PD6830 Explosion-Proof Pulse Input Rate/Totalizer
Connections
Screw terminals accept 12 to 22 AWG wire
Enclosure
NEMA 4X, IP68 Explosion-proof die cast
aluminum, 0.30% max copper content,
corrosion resistant epoxy coating,
Color: Blue
Window: Glass
Three ¾" NPT threaded conduit openings.
One ¾" NPT nickel plated brass conduit
plug with 12 mm hex key fitting installed.
Mounting
May be mounted directly to conduit. Two
slotted flanges for wall mounting or NPS
1½" to 2½" or DN 40 to 65 mm pipe
mounting.
See Dimensions on page 11.
Overall
5.65" x 5.25" x 4.86" (W x H x D)
Dimensions
(144 mm x 133 mm x 124 mm)
Weight
5.00 lbs (80 oz, 2.27 kg)
Warranty
3 years parts and labor. See Warranty
Information and Terms & Conditions on
www.predig.com

Rate Input

Pulse/Transistor/
Field selectable; Sourcing or sinking
Contact Closure
pulse or square wave 0-5 V, 0-12 V,
Input
or 0-24 V; TTL; NPN or PNP
transistor; Open collector 100 kΩ
pull-up to 3 V; Switch contact 100 kΩ
pull-up to 3 V; PNP transistor 100 kΩ
pull-down to ground (COM) Active
input 100 kΩ to battery level, 10 kΩ
to power
Maximum Frequency: 64 kHz
Minimum Pulse Width: 5 µs
Threshold Setting Low (V) High (V)
Normal
Low
Opto-Isolated
Sourcing pulse or square wave 0-5 V,
Input
0-12 V, or 0-24 V;
Logic High: 2-24 V, Logic Low: < 1 V
Maximum Frequency: 20 kHz
Minimum Pulse Width: 20 µs
Input Current: 1 mA @ 5 V,
2.5 mA @ 12 V, 5 mA @ 24 V
Low Voltage Mag
Sensitivity: 20 mVp-p to 24 Vp-p
Pickup Input
Maximum Frequency: 6 kHz
Minimum Input
0.0001 Hz. Minimum frequency is
Frequency
dependent on high gate setting
(rate display).
Input Impedance
Pulse input: Greater than 75 kΩ @ 1 kHz.
Open collector/switch input:
100 kΩ pull-up to 3 V.
Accuracy
±0.03% of calibrated span ±1 count
Temperature Drift Rate display is not affected by changes
in temperature.
Low-Flow Cutoff
0.1 to 99,999 or disable. Point below at
which the display always shows zero.
Decimal Point
Up to four decimal places or none:
4. 4 444, 33. 3 33, 222. 2 2, 1111. 1 , or 00000
Calibration
May be calibrated using K-Factor, scale
without signal source, or by applying an
external calibration signal.
K-Factor
Field programmable K-Factor converts
input pulses to rate in engineering units.
May be programmed from 0.000001 to
9,999,999 pulses/unit.
for complete details.
1.2
2.0
0.2
1.2
7
Calibration Range Input 1 signal must be ≥ 1 Hz; input 2
signal may be set anywhere above
input 1 setting. Minimum input span is
1 Hz. An Error message will appear if
the input 1 and input 2 signals are too
close together.
Input Contact
Programmable contact debounce filter.
Debounce Filter
Input signal frequency speed selections
of Hi (no filter), Med (250 Hz max input,
2 ms pulse width), and Low (100 Hz
max input, 5 ms minimum pulse width).
Time Base
Second, minute, hour, or day
Gate
Low gate: 1-99 seconds;
High gate: 2-9,999 seconds

Rate/Totalizer

Display
The Top display is assigned to rate or
total. The Bottom display is
Assignment
programmable to display total; total and
units; total and tag; total, total units, and
rate units; grand total; grand total and
grand total units; grand total and tag;
grand total, grand total units, and rate
units; rate units; rate; rate and total
units; rate and rate units; rate and tag;
rate units; total units; a custom tag; or
be off (blank).
Rate Display
Gallons, liters, imperial gallons, cubic
Units
meters, barrels, bushels, cubic yards,
cubic feet, cubic inches, liquid barrels,
beer barrels, hectoliters, or custom.
Rate Display
Rate display may be calculated in
terms of units per second, minute,
Time Base
hour, or day.
Total & Grand
Gallons, liters, imperial gallons, cubic
Total Display
meters, barrels, bushels, cubic yards,
cubic feet, cubic inches, liquid barrels,
Units
beer barrels, hectoliters, or custom.
Setting is independent for each.
Total & Grand
x1, x100 (h), x1000 (k), or x1,000,000
Total Display
(M) multiplier (and prefix) applied to
total or grand total display units. Setting
Unit Multiplier
is independent for each.
Total & Grand
Up to six decimal places or none:
Total Decimal
6. 6 66666, 55. 5 5555, 444. 4 444, 3333. 3 33,
22222. 2 2, 111111. 1 or 0000000 Total
Point
and grand total decimal points are
independently programmed, and are
independent of rate decimal point.
Totalizers
Calculates total and grand total based
on rate and field programmable
multiplier to display total in engineering
units. Time base must be selected
according to the time units in which the
rate is displayed. The total and grand
total utilize the same time base, with
different conversion factors and resets.
Totalizer Reset
Via SafeTouch RESET button,
mechanical button (cover off), external
contact closure (total only),
automatically via user selectable preset
value and time delay (1 – 99,999 sec).
Manual reset may be disabled or
protected by password for the total and
grand total. Total and grand total reset
independently.