustrates the TR-FML/TR-FSL installed to the Figure 4 illustrates the TR-FML/TR-FSL installed to the TR-NIC. ECS-NVCM. TR-NIC TR-FML TR-FSL ECS-NVCM TR-FML TR-FSL TR-FML TR-FSL TR-FML TR-FSL Figure 3 TR-FML Installation Figure 4 TR-FSL Installation PRELIMINARY: TR-FML/TR-FSL Product Installation Document — P/N LSL10178-003TR-E:A 02/03/21...
  • Page 3 FIBER OUT FIBER-IN Figure 6 TR-FSL Circuit Board Diagram TR-FSL Fiber-Optic Module Wiring Connections FIBER-OUT Table 5 lists the TR-FML terminal wiring designations to connect the module. Designation Description Figure 5 TR-FML Circuit Board Diagram Plugs on to P5 (Port 1) or P6 (Port 2) of the TR-FML Fiber-Optic Module Wiring Connections TR-NVCM or TR-NIC.

This manual is also suitable for:

Tr-fsl