Floor mounted, gas-fired condensing boiler with matrix gas burner and lambda pro control (116 pages)
Summary of Contents for Viessmann Vitogas 100
Page 1
Service instructions for heating engineers Vitogas 100 Type GS1, 72 to 144 kW Gas fired boiler for natural gas and LPG See notes on applicability, page 2. VITOGAS 100 Please keep safe 5692 382 GB 2/2004...
It is not permitted to carry out repairs maintenance and repairs must only on parts that fulfil a safety function. be carried out by a competent Use only original Viessmann spare person (heating engineer/installation parts, or equivalent parts that have contractor).
Initial start-up, inspection and maintenance Steps initial start-up, inspection and maintenance For further instructions on individual steps, see pages indicated. Commissioning steps Inspection steps Maintenance steps Page 1. Preparing for commissioning and checking diaphragm expansion vessel ..........2.
Initial start-up, inspection and maintenance Further details regarding the individual steps Preparing for commissioning and checking the diaphragm expansion vessel ¨ Safety instructions Only for commissioning with Vitotronic 300, type GW2 Check that the high limit safety cut-out of the control unit is not set higher than 110 ºC.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking the gas type 1. Enquire the gas type and Wobbe After conversion from index (Wo) from your local mains H Natural gas E to natural gas LL: gas or LPG supplier.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking static and supply pressure ¨ Safety instructions Measure the CO value before and after any work on gas appliances, to prevent any health hazards and to ensure the perfect operational condition of the system.
Page 8
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) 6. Check the supply (flow) pressure; it should be H 17.4 to 25 mbar for natural gas, H 42.5 to 57.5 mbar for LPG Record the actual value in the service report.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking the nozzle pressure 1. Close the gas shut-off valve. 2. Unscrew the screw inside test nipple A and connect the pressure gauge. 3. Open the gas shut-off valve. Start up the boiler.
Page 10
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) 10. Switch OFF system ON/OFF switch 11. ¨ Safety instructions at the control unit (boiler shuts Open gas shut-off valve, start up down), close gas shut-off valve, boiler and check soundness of remove pressure gauge and close test nipple A.
Page 11
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Rated output Full Full Full Full load load load load 108 kW 120 kW 132 kW 144 kW Partial Partial Partial Partial load load load load 70.2 kW 78.0 kW 85.8 kW 93.6 kW...
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking the flue gas values ¨ Safety instructions Measure the CO value before and after any work on gas appliances, to prevent any health hazards and to ensure perfect system condition. Record the flue gas values in the service report.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking the draught Check the supply pressure behind the draught hood in hPa (1 hPa = 1 mbar) and record in the service report. Please note: Required boiler draught: 0.03 hPa (0.03 mbar). The chimney draught must not be higher than 0.1 hPa (0.1 mbar), install a draught stabiliser (agree details with your local flue gas inspector) in the chimney.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking the burner tubes 1. Check the gas orifices for damage. 2. Blow out the burner tubes with compressed air or wash in a soapy solution. Checking the ignition burner 1.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Clean the heating surfaces, if required (with the burner removed) 1. Release the self-tapping screws and remove top panel A. 2. Release the tensioning springs, thermal insulation mat B and mineral fibre mat C.
Initial start-up, inspection and maintenance Further details regarding the individual steps (cont.) Checking the flue gas monitoring equipment 1. Remove the flue pipe from the draught hood. 2. Cover up the flue pipe connector of the draught hood to carry out the function test.
Troubleshooting Diagnostics Fault Cause Remedy The boiler will No voltage Check the fuse and connections of not start the main power supply. Check the switches on the control unit for their settings. Boiler water Wait until the boiler water temperature temperature too high has fallen by approx.
Appendix Function of the ignition burner system The burner control unit is supplied The pressure switches are controlled with current when there is a heat with a switching differential of demand. The control indicator on the < 2 seconds. burner control unit illuminates. The All burner areas are ignited.
Appendix Connection diagram for burner 72 to 96 kW Boiler circuit control unit Burner control unit Ignition cable Gas connection Pilot burner Manifold Manifold GDW 2 GDW 1 Key to symbols 1 Connecting cable Fuel valve modulation coils Modulation coil 2 Connecting cable GDW Gas pressure switch main gas valves...
Appendix Connection diagram for burner 108 to 144 kW Boiler circuit control unit Burner control unit Ignition unit Gas connection BV 1.1 BV 2.1 BV 3.1 BV 1.2 BV 2.2 BV 3.2 MS 1" MS 2" MS 3" Pilot burner Manifold Manifold Manifold...
056 Cover cap 011 R.h. side panel 057 O-ring 25 × 4 mm 012 L.h. side panel 058 Burner (with items 040, 042, 044, 013 Vitogas 100 logo 048, 050, 059 and 065) 014 Diaphragm grommet 059 Thermal insulation panel 015 Closure...
Page 23
Appendix Parts lists (cont.) Parts not shown Wear parts 023 Insulation pack 035 Cleaning brush 038 Gas governor 050 Ignition burner 039 Draught hood pack 051 Gasket set A Type plate intermittent ignition system B Vitotronic, Gkk boiler control 060 Conversion parts for natural unit, see installation and service gas E instructions for the control unit...
Appendix Commissioning/service report Setting and test values Set value Initial start-up Date: Static pressure mbar max. 57.5 mbar Supply pressure (flow pressure) j for natural gas E mbar 17.4 25 mbar j for natural gas LL mbar 17.4 25 mbar j for LPG mbar 42.5 57.7 mbar...
Page 30
Appendix Commissioning/service report (cont.) Setting and test values Set value Maint./service Date: Static pressure mbar max. 57.5 mbar Supply pressure (flow pressure) j for natural gas E mbar 17.4 25 mbar j for natural gas LL mbar 17.4 25 mbar j for LPG mbar 42.5 57.7 mbar...
Page 32
Appendix Commissioning/service report (cont.) Setting and test values Set value Maint./service Date: Static pressure mbar max. 57.5 mbar Supply pressure (flow pressure) j for natural gas E mbar 17.4 25 mbar j for natural gas LL mbar 17.4 25 mbar j for LPG mbar 42.5 57.7 mbar...
This product meets the requirements of the Efficiency Directive (92/42/EEC) for: Low temperature boilers. The product characteristics determined as system values for Vitogas 100 as part of EC type testing according to the Efficiency Directive (see specification table) can be utilised to assess the energy consumption of heating and ventilation equipment to DIN V 4701 10 which is specified by the EnEV.
Need help?
Do you have a question about the Vitogas 100 and is the answer not in the manual?
Questions and answers