Smart Grid Control
NOTE
MIM-E03CN(MONO Control Kit) model does not support this Smart grid function.
The FSV #5091 should be set to "1(Yes)" for Smart Grid control.
FSV
#5091
Operation mode for Smart Grid
Operation Mode
Mode 1
Mode 2
Mode 3
Mode 4
Mode 1 : Forced thermo off operation of all system
Mode 2 : Normal operation
It is equally applied both heating and hot water mode.
The heating and hot water setting temperature are set by the FSV setting value.
Heating mode (Room sensor setting) : Current setting value + FSV #5092
Heating mode (Water outlet setting) : Current setting value + FSV #5092
Heating mode (Water law setting) : Current setting value + FSV #5092
Hot water mode : Current setting value + FSV #5093
Mode 4 : When operating on, the setting temperature is reflected as follows.
Hot water mode
[If FSV #3031 is 0 (no use booster heater) or DHW mode is economic mode, it does not
activate booster heater.]
Heating mode
0
Disable (Default)
Terminal 1
Short
Open
Open
Short
(Max=FSV #2021, #2022, #2031, #2032)
1
Activation
Terminal 2
Open
Open
Short
Short
English